TeSys LR9F electronic overload relay, thermal setting range 380-630A, selectable class 10-10A-20, for protection of motors 250-355kW@400V. to be mounted directly below a TeSys F 3-pole contactor LC1 F400, F500, F630, F800, use of a support mounting plate LA7F902 is mandatory (to be ordered separately). The motor protection includes thermal overload of 1-phase and 3-phase motors, phase failure, phase unbalance, prolonged starting times, stalled rotor conditions, completed with an overheating alarm function. On the front, the relay provides a thermal adjustement dial, buttons for test, stop & reset, a trip indicator, trip auxiliary contacts 1NO+1NC, and alarm circuit terminals. Multi standards certified (IEC, UL, CSA, CCC, Marine), Green Premium compliant (RoHs/Reach).

Add to Quote Catalogue
Specifications
Part Number LR9F81
Country of Origin FR
UPC 389118057586
UPC11 38911805758
EAN 3389118057586
Availability N
Lead Time 20
UNSPSC 39122330
ECCN EAR99
HTs Code 8536490050
Prop 65 This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Discount Schedule I12
Return Indicator No
Depth 5.02 inch
Height 9.01 inch
Width 7.60 inch
Weight 9.17 pound
Characteristics
Range TeSys
Product Name TeSys LRF
Device Short Name LR9F
Product Or Component Type Electronic thermal overload relay
Relay Application Motor protection
Product Compatibility LC1F800 LC1F400...LC1F630
Network Type AC
Thermal Overload Class Class 10/20 IEC 60947-4
Thermal Protection Adj Range 380…630 A
Signalling Function Pre-alarm indicator
Network Frequency 50/60 Hz
[Us] Rated Supply Voltage 24 V DC
Supply Voltage Limits 17…32 V
Mounting Support Direct on contactor Plate
Tripping Threshold 1.05 +/- 0.06 In alarm IEC 60947-4-1 1.12 +/- 0.06 In tripping IEC 60947-4-1
Surge Withstand 4 kV IEC 61000-4-5
Contacts Type And Composition 1 NO + 1 NC
Ith Cnvtl Free Air Therm Crrt 5 A control circuit
Ue Rated Operational Voltage 1000 V AC 50/60 Hz power circuit VDE 0110 group C
Ui Rated Insulation Voltage Power circuit 1000 V AC IEC 60947-4
Uimp Rated Imp Wstd Voltage 8 kV IEC 60947-1
Phase Failure Sensitivity Tripping in 4 s +/- 20 % IEC 60947-4-1
Reset Manual reset
Control Type Dial White full-load current adjustment Test button Red Push-button reset Push-button Red stop Selector switch load balancing Selector switch class 10/20
Local Signalling Alarm Trip indicator
Temperature Compensation -4…158 °F (-20…70 °C)
Current Consumption <= 5 mA no-load
Switching Capacity For Alarm 0...150 mA
Voltage Drop <2.5 V closed state
Connections - Terminals Control circuit screw clamp terminals 1 0.00…0.00 in² (0.75…2.5 mm²) flexible - with cable end Control circuit screw clamp terminals 1 0.00…0.00 in² (0.75…2.5 mm²) solid Control circuit screw clamp terminals 1 0.00…0.01 in² (0.75…4 mm²) flexible - without cable end Control circuit screw clamp terminals 2 0.00…0.00 in² (1…1.5 mm²) flexible - with cable end Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²) flexible - without cable end Control circuit screw clamp terminals 2 0.00 in² (1 mm²) solid Alarm circuit screw clamp terminals 1 0.00…0.00 in² (0.5…1.5 mm²) flexible - without cable end Power circuit lugs-ring terminals M12
Tightening Torque Control circuit 1.2 N.m screw clamp terminals Alarm circuit 0.45 N.m screw clamp terminals Power circuit 58 N.m screw clamp terminals
Height 9.01 in (228.8 mm)
Width 7.60 in (193 mm)
Depth 5.02 in (127.6 mm)
Product Weight 9.17 lb(US) (4.16 kg)
Standards IEC 60947-4-1 IEC 60255-17 EN 60947-4-1 VDE 0660 IEC 60255-8
Product Certifications CSA UL
Protective Treatment TH
IP Degree Of Protection IP20 IEC 60529
Ambient Air Temp For Op -4…131 °F (-20…55 °C) IEC 60255-8
Ambient Air Temp For Storage -40…185 °F (-40…85 °C)
Operating Altitude <= 6561.68 ft (2000 m) without derating
Fire Resistance 1562 °F (850 °C) IEC 60695-2-1
Mechanical Robustness Shocks13 Gn for 11 ms IEC 60068-2-7 Vibrations 5...300 Hz2 Gn IEC 60068-2-6
Dielectric Strength 6 kV 50 Hz IEC 255-5
Electromagnetic Compatibility Resistance to electrostatic discharge 6 kV in indirect mode IEC 61000-4-2 Resistance to electrostatic discharge 8 kV in air IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test 10 V/m IEC 61000-4-3 Fast transients immunity test 2 kV IEC 61000-4-4