Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
LC2D80FE7 – TeSys Deca reversing contactor – 3P(3 NO) – AC-3/AC-3e –
LC2D80FE7
TeSys Deca reversing contactor - 3P(3 NO) - AC-3/AC-3e - <= 440 V 80 A - 115 V AC coil
Specifications
Mechanical Robustness
  • vibrations contactor open2 Gn, 5...300 Hz
  • shocks contactor open8 Gn for 11 ms
  • vibrations contactor closed3 Gn, 5...300 Hz
  • shocks contactor closed10 Gn for 11 ms
Ambient Air Temperature For Operation
  • -40-60 °C
  • 60-70 °C with derating
Height 127 mm
Climatic Withstand IACS E10
Pollution Degree 3
Net Weight 3.2 kg
Flame Retardance V1 conforming to UL 94
Ambient Air Temperature For Storage -60-80 °C
Protective Treatment TH IEC 60068-2-30
Ip Degree Of Protection IP20 front face IEC 60529
Operating Altitude 0...9842.52 ft (0...3000 m)
Fire Resistance 850 °C IEC 60695-2-1
Width 182 mm
Depth 158 mm
Warranty 18 months
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP110205EN
Sustainable Offer Status Green Premium product
Pvc Free Yes
Toxic Heavy Metal Free Yes
California Proposition 65 WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc Yes
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation Pro-active China RoHS declaration (out of China RoHS legal scope)
Circularity Profile N/A
Eu Rohs Directive Compliant
Non-Overlap Time
  • 1.5 ms on de-energisation between NC and NO contact
  • 1.5 ms on energisation between NC and NO contact
Minimum Switching Current 5 mA for signalling circuit
Control Circuit Voltage Limits
  • 0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz
  • 0.8...1.1 Uc -40-55 °C operational AC 50 Hz
  • 0.85...1.1 Uc -40-55 °C operational AC 60 Hz
  • 1...1.1 Uc 55-70 °C operational AC 50/60 Hz
Insulation Resistance > 10 MOhm for signalling circuit
Inrush Power In Va
  • 245-245 VA 60 Hz cos phi 0.75 (at 20 °C)
  • 245-245 VA 50 Hz cos phi 0.75 (at 20 °C)
Coil Technology without built-in suppressor module
Minimum Switching Voltage 17 V for signalling circuit
Signalling Circuit Frequency 25...400 Hz
Auxiliary Contacts Type
  • mechanically linked 1 NO + 1 NC IEC 60947-5-1
  • mirror contact 1 NC IEC 60947-4-1
Hold-In Power Consumption In Va
  • 26-26 VA 60 Hz cos phi 0.3 (at 20 °C)
  • 26-26 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat Dissipation 6-10 W 50/60 Hz
Country of Origin France
Width 182 mm
Height 127 mm
Weight 3.2 kg
Product Certifications
  • UL
  • CSA
  • RINA
  • GOST
  • CCC
  • DNV
  • LROS (Lloyds register of shipping)
  • GL
  • BV
  • UKCA
Interlocking Type mechanical
[Uc] Control Circuit Voltage 115 V AC 50/60 Hz
[Ue] Rated Operational Voltage
  • power circuit <= 690 V AC 25...400 Hz
  • power circuit <= 300 V DC
Power Dissipation Per Pole
  • 12.5 W AC-1
  • 5.1 W AC-3
  • 5.1 W AC-3e
Average Impedance 0.8 mOhm - Ith 125 A 50 Hz for power circuit
Auxiliary Contact Composition 1 NO + 1 NC
[Ith] Conventional Free Air Thermal Current
  • 10 A (at 60 °C) for signalling circuit
  • 125 A (at 60 °C) for power circuit
Mounting Support
  • rail
  • plate
Control Circuit Type AC 50/60 Hz
Standards
  • CSA C22.2 No 14
  • EN 60947-4-1
  • EN 60947-5-1
  • IEC 60947-4-1
  • IEC 60947-5-1
  • UL 508
Safety Reliability Level
  • B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
  • B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Contactor Application
  • resistive load
  • motor control
Rated Breaking Capacity 1100 A at 440 V for power circuit conforming to IEC 60947
Product Or Component Type reversing contactor
Irms Rated Making Capacity
  • 140 A AC for signalling circuit conforming to IEC 60947-5-1
  • 250 A DC for signalling circuit conforming to IEC 60947-5-1
  • 1100 A at 440 V for power circuit conforming to IEC 60947
Product Name TeSys Deca
Associated Fuse Rating
  • 10 A gG for signalling circuit conforming to IEC 60947-5-1
  • 200 A gG at <= 690 V coordination type 1 for power circuit
  • 160 A gG at <= 690 V coordination type 2 for power circuit
[Uimp] Rated Impulse Withstand Voltage 8 kV IEC 60947
Connections - Terminals
  • control circuit screw clamp terminals 1 1-4 mm²flexible without cable end
  • control circuit screw clamp terminals 2 1-4 mm²flexible without cable end
  • control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end
  • control circuit screw clamp terminals 1 1-4 mm²solid
  • control circuit screw clamp terminals 2 1-4 mm²solid
  • control circuit screw clamp terminals 1 1-2.5 mm²flexible with cable end
  • power circuit connector 1 4-50 mm²flexible without cable end
  • power circuit connector 2 4-25 mm²flexible without cable end
  • power circuit connector 1 4-50 mm²flexible with cable end
  • power circuit connector 2 4-16 mm²flexible with cable end
  • power circuit connector 1 4-50 mm²solid
  • power circuit connector 2 4-25 mm²solid
Range TeSys
Pole Contact Composition 3 NO
Device Presentation preassembled with reversing power busbar
Utilisation Category
  • AC-1
  • AC-3
  • AC-3e
  • AC-4
[Ie] Rated Operational Current
  • 125 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
  • 80 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
  • 80 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
  • 55 A (at <60 °C) at <= 400 V AC AC-4 for power circuit
Maximum Operating Rate 3600 cyc/h 60 °C
Tightening Torque
  • control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm
  • control circuit 1.2 N.m screw clamp terminals Philips No 2
  • power circuit 12 N.m connector flat Ø 6 to Ø 8 mm
  • power circuit 12 N.m connector hexagonal 4 mm
  • control circuit 1.2 N.m screw clamp terminals pozidriv No 2
Electrical Durability
  • 0.8 Mcycles 125 A AC-1 <= 440 V
  • 1.5 Mcycles 80 A AC-3 <= 440 V
  • 1.5 Mcycles 80 A AC-3e <= 440 V
Mechanical Durability 4 Mcycles
Poles Description 3P
Operating Time
  • 20...35 ms closing
  • 6...20 ms opening
Overvoltage Category III
Motor Power Kw
  • 22 kW at 220...230 V AC 50 Hz
  • 37 kW at 380...400 V AC 50 Hz
  • 45 kW at 415...440 V AC 50 Hz
  • 55 kW at 500 V AC 50 Hz
  • 45 kW at 660...690 V AC 50 Hz
Maximum Horse Power Rating
  • 20 hp at 200/208 V AC 60 Hz for 3 phase motors
  • 7.5 hp at 115 V AC 60 Hz for 1 phase motors
  • 15 hp at 230/240 V AC 60 Hz for 1 phase motors
  • 25 hp at 230/240 V AC 60 Hz for 3 phase motors
  • 60 hp at 460/480 V AC 60 Hz for 3 phase motors
  • 60 hp at 575/600 V AC 60 Hz for 3 phase motors
[Ui] Rated Insulation Voltage
  • power circuit 600 V CSA
  • power circuit 600 V UL
  • signalling circuit 690 V IEC 60947-1
  • signalling circuit 600 V CSA
  • signalling circuit 600 V UL
  • power circuit 1000 V IEC 60947-4-1
Device Short Name LC2D
[Icw] Rated Short-Time Withstand Current
  • 135 A 40 °C - 10 min for power circuit
  • 320 A 40 °C - 1 min for power circuit
  • 640 A 40 °C - 10 s for power circuit
  • 990 A 40 °C - 1 s for power circuit
  • 100 A - 1 s for signalling circuit
  • 120 A - 500 ms for signalling circuit
  • 140 A - 100 ms for signalling circuit
Protective Cover with
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews