| Part Number | ATV71HC50Y |
|---|---|
| Country of Origin | CN |
| UPC | 389119215015 |
| UPC11 | 38911921501 |
| EAN | 3389119215015 |
| Availability | N |
| Lead Time | 20 |
| UNSPSC | 26111503 |
| ECCN | EAR99 |
| HTs Code | 8504404000 |
| Prop 65 | This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov |
| RoHS Compliant | Yes |
| Discount Schedule | CP4C |
| Return Indicator | No |
| Depth | 14.84 inch |
| Height | 54.72 inch |
| Width | 44.09 inch |
| Weight | 959.01 pound |
| Range Of Product | Altivar 71 |
|---|---|
| Product Or Component Type | Variable speed drive |
| Product Specific Application | Complex, high-power machines |
| Component Name | ATV71 |
| Motor Power kW | 400 kW, 3 phase 500 V 500 kW, 3 phase 690 V |
| Motor Power Hp | 550 hp, 3 phase 575 V |
| Motor Cable Length | 49.21 ft (15 m) shielded cable 98.43 ft (30 m) unshielded cable |
| Power Supply Voltage | 500...690 V - 15...10 % |
| Network Number Of Phases | 3 phase |
| Line Current | 491 A 600 V 3 phase / 600 hp 498 A 690 V 3 phase 500 kW 544 A 500 V 3 phase 400 kW |
| Emc Filter | Integrated |
| Assembly Style | With heat sink |
| Variant | Reinforced version |
| Prospective Line Isc | 35 kA 3 phase |
| Nominal Output Current | 528 A 2.5 kHz 575 V 3 phase / 600 hp 543 A 2.5 kHz 690 V 3 phase 500 kW 590 A 2.5 kHz 500 V 3 phase 400 kW |
| Max Transient Current | 885 A 60 s 3 phase 400 kW 973.5 A 2 s 3 phase / 600 hp 973.5 A 2 s 3 phase 500 kW |
| Output Frequency | 0.1…500 Hz |
| Nominal Switching Frequency | 2.5 kHz |
| Switching Frequency | 2.5...4.9 kHz adjustable 2.5...4.9 kHz with derating factor |
| Async Motor Control Profile | Flux vector control (FVC) with sensor (current vector) Sensorless flux vector control (SFVC) (voltage or current vector) Voltage/frequency ratio (2 or 5 points) ENA (Energy adaptation) system for unbalanced loads |
| Type Of Polarization | No impedance Modbus |
| Product Destination | Asynchronous motors Synchronous motors |
| Power Supply Voltage Limits | 425…759 V |
| Power Supply Frequency | 50...60 Hz - 5...5 % |
| Power Supply Frequency Limits | 47.5...63 Hz |
| Speed Range | 1…100 asynchronous motor in open-loop mode, without speed feedback 1…1000 asynchronous motor in closed-loop mode with encoder feedback 1…50 synchronous motor in open-loop mode, without speed feedback |
| Speed Accuracy | +/- 0.01 % of nominal speed in closed-loop mode with encoder feedback 0.2 Tn to Tn +/- 10 % of nominal slip without speed feedback 0.2 Tn to Tn |
| Torque Accuracy | +/- 15 % in open-loop mode, without speed feedback +/- 5 % in closed-loop mode with encoder feedback |
| Transient Overtorque | 170 % +/- 10 % 60 s every 10 minutes 220 % +/- 10 % 2 s |
| Braking Torque | <= 150 % with braking or hoist resistor 30 % without braking resistor |
| Sync Motor Control Profile | Vector control without speed feedback |
| Regulation Loop | Adjustable PI regulator |
| Motor Slip Compensation | Suppressable Automatic whatever the load Not available in voltage/frequency ratio (2 or 5 points) Adjustable |
| Diagnostic | Drive voltage 1 LED red) |
| Output Voltage | <= power supply voltage |
| Insulation | Electrical between power and control |
| Type Of Cable For Mounting In An Enclosure | With a NEMA Type1 kit 3 UL 508 cable 104 °F (40 °C), copper 75 °C / PVC With an IP21 or an IP31 kit 3 IEC cable 104 °F (40 °C), copper 70 °C / PVC Without mounting kit 1 IEC cable 113 °F (45 °C), copper 70 °C / PVC Without mounting kit 1 IEC cable 113 °F (45 °C), copper 90 °C / XLPE/EPR |
| Electrical Connection | Terminal 2.5 mm², AWG 14 AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR) Terminal 8 x 185 mm² PC/-, PA/+) Terminal 2 x 4 x 185 mm² R/L1.1, S/L2.1, T/L3.1, R/L1.2, S/L2.2, T/L3.2) Terminal 6 x 185 mm² U/T1, V/T2, W/T3) |
| Tightening Torque | 5.31 lbf.in (0.6 N.m) AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR) 362.88 lbf.in (41 N.m), 360 lb.in PC/-, PA/+) 362.88 lbf.in (41 N.m), 360 lb.in R/L1.1, S/L2.1, T/L3.1, R/L1.2, S/L2.2, T/L3.2) 362.88 lbf.in (41 N.m), 360 lb.in U/T1, V/T2, W/T3) |
| Supply | Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection Internal supply 24 V DC 21…27 V), <200 mA overload and short-circuit protection |
| Analogue Input Number | 2 |
| Analogue Input Type | AI1-/Al1+ bipolar differential voltage +/- 10 V DC 24 V max 11 bits + sign AI2 software-configurable current 0...20 mA 242 Ohm 11 bits AI2 software-configurable voltage 0...10 V DC 24 V max 30000 Ohm 11 bits |
| Input Sampling Time | 2 ms +/- 0.5 ms AI1-/Al1+) - analog 2 ms +/- 0.5 ms Al2) - analog 2 ms +/- 0.5 ms LI1...LI5) - discrete 2 ms +/- 0.5 ms LI6)if configured as logic input - discrete |
| Response Time | <= 100 ms in STO (Safe Torque Off) AO1 2 ms +/- 0.5 ms analog R1A, R1B, R1C 7 ms +/- 0.5 ms discrete R2A, R2B 7 ms +/- 0.5 ms discrete |
| Absolute Accuracy Precision | +/- 0.6 % AI1-/Al1+) for a temperature variation 60 °C +/- 0.6 % AI2) for a temperature variation 60 °C +/- 1 % AO1) for a temperature variation 60 °C |
| Linearity Error | +/- 0.15 % of maximum value AI1-/Al1+, AI2) +/- 0.2 % AO1) |
| Analogue Output Number | 1 |
| Analogue Output Type | AO1 software-configurable logic output 10 V 20 mA AO1 software-configurable current 0...20 mA 500 Ohm 10 bits AO1 software-configurable voltage 0...10 V DC 470 Ohm 10 bits |
| Discrete Output Number | 2 |
| Discrete Output Type | Configurable relay logic R1A, R1B, R1C) NO/NC - 100000 cycles Configurable relay logic R2A, R2B) NO - 100000 cycles |