Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
NSYCU1K62P4UL – ClimaSys standard cooling unit side of enclosure – 1600W at 400…440 V
NSYCU1K62P4UL
ClimaSys standard cooling unit side of enclosure - 1600W at 400...440 V

ClimaSys CU standard cooling unit side of enclosure. 999 x 405 x 237 mm. 400V to 440V 50Hz or 60Hz. 2 phases. 840W 50Hz or 60Hz L35-L35, 960W 50Hz or 60Hz L35-L50. Flow rate of internal circuit 570 m3/h at 50Hz or 60Hz and for external circuit 1050 m3/h at 50Hz or 60Hz. Control type by electronic controller. Optional external circuit filter. Made in steel grey RAL 7035. Mounting mode by screws. Protection by thermal protection: T 6 A, short-circuit protection (magnetic). IP34 on the internal circuit, IP55 on the external circuit.

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Product Destination for enclosure
Cooling Power
  • 5460 Btu/h 50/60 Hz L35-L35
  • 4200 Btu/h 50/60 Hz L35-L50
Product Or Component Type cooling unit
Product Name CU
Range ClimaSys
Mounting Location side
Mounting Mode by screws
Pressure 25 bar
Air Flow
  • internal circuit 570 m3/h 50/60 Hz
  • external circuit 1050 m3/h 50/60 Hz
Inrush Current 11 A
Protection Type
  • thermal protection T 6 A
  • short-circuit protection (magnetic)
Type Of Ventilation Filter optional external circuit filter
Ambient Air Temperature For Operation
  • maximum 50-50 °C
  • inside the enclosure 20-46 °C
  • outside the enclosure 20-50 °C
Energy Efficiency Ratio 1.9
Material steel
Net Weight 42 kg
Depth 237 mm
Control Type electronic controller
Power Consumption In W
  • 840 W 50/60 Hz, L35-L35
  • 960 W 50/60 Hz, L35-L50
Noise Level 65 dB
Cooling Gas Type R134a 0.45 kg)
Width 405 mm
Height 999 mm
Temperature Setting Range 20-50 °C
Line Rated Current 2.9 A
Color Gray RAL 7035)
Rohs Exemption Information Yes
Mercury Free Yes
Toxic Heavy Metal Free Yes
Reach Regulation Free of Substances of Very High Concern above the threshold
Reach Free Of Svhc Yes
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation Pro-active China RoHS declaration (out of China RoHS legal scope)
Eu Rohs Directive Compliant
Product Certifications UL
Standards DIN 3168
Ip Degree Of Protection
  • IP55 IEC 60529 on the internal circuit)
  • IP34 IEC 60529 on the external circuit)
Documents