TeSys K contactor, 3 poles (3NO), for motor control applications up to 9A/690V AC-3 (4kW@400V), and for non-inductive load control applications up to 20A/690V AC-1. It provides a 380-400V 50/60Hz AC coil, 1NO built-in auxiliary contact, connection by screw clamp terminals. For operating rates until 600 cycles/hour and environments until 50°C, it procures reliability and durability to standard applications. Very compact (45mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).
Add to Quote CataloguePart Number | LC1K0910Q7 |
---|---|
Country of Origin | FR |
UPC | 785901267782 |
UPC11 | 78590126778 |
EAN | 3389110238945 |
Availability | N |
Lead Time | 29 |
UNSPSC | 39121529 |
ECCN | EAR99 |
HTs Code | 8536490065 |
Prop 65 | This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Discount Schedule | I12 |
Return Indicator | No |
Weight | 0.40 pound |
Range | TeSys |
---|---|
Product Or Component Type | Contactor |
Product Name | TeSys K |
Device Application | Control |
Contactor Application | Motor control Resistive load |
Utilisation Category | AC-1 AC-4 AC-3 |
Poles Description | 3P |
Power Pole Contact Composition | 3 NO |
Ie Rated Operational Current | 20 A 122 °F (50 °C)) <= 440 V AC AC-1 power circuit 9 A<= 440 V AC AC-3 power circuit 16 A 158 °F (70 °C)) 690 V AC AC-1 power circuit |
Control Circuit Type | AC 50/60 Hz |
Uc Control Circuit Voltage | 380...400 V AC 50/60 Hz |
Motor Power kW | 2.2 kW 220...230 V AC 50/60 Hz AC-3 4 kW 380...415 V AC 50/60 Hz AC-3 4 kW 440 V AC 50/60 Hz AC-3 4 kW 480 V AC 50/60 Hz AC-3 4 kW 500...600 V AC 50/60 Hz AC-3 4 kW 660...690 V AC 50/60 Hz AC-3 2.2 kW 400 V AC 50/60 Hz AC-4 |
Auxiliary Contact Composition | 1 NO |
Overvoltage Category | III |
Ith Cnvtl Free Air Therm Crrt | 20 A 122 °F (50 °C) power circuit 10 A 122 °F (50 °C) signalling circuit |
Irms Rated Making Capacity | 110 A AC power circuit NF C 63-110 110 A AC power circuit IEC 60947 110 A AC signalling circuit IEC 60947 |
Rated Breaking Capacity | 110 A 415 V IEC 60947 110 A 440 V IEC 60947 80 A 500 V IEC 60947 110 A 220...230 V IEC 60947 110 A 380...400 V IEC 60947 70 A 660...690 V IEC 60947 |
Associated Fuse Rating | 25 A gG <= 440 V power circuit 25 A aM power circuit 10 A gG signalling circuit IEC 60947 10 A gG signalling circuit VDE 0660 |
Average Impedance | 3 mOhm - Ith 20 A 50 Hz power circuit |
Insulation Resistance | > 10 MOhm signalling circuit |
Inrush Power In VA | 30 VA 68 °F (20 °C)) |
Hold-In Power Consumption Va | 4.5 VA 68 °F (20 °C)) |
Heat Dissipation | 1.3 W |
Ctrl Circuit Voltage Limits | Operational 0.8...1.15 Uc 122 °F (50 °C)) Drop-out 0.2...0.75 Uc 122 °F (50 °C)) |
Operating Rate | 3600 cyc/h |
Auxiliary Contacts Type | Instantaneous 1 NO |
Signalling Circuit Frequency | <= 400 Hz |
Minimum Switching Current | 5 mA signalling circuit |
Minimum Switching Voltage | 17 V signalling circuit |
Operating Time | 10...20 ms coil de-energisation and NO opening 10...20 ms coil energisation and NO closing |
Safety Reliability Level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
Non Overlap Distance | 0.02 in (0.5 mm) |
Mechanical Robustness | Shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27 Shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27 Shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 Shocks contactor opened, on X axis6 Gn for 11 ms IEC 60068-2-27 Shocks contactor opened, on Y axis10 Gn for 11 ms IEC 60068-2-27 Shocks contactor opened, on Z axis10 Gn for 11 ms IEC 60068-2-27 Vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6 Vibrations contactor opened2 Gn, 5...300 Hz IEC 60068-2-6 |
Product Weight | 0.40 lb(US) (0.18 kg) |
Standards | BS 5424 IEC 60947 NF C 63-110 VDE 0660 |
Product Certifications | UL CSA |
Protective Treatment | TC IEC 60068 TC DIN 50016 |
Ambient Air Temp For Storage | -58…176 °F (-50…80 °C) |
Operating Altitude | 6561.68 ft (2000 m) without derating |
Flame Retardance | V1 UL 94 Requirement 2 NF F 16-101 Requirement 2 NF F 16-102 |
Category | 22326 - CTR,K-LINE,AC,OPEN,NONREV |
Discount Schedule | I12 |
GTIN | 00785901267782 |
Nbr. Of Units In Pkg. | 1 |
Country Of Origin | FR |
Green Premium Status | Green Premium product |
REACh Free Of SVHC | Yes |
EU RoHs Directive | Compliant |
Toxic Heavy Metal Free | Yes |
Mercury Free | Yes |
Powered by
Based on 2 User Reviews
1619 Boyd St, Santa Ana, CA 92705
(714) 835-6211
(714) 972-2366