Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
TeSys LRD thermal overload relays – 95…120 A – class 10A
LRD4367
TeSys LRD thermal overload relays – 95…120 A – class 10A

LRD4367 is a TeSys LRD thermal overload relay from Schneider Electric to be used with a TeSys D contactor. It protects motors 55kW@400V thanks to a thermal range 95-120A, a tripping class 10A and phase unbalance protection. LRD4367 is a TeSys LRD thermal overload relay from Schneider Electric for direct mounting on TeSys D contactors. With a thermal setting range 95-120A, a tripping class 10A and phase unbalance detection, it protects motors 55kW@400V. It provides manual test & reset buttons, automatic reset, trip auxiliary contact and flag indicator. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach). Thermal overload protection relay, bimetallic type, with phase unbalance protection (differential). Direct mounting on the bottom terminals of a Tesys contactor LC1D115 and D150 to form a compact starter. Light and compact, 120mm wide. Temperature compensated for a good accuracy of the protection. Manual control with test & reset buttons, manual / automatic reset selector. Trip signaling with 1NO+1NC auxiliary contacts and trip flag indicator. Can be completed with terminal blocks for separate mounting (LAD7B, LAD96) and remote control devices (LAD703, LA7D03).

Add to Quote Catalogue
Specifications
Part Number LRD4367
Country of Origin FR
UPC 785901234470
UPC11 78590123447
EAN 3389110523348
Availability S
Lead Time 3
UNSPSC 39122330
ECCN EAR99
HTs Code 8536490075
Prop 65 This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Discount Schedule I12
Return Indicator Yes
Depth 5.20 inch
Weight 1.98 pound
Characteristics
Range TeSys
Product Name TeSys LRD
Product Or Component Type Differential thermal overload relay
Device Short Name LRD
Relay Application Motor protection
Product Compatibility LC1D150 LC1D115
Network Type AC DC
Thermal Protection Adj Range 95…120 A
Ui Rated Insulation Voltage Power circuit 1000 V IEC 60947-4-1 Power circuit 600 V CSA Power circuit 600 V UL
Network Frequency 0...400 Hz
Mounting Support Plate, with specific accessories Rail, with specific accessories Under contactor
Tripping Threshold 1.14 +/- 0.06 Ir IEC 60947-4-1
Ith Cnvtl Free Air Therm Crrt 5 A signalling circuit
Permissible Current 0.06 A 440 V DC-13 signalling circuit 0.12 A 600 V AC-15 signalling circuit
Ue Rated Operational Voltage 690 V AC 0...400 Hz
Uimp Rated Imp Wstd Voltage 6 kV
Phase Failure Sensitivity Tripping current 130 % of Ir on two phase, the last one at 0
Control Type Red push-button stop Blue push-button reset
Temperature Compensation -4…140 °F (-20…60 °C)
Connections - Terminals Power circuit screw clamp terminals 1 0.01…0.05 in² (4…35 mm²) flexible with cable end Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²) flexible without cable end Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²) flexible with cable end Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²) solid without cable end Power circuit screw clamp terminals 1 0.01…0.08 in² (4…50 mm²) flexible without cable end Power circuit screw clamp terminals 1 0.01…0.08 in² (4…50 mm²) solid without cable end
Tightening Torque Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Power circuit 79.66 lbf.in (9 N.m) screw clamp terminals
Depth 5.20 in (132 mm)
Product Weight 1.98 lb(US) (0.9 kg)
Protective Treatment TH IEC 60068
IP Degree Of Protection IP20 IEC 60529
Ambient Air Temp For Op -4…140 °F (-20…60 °C) without derating IEC 60947-4-1
Ambient Air Temp For Storage -76…158 °F (-60…70 °C)
Flame Retardance V1 UL 94
Mechanical Robustness Vibrations6 Gn IEC 60068-2-6 Shocks15 Gn for 11 ms IEC 60068-2-7
Dielectric Strength 6 kV 50 Hz IEC 60255-5
Standards EN 60947-5-1 IEC 60947-4-1 CSA C22.2 No 14 EN 60947-4-1 ATEX D 94/9/CE IEC 60947-5-1 UL 508
Product Certifications RINA LROS (Lloyds register of shipping) DNV GL CCC UL CSA BV ATEX INERIS GOST
Category 22347 - CONTACTOR,D-LINE,OVERLOADS-NEW
Discount Schedule I12
GTIN 00785901234470
Nbr. Of Units In Pkg. 1
Country Of Origin FR
Green Premium Status Green Premium product
REACh Free Of SVHC Yes
EU RoHs Directive Compliant
Toxic Heavy Metal Free Yes
Mercury Free Yes
Warranty 18 months
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews