Specifications
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP110717EN
Sustainable Offer Status Green Premium product
China Rohs Regulation Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile ENVEOLI1107017EN
Eu Rohs Directive Compliant with Exemptions
Connections - Terminals cable
Ambient Air Temperature For Operation -10-70 °C
Power Range 11 W
Condition Of Use
  • surrounding environment must be relatively clean
  • filter must be cleaned and replaced regularly
  • flow rates depends on the work point, see ProClima software
  • outside temperature must be 5 °C lower than inside temperature
  • overfrequent filter replacement should be avoided
Maximum Pressure 158 Pa flow rate 0 m³/h
Device Composition
  • 1 axial motor
  • 2 protective grille on the front and rear surfaces
  • 1 filter front of axial motor
  • 1 outlet grille front
  • 1 cut-out template
  • 1 power cord
Net Weight 1.1 kg
Depth external : 103.4 mm
Cut-Out Dimensions 223 x 223 mm
Ambient Air Temperature For Storage -40-70 °C
Width external: 248 mm
Height external: 268 mm
Material outlet grille injected thermoplastic (ASA PC)
Ip Degree Of Protection IP54
Color outlet grille Gray RAL 7035)
Line Rated Current 0.24-0.24 A
Bearing Type ball
Noise Level 55-56 dB
Country of Origin France
Weight 1.1 kg
[Us] Rated Supply Voltage 25...60 V
Air Flow free flow rate with standard filter: 262 m3/h
Type Of Ventilation Filter standard
Product Or Component Type fan
Product Name ClimaSys CV
Range ClimaSys
Input Voltage 48 V DC
Warranty 18 months