Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
RMTK80BD – Converter for thermocouples, Harmony Analog, temperature transmitter, 0…600 degree COr 32…112 degree F
RMTK80BD
Converter for thermocouples, Harmony Analog, temperature transmitter, 0...600 degree COr 32...112 degree F
Specifications
Product Certifications
  • CSA
  • UL
  • GL
Standards
  • IEC 60584-1
  • IEC 60947-1
Ambient Air Temperature For Operation
  • 0-50 °C mounting side by side
  • 0-60 °C 2 cm spacing
Shock Resistance 50 gn 11 ms IEC 60068-2-27
Vibration Resistance 5 gn 10-100 Hz)IEC 60068-2-6
Ip Degree Of Protection
  • IP20 terminal block)
  • IP50 housing)
Disturbance Radiated/Conducted
  • CISPR 11
  • CISPR 22 group 1 - class B
Pollution Degree 2 IEC 60664-1
Ambient Air Temperature For Storage -40-85 °C
Resistance To Electrostatic Discharge
  • 6 kV in contact)IEC 61000-4-2 level 3
  • 8 kV in air)IEC 61000-4-2 level 3
Fire Resistance
  • 850 °C IEC 60695-2-1
  • 850 °C UL
Resistance To Fast Transients
  • 1 kV IEC 61000-4-4 on input-output)
  • 2 kV IEC 61000-4-4 on power supply)
Warranty 18 months
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP1607005EN
Sustainable Offer Status Green Premium product
California Proposition 65 WARNING: This product can expose you to chemicals including: Nickel compounds, which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation X
Circularity Profile ENVEOLI1607005EN
Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)
Current Consumption
  • <= 40 mA voltage output
  • <= 60 mA current output
Safety Reliability Data
  • MTTFd = 49.2 years
  • B10d = 45447
Measurement Error +/- 1 % of full scale 20 °C temporary performance degradation when subject to electromagnetic interference)
Clamping Connection Capacity
  • 1 x 2.5 mm²
  • 2 x 1.5 mm²
Cold Junction Compensation built-in between 0 and 60 °C
[Ui] Rated Insulation Voltage 2 kV
Marking CE
Analogue Output Voltage
  • -15...-11 V no input or input wire broken
  • 11...15 V no input or input wire broken
Net Weight 0.12 kg
Fixing Mode
  • by screws (mounting plate)
  • clip-on (35 mm symmetrical DIN rail)
Surge Withstand 0.5 kV 1.2/50 µs IEC 61000-4-5
Local Signalling for power ON LED (green)
Temperature Coefficient 200 ppm/°C
Protection Type
  • overvoltage protection on output (+/- 30 V)
  • reverse polarity protection on output
  • short-circuit protection on output
Tightening Torque 0.6-1.1 N.m
Analogue Output Current -30-0 mA no input or input wire broken
Repeat Accuracy
  • +/- 0.25 % full scale 20 °C
  • +/- 0.8 % full scale 60 °C
[Us] Rated Supply Voltage 24 V DC +/- 20 %, non isolated
Country of Origin Indonesia
Weight 0.12 kg
Range Of Product Harmony Analog
Analogue Output Type
  • current 0...20 mA <= 500 Ohm
  • current 4...20 mA <= 500 Ohm
  • voltage 0...10 V >= 100 kOhm
Product Or Component Type converter for thermocouples
Analogue Input Type thermocouple 0...600 °C/32...1112 °F thermocouple K IEC 60584
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews