Part Number | ATV71HD37Y |
---|---|
Country of Origin | FR |
UPC | 785901749165 |
UPC11 | 78590174916 |
EAN | 3389119214896 |
Availability | S |
Lead Time | 21 |
UNSPSC | 39122001 |
ECCN | EAR99 |
HTs Code | 8504404000 |
Prop 65 | This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Discount Schedule | CP4C |
Return Indicator | No |
Depth | 11.42 inch |
Height | 24.80 inch |
Width | 12.60 inch |
Weight | 149.91 pound |
Range Of Product | Altivar 71 |
---|---|
Product Or Component Type | Variable speed drive |
Product Specific Application | Complex, high-power machines |
Component Name | ATV71 |
Motor Power kW | 30 kW, 3 phase 500 V 37 kW, 3 phase 690 V |
Motor Power Hp | 40 hp, 3 phase 575 V |
Motor Cable Length | 32.81 ft (10 m) shielded cable 32.81 ft (10 m) unshielded cable |
Power Supply Voltage | 500...690 V - 15...10 % |
Network Number Of Phases | 3 phase |
Line Current | 41 A 600 V 3 phase / 40 hp 47 A 690 V 3 phase 37 kW 48 A 500 V 3 phase 30 kW |
Emc Filter | Integrated |
Assembly Style | With heat sink |
Variant | Reinforced version |
Prospective Line Isc | 22 kA 3 phase |
Nominal Output Current | 41 A 2.5 kHz 575 V 3 phase / 40 hp 43 A 2.5 kHz 690 V 3 phase 37 kW 47 A 2.5 kHz 500 V 3 phase 30 kW |
Max Transient Current | 70.5 A 60 s 3 phase 30 kW 77.55 A 2 s 3 phase / 40 hp 77.55 A 2 s 3 phase 37 kW |
Output Frequency | 0.1…500 Hz |
Nominal Switching Frequency | 2.5 kHz |
Switching Frequency | 2.5...4.9 kHz adjustable 2.5...4.9 kHz with derating factor |
Async Motor Control Profile | Sensorless flux vector control (SFVC) (voltage or current vector) ENA (Energy adaptation) system for unbalanced loads Flux vector control (FVC) with sensor (current vector) Voltage/frequency ratio (2 or 5 points) |
Type Of Polarization | No impedance Modbus |
Product Destination | Synchronous motors Asynchronous motors |
Power Supply Voltage Limits | 425…759 V |
Power Supply Frequency | 50...60 Hz - 5...5 % |
Power Supply Frequency Limits | 47.5...63 Hz |
Speed Range | 1…100 asynchronous motor in open-loop mode, without speed feedback 1…1000 asynchronous motor in closed-loop mode with encoder feedback 1…50 synchronous motor in open-loop mode, without speed feedback |
Speed Accuracy | +/- 0.01 % of nominal speed in closed-loop mode with encoder feedback 0.2 Tn to Tn +/- 10 % of nominal slip without speed feedback 0.2 Tn to Tn |
Torque Accuracy | +/- 15 % in open-loop mode, without speed feedback +/- 5 % in closed-loop mode with encoder feedback |
Transient Overtorque | 170 % +/- 10 % 60 s every 10 minutes 220 % +/- 10 % 2 s |
Braking Torque | <= 150 % with braking or hoist resistor 30 % without braking resistor |
Sync Motor Control Profile | Vector control without speed feedback |
Regulation Loop | Adjustable PI regulator |
Motor Slip Compensation | Not available in voltage/frequency ratio (2 or 5 points) Suppressable Automatic whatever the load Adjustable |
Diagnostic | Drive voltage 1 LED red) |
Output Voltage | <= power supply voltage |
Insulation | Electrical between power and control |
Type Of Cable For Mounting In An Enclosure | With a NEMA Type1 kit 3 UL 508 cable 104 °F (40 °C), copper 75 °C / PVC With an IP21 or an IP31 kit 3 IEC cable 104 °F (40 °C), copper 70 °C / PVC Without mounting kit 1 IEC cable 113 °F (45 °C), copper 70 °C / PVC Without mounting kit 1 IEC cable 113 °F (45 °C), copper 90 °C / XLPE/EPR |
Electrical Connection | Terminal 2.5 mm², AWG 14 AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR) Terminal 150 mm² L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB) |
Tightening Torque | 5.31 lbf.in (0.6 N.m) AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR) 362.88 lbf.in (41 N.m), 360 lb.in L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB) |
Supply | Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection Internal supply 24 V DC 21…27 V), <200 mA overload and short-circuit protection |
Analogue Input Number | 2 |
Analogue Input Type | AI1-/Al1+ bipolar differential voltage +/- 10 V DC 24 V max 11 bits + sign AI2 software-configurable current 0...20 mA 242 Ohm 11 bits AI2 software-configurable voltage 0...10 V DC 24 V max 30000 Ohm 11 bits |
Input Sampling Time | 2 ms +/- 0.5 ms AI1-/Al1+) - analog 2 ms +/- 0.5 ms Al2) - analog 2 ms +/- 0.5 ms LI1...LI5) - discrete 2 ms +/- 0.5 ms LI6)if configured as logic input - discrete |
Response Time | <= 100 ms in STO (Safe Torque Off) AO1 2 ms +/- 0.5 ms analog R1A, R1B, R1C 7 ms +/- 0.5 ms discrete R2A, R2B 7 ms +/- 0.5 ms discrete |
Absolute Accuracy Precision | +/- 0.6 % AI1-/Al1+) for a temperature variation 60 °C +/- 0.6 % AI2) for a temperature variation 60 °C +/- 1 % AO1) for a temperature variation 60 °C |
Linearity Error | +/- 0.15 % of maximum value AI1-/Al1+, AI2) +/- 0.2 % AO1) |
Analogue Output Number | 1 |
Analogue Output Type | AO1 software-configurable logic output 10 V 20 mA AO1 software-configurable current 0...20 mA 500 Ohm 10 bits AO1 software-configurable voltage 0...10 V DC 470 Ohm 10 bits |
Discrete Output Number | 2 |
Discrete Output Type | Configurable relay logic R1A, R1B, R1C) NO/NC - 100000 cycles Configurable relay logic R2A, R2B) NO - 100000 cycles |