                  TeSys K contactor, 3 poles (3NO), for motor control applications up to 9A/690V AC-3 (4kW@400V), and for non-inductive load control applications up to 20A/690V AC-1. It provides a 220V 50/60Hz AC coil, 1NO built-in auxiliary contact, connection by Faston connectors. For operating rates until 600 cycles/hour and environments until 50°C, it procures reliability and durability to standard applications. Very compact (45mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).
Add to Quote Catalogue| Part Number | LC1K09107M7 | 
|---|---|
| Country of Origin | FR | 
| UPC | 785901846963 | 
| UPC11 | 78590184696 | 
| EAN | 3389110490602 | 
| Availability | N | 
| Lead Time | 20 | 
| UNSPSC | 39121529 | 
| ECCN | EAR99 | 
| HTs Code | 8536490065 | 
| Prop 65 | This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov | 
| RoHS Compliant | Yes | 
| Discount Schedule | I12 | 
| Return Indicator | No | 
| Depth | 2.24 inch | 
| Width | 1.77 inch | 
| Weight | 0.40 pound | 
| Range | TeSys | 
|---|---|
| Product Or Component Type | Contactor | 
| Product Name | TeSys K | 
| Device Short Name | LC1K | 
| Device Application | Control | 
| Contactor Application | Motor control Resistive load | 
| Utilisation Category | AC-3 AC-1 AC-4 | 
| Poles Description | 3P | 
| Power Pole Contact Composition | 3 NO | 
| Ue Rated Operational Voltage | Power circuit 690 V AC 50/60 Hz Signalling circuit <= 690 V AC 50/60 Hz | 
| Ie Rated Operational Current | 20 A 122 °F (50 °C)) <= 440 V AC AC-1 power circuit 9 A<= 440 V AC AC-3 power circuit 16 A 158 °F (70 °C)) 690 V AC AC-1 power circuit | 
| Control Circuit Type | AC 50/60 Hz | 
| Uc Control Circuit Voltage | 220...230 V AC 50/60 Hz | 
| Motor Power kW | 2.2 kW 220...230 V AC 50/60 Hz AC-3 4 kW 380...415 V AC 50/60 Hz AC-3 4 kW 440 V AC 50/60 Hz AC-3 4 kW 480 V AC 50/60 Hz AC-3 4 kW 500...600 V AC 50/60 Hz AC-3 4 kW 660...690 V AC 50/60 Hz AC-3 2.2 kW 400 V AC 50/60 Hz AC-4 | 
| Auxiliary Contact Composition | 1 NO | 
| Uimp Rated Imp Wstd Voltage | 8 kV | 
| Overvoltage Category | III | 
| Ith Cnvtl Free Air Therm Crrt | 20 A 122 °F (50 °C) power circuit 10 A 122 °F (50 °C) signalling circuit | 
| Irms Rated Making Capacity | 110 A AC power circuit NF C 63-110 110 A AC power circuit IEC 60947 110 A AC signalling circuit IEC 60947 | 
| Rated Breaking Capacity | 110 A 415 V IEC 60947 110 A 440 V IEC 60947 80 A 500 V IEC 60947 110 A 220...230 V IEC 60947 110 A 380...400 V IEC 60947 70 A 660...690 V IEC 60947 | 
| Icw Rated Short-Time Wstd Crrt | 90 A 122 °F (50 °C) - 1 s power circuit 85 A 122 °F (50 °C) - 5 s power circuit 80 A 122 °F (50 °C) - 10 s power circuit 60 A 122 °F (50 °C) - 30 s power circuit 45 A 122 °F (50 °C) - 1 min power circuit 40 A 122 °F (50 °C) - 3 min power circuit 20 A 122 °F (50 °C) - >= 15 min power circuit 80 A - 1 s signalling circuit 90 A - 500 ms signalling circuit 110 A - 100 ms signalling circuit | 
| Associated Fuse Rating | 25 A gG <= 440 V power circuit 25 A aM power circuit 10 A gG signalling circuit IEC 60947 10 A gG signalling circuit VDE 0660 | 
| Average Impedance | 3 mOhm - Ith 20 A 50 Hz power circuit | 
| Ui Rated Insulation Voltage | Power circuit 600 V UL 508 Power circuit 690 V IEC 60947-4-1 Signalling circuit 690 V IEC 60947-4-1 Signalling circuit 690 V IEC 60947-5-1 Signalling circuit 600 V UL 508 Power circuit 600 V CSA C22.2 No 14 Signalling circuit 600 V CSA C22.2 No 14 | 
| Insulation Resistance | > 10 MOhm signalling circuit | 
| Inrush Power In VA | 30 VA 68 °F (20 °C)) | 
| Hold-In Power Consumption Va | 4.5 VA 68 °F (20 °C)) | 
| Heat Dissipation | 1.3 W | 
| Ctrl Circuit Voltage Limits | Operational 0.8...1.15 Uc 122 °F (50 °C)) Drop-out 0.2...0.75 Uc 122 °F (50 °C)) | 
| Connections - Terminals | Faston terminals 2 2.8 mm Faston terminals 1 6.35 mm | 
| Operating Rate | 3600 cyc/h | 
| Auxiliary Contacts Type | Instantaneous 1 NO | 
| Signalling Circuit Frequency | <= 400 Hz | 
| Minimum Switching Current | 5 mA signalling circuit | 
| Minimum Switching Voltage | 17 V signalling circuit | 
| Mounting Support | Rail Plate | 
| Operating Time | 10...20 ms coil de-energisation and NO opening 10...20 ms coil energisation and NO closing | 
| Safety Reliability Level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 | 
| Non Overlap Distance | 0.02 in (0.5 mm) | 
| Mechanical Durability | 10 Mcycles | 
| Electrical Durability | 0.18 Mcycles 20 A AC-1 <= 440 V 1.3 Mcycles 9 A AC-3 <= 440 V | 
| Mechanical Robustness | Shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27 Shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27 Shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 Shocks contactor opened, on X axis6 Gn for 11 ms IEC 60068-2-27 Shocks contactor opened, on Y axis10 Gn for 11 ms IEC 60068-2-27 Shocks contactor opened, on Z axis10 Gn for 11 ms IEC 60068-2-27 Vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6 Vibrations contactor opened2 Gn, 5...300 Hz IEC 60068-2-6 | 
| Width | 1.77 in (45 mm) | 
| Depth | 2.24 in (57 mm) | 
| Product Weight | 0.40 lb(US) (0.18 kg) | 
| Standards | BS 5424 IEC 60947 NF C 63-110 VDE 0660 | 
| Product Certifications | CSA UL | 
| IP Degree Of Protection | IP2x VDE 0106 | 
| Protective Treatment | TC IEC 60068 TC DIN 50016 | 
| Ambient Air Temp For Storage | -58…176 °F (-50…80 °C) | 