TeSys K reversing contactor – 3P – AC-3
LP5K0910EW3
TeSys K reversing contactor – 3P – AC-3
Specifications
Part Number LP5K0910EW3
Country of Origin FR
UPC 389110501841
UPC11 38911050184
EAN 3389110501841
Availability N
Lead Time 20
UNSPSC 39121529
HTs Code 8536410020
Prop 65 This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Discount Schedule I12
Return Indicator No
Depth 2.24 inch
Height 2.28 inch
Width 3.54 inch
Weight 1.08 pound
Characteristics
Range TeSys
Product Name TeSys K
Product Or Component Type Reversing contactor
Device Short Name LP5K
Device Application Control
Contactor Application Resistive load Motor control
Utilisation Category AC-1 AC-4 AC-3
Device Presentation Preassembled with reversing power busbar
Poles Description 3P
Power Pole Contact Composition 3 NO
Ue Rated Operational Voltage Power circuit 690 V AC 50/60 Hz Signalling circuit <= 690 V AC 50/60 Hz
Ie Rated Operational Current 20 A 122 °F (50 °C)) <= 440 V AC AC-1 power circuit 16 A 158 °F (70 °C)) 690 V AC AC-1 power circuit 9 A<= 440 V AC AC-3 power circuit
Motor Power kW 2.2 kW 220...230 V AC 50/60 Hz 4 kW 380...415 V AC 50/60 Hz 4 kW 440 V AC 50/60 Hz 4 kW 480 V AC 50/60 Hz 4 kW 500...600 V AC 50/60 Hz 4 kW 660...690 V AC 50/60 Hz
Control Circuit Type DC low consumption
Uc Control Circuit Voltage 48 V DC
Auxiliary Contact Composition 1 NO
Uimp Rated Imp Wstd Voltage 8 kV
Overvoltage Category III
Ith Cnvtl Free Air Therm Crrt 20 A 122 °F (50 °C) power circuit 10 A 122 °F (50 °C) signalling circuit
Irms Rated Making Capacity 110 A AC power circuit NF C 63-110 110 A AC power circuit IEC 60947 110 A AC signalling circuit IEC 60947
Rated Breaking Capacity 110 A 415 V IEC 60947 110 A 440 V IEC 60947 80 A 500 V IEC 60947 110 A 220...230 V IEC 60947 110 A 380...400 V IEC 60947 70 A 660...690 V IEC 60947
Icw Rated Short-Time Wstd Crrt 90 A 122 °F (50 °C) - 1 s power circuit 85 A 122 °F (50 °C) - 5 s power circuit 80 A 122 °F (50 °C) - 10 s power circuit 60 A 122 °F (50 °C) - 30 s power circuit 45 A 122 °F (50 °C) - 1 min power circuit 40 A 122 °F (50 °C) - 3 min power circuit 80 A - 1 s signalling circuit 90 A - 500 ms signalling circuit 110 A - 100 ms signalling circuit 20 A 122 °F (50 °C) - >= 15 min power circuit
Associated Fuse Rating 25 A gG <= 440 V power circuit 25 A aM power circuit 10 A gG signalling circuit IEC 60947 10 A gG signalling circuit VDE 0660
Average Impedance 3 mOhm - Ith 20 A 50 Hz power circuit
Ui Rated Insulation Voltage Power circuit 600 V UL 508 Power circuit 690 V IEC 60947-4-1 Signalling circuit 690 V IEC 60947-4-1 Signalling circuit 690 V IEC 60947-5-1 Signalling circuit 600 V UL 508 Power circuit 600 V CSA C22.2 No 14 Signalling circuit 600 V CSA C22.2 No 14
Electrical Durability 0.18 Mcycles 20 A AC-1 <= 440 V 1.3 Mcycles 9 A AC-3 <= 440 V
Interlocking Type Mechanical
Mounting Support Plate Rail
Standards IEC 60947 VDE 0660 BS 5424 NF C 63-110
Product Certifications CSA UL
Connections - Terminals screw clamp terminals 1 0.00…0.01 in² (1.5…4 mm²)solid screw clamp terminals 1 0.00…0.01 in² (0.75…4 mm²)flexible without cable end screw clamp terminals 1 0.00…0.00 in² (0.34…2.5 mm²)flexible with cable end screw clamp terminals 2 0.00…0.01 in² (1.5…4 mm²)solid screw clamp terminals 2 0.00…0.01 in² (0.75…4 mm²)flexible without cable end screw clamp terminals 2 0.00…0.00 in² (0.34…1.5 mm²)flexible with cable end
Tightening Torque 11.51 lbf.in (1.3 N.m) screw clamp terminals Philips No 2 11.51 lbf.in (1.3 N.m) screw clamp terminals flat Ø 6 mm
Operating Time 10...20 ms coil de-energisation and NO opening 30...40 ms coil energisation and NO closing
Safety Reliability Level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical Durability 5 Mcycles
Operating Rate 3600 cyc/h
Coil Technology Built-in bidirectional peak limiting diode suppressor
Ctrl Circuit Voltage Limits Operational 0.7...1.30 Uc 122 °F (50 °C)) Drop-out 0.1...0.7 Uc 122 °F (50 °C))
Inrush Power In W 1.8 W 68 °F (20 °C))
Hold-In Power Consumption W 1.8 W 68 °F (20 °C)
Heat Dissipation 1.8 W
Auxiliary Contacts Type Instantaneous 1 NO
Minimum Switching Current 5 mA signalling circuit
Minimum Switching Voltage 17 V signalling circuit
Non Overlap Distance 0.02 in (0.5 mm)
Insulation Resistance > 10 MOhm signalling circuit
IP Degree Of Protection IP20 VDE 0106
Protective Treatment TC IEC 60068 TC DIN 50016
Ambient Air Temp For Op -13…122 °F (-25…50 °C)
Ambient Air Temp For Storage -58…176 °F (-50…80 °C)
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews