TeSys D time delay auxiliary contact block, for contactors LC1D, LC1F and control relays CAD. It provides 1NO+1NC contacts rated up to 10A 690V AC, On-delay setting range 10-180s, connection by screw clamp terminals. Clip-on front mounting, it procures high reliability and durability. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHs/Reach).

Add to Quote Catalogue
Specifications
Part Number LADT4
Country of Origin FR
UPC 785901213833
UPC11 78590121383
EAN 3389110385977
Availability S
Lead Time 3
UNSPSC 39121529
ECCN EAR99
HTs Code 8538908180
Prop 65 This product can expose you to chemicals including: Diisononyl phthalate (DINP) which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Discount Schedule I12
Return Indicator Yes
Depth 2.40 inch
Height 1.89 inch
Width 1.73 inch
Characteristics
Range TeSys
Range Of Product TeSys D TeSys F
Product Or Component Type Time delay auxiliary contact block
Range Compatibility TeSys D CAD TeSys D LC1D TeSys F LC1F TeSys F CR1F
Mounting Location Front
Pole Contact Composition 1 NO + 1 NC
Contacts Operation Time delay
Timer Type On delay
Time Delay Range 10...180 s
Ue Rated Operational Voltage 690 V AC 25...400 Hz
Ui Rated Insulation Voltage 690 V IEC 60947-5-1 600 V UL 600 V CSA
Ith Cnvtl Free Air Therm Crrt 10 A 140 °F (60 °C)
Standards EN/IEC 60947-5-1 UL 60947-5-1 CSA C22.2 No 60947-5-1 GB/T 14048.5
Product Certifications IECEE CB Scheme UL CSA CCC EAC
Irms Rated Making Capacity 140 A <= 690 V AC IEC 60947-5-1 250 A <= 690 V DC IEC 60947-5-1
Permissible Short-Time Rating 100 A 140 °F (60 °C) 1 s 120 A 140 °F (60 °C) 500 ms 140 A 140 °F (60 °C) 100 ms
Protection Type GG fuse 10 A
Mechanical Durability 5 Mcycles
Minimum Switching Current 5 mA
Minimum Switching Voltage 17 V
Non-Overlap Time 1.5 ms on de-energisation no overlap between NC and NO contact 1.5 ms on energisation no overlap between NC and NO contact
Insulation Resistance > 10 MOhm
Connections - Terminals screw clamp terminals 1 0.00…0.00 in² (1…2.5 mm²)flexible with cable end screw clamp terminals 1 0.00…0.00 in² (1…2.5 mm²)flexible without cable end screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)flexible with cable end screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)flexible without cable end screw clamp terminals 1 0.00…0.00 in² (1…2.5 mm²)solid screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)solid screw clamp terminals
Tightening Torque 15.05 lbf.in (1.7 N.m) flat Ø 6 mm 15.05 lbf.in (1.7 N.m) Philips No 2
Height 1.89 in (48 mm)
Width 1.73 in (44 mm)
Depth 2.40 in (61 mm)
Environmental Characteristic Normal environment
IP Degree Of Protection IP20 IEC 60529
Protective Treatment TH IEC 60068
Ambient Air Temp For Storage -76…176 °F (-60…80 °C)
Ambient Air Temp For Op 23…140 °F (-5…60 °C)
Operating Altitude 9842.52 ft (3000 m)
Category 22341 - CONTACTOR,D,K,&F ACCESS
Discount Schedule I12
GTIN 00785901213833
Nbr. Of Units In Pkg. 1
Country Of Origin FR
Green Premium Status Green Premium product
EU RoHs Directive Compliant
Mercury Free Yes