Low voltage power factor correction solution, from VarSet family, helps to eliminate utility penalties. To do energy savings, to lower capital costs, and to reduce CO² emissions by the reactive power compensation of inductive loads. This hardware is compatible with power management software to take advantage of the IoT digital power installation and allow a seemless integration to EcoStruxture Power. Smart monitoring and measurement features are available to secure operations. To optimize perfomance and maintenance, across a broad range of applications, commercial or industrial. This capacitor bank version, suitable for network voltage 480V – 60Hz is providing a reactive power up to 125kvar. The compensation is automatically adjusted by the Power factor controller from VarplusLogic family. It is designed for network harmonic voltage up to 3% or network harmonic current up to 8%. VarSet range is certified to CSA 22.2 No 190 and to UL 811. It is embedding high life expectancy capacitors from Varplus family designed as per IEC831 part 1, IEC831 part 2, UL810. And include a smart controller with modbus communication RS485. The enclosure is floorstanding type with a top entry incoming connection. Frame exterior dimensions are 1000 millimetres in width, 400 millimetres in depth, 1200 millimetres height and a max product weight of 125kg. As a standard, the enclosures are NEMA 1 for indoor application. This product is particularly adapted for power factor correction applications with variable or unstable loads.
Brand: Square D
Add to Quote CataloguePart Number | VLVAW3N66125AA |
---|---|
Availability | N |
Lead Time | 30 |
Discount Schedule | DE2C |
Return Indicator | No |
Depth | 15.7 inch |
Height | 47.24 inch |
Width | 39.37 inch |
Network Rated Voltage | 480 V AC 60 Hz |
---|---|
Reactive Power Rating | 125 kvar |
Operating Mode | Automatic |
Range Of Product | VarSet |
Device Short Name | VarSet standard |
Product Or Component Type | Capacitor bank |
Controller Type | Varplus Logic VPL6 Modbus |
Capacitor Technology | VarPlus Can |
Accessibility For Operation | Front |
Colour | Gray RAL 7035) |
Network Pollution Level | No polluted |
[Thdv] Total Harmonic Distortion | 0…3 % |
Power Per Step | 25 kvar |
Step Composition | 25 + 2x50 |
Location Of Connection | Top |
Internal Voltage Transformer | 480/120 V |
Poles Description | 3P |
Capacitance Tolerance | 5 % to 10 % |
Maximum Permissible Voltage | 1.1 x Un 8 hours over 24 hours) |
Protection Type | Main lug |
Incoming Connection Short Circuit Rating | 25 kA 3 cycles |
Maximum Weight | 275 lb(US) (124.74 kg) 275.58 lb(US) (125 kg) |
Height | 47.24 in (1200 mm) 47.2 in (1198.88 mm) |
Width | 39.37 in (1000 mm) 39.4 in (1000.76 mm) |
Depth | 15.7 in (398.78 mm) 15.75 in (400 mm) |
Mounting Location | Indoor |
Standards | UL 810 CSA C22.2 No 190-M1985 |
Nema Degree Of Protection | NEMA 1 |
Mechanical Degree Of Protection | IK10 |
Relative Humidity | 0…95 % |
Operating Altitude | <= 6561.68 ft (2000 m) |
Ambient Air Temp For Op | 14…104 °F (-10…40 °C) |
Average Ambient Air Temp F Opr | 30 °C annual) |
Category | 00085 - VARSET VLV LV CAP BANK (CTO) |
Discount Schedule | DE2C |
Nbr. Of Units In Pkg. | 1 |
Green Premium Status | Green Premium product |
EU RoHs Directive | Compliant |
Powered by
Based on 2 User Reviews