Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
TeSys K changeover contactor – 4P – AC-1
LC2K12004B7
TeSys K changeover contactor – 4P – AC-1

TeSys K changeover contactor, 4 poles (4NO), for non-inductive load control applications up to 20A/690V AC-1. It provides 24V 50/60Hz AC coils, without built-in auxiliary contacts, connection by screw clamp terminals. For operating rates until 600 cycles/hour in AC-3 and environments until 50°C, it procures reliability and durability to standard applications. Compact (90mm width), DIN-rail mounting or screw fixing. With pre-wired changeover power connections, mechanical interlock (without electrical interlocking). Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).

Add to Quote Catalogue
Specifications
Part Number LC2K12004B7
Country of Origin FR
UPC 785901790181
UPC11 78590179018
EAN 3389110225099
Availability N
Lead Time 20
UNSPSC 39121529
ECCN EAR99
HTs Code 8536490065
Prop 65 This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Discount Schedule I12
Return Indicator No
Depth 2.24 inch
Height 2.28 inch
Width 3.54 inch
Weight 0.84 pound
Characteristics
Range TeSys
Product Name TeSys K
Product Or Component Type Changeover contactor
Device Short Name LC2K
Device Application Control
Contactor Application Resistive load
Utilisation Category AC-1
Device Presentation Preassembled with reversing power busbar
Poles Description 4P
Power Pole Contact Composition 4 NO
Ue Rated Operational Voltage Power circuit 690 V AC 50/60 Hz
Ie Rated Operational Current 20 A 122 °F (50 °C)) <= 440 V AC AC-1 power circuit 16 A 158 °F (70 °C)) 690 V AC AC-1 power circuit
Control Circuit Type AC 50/60 Hz
Uc Control Circuit Voltage 24 V AC 50/60 Hz
Uimp Rated Imp Wstd Voltage 8 kV
Overvoltage Category III
Ith Cnvtl Free Air Therm Crrt 20 A 122 °F (50 °C) power circuit
Irms Rated Making Capacity 144 A 690 V AC power circuit NF C 63-110 144 A 690 V AC power circuit IEC 60947
Rated Breaking Capacity 110 A 440 V IEC 60947 80 A 500 V IEC 60947 70 A 660...690 V IEC 60947
Icw Rated Short-Time Wstd Crrt 115 A 122 °F (50 °C) - 1 s power circuit 105 A 122 °F (50 °C) - 5 s power circuit 100 A 122 °F (50 °C) - 10 s power circuit 75 A 122 °F (50 °C) - 30 s power circuit 55 A 122 °F (50 °C) - 1 min power circuit 50 A 122 °F (50 °C) - 3 min power circuit 25 A 122 °F (50 °C) - >= 15 min power circuit
Associated Fuse Rating 25 A gG <= 440 V power circuit 25 A aM power circuit
Average Impedance 3 mOhm - Ith 20 A 50 Hz power circuit
Ui Rated Insulation Voltage Power circuit 600 V UL 508 Power circuit 690 V IEC 60947-4-1 Power circuit 600 V CSA C22.2 No 14
Electrical Durability 0.3 Mcycles 20 A AC-1 <= 440 V
Interlocking Type Mechanical
Mounting Support Rail Plate
Standards NF C 63-110 IEC 60947 BS 5424 VDE 0660
Product Certifications UL CSA
Connections - Terminals screw clamp terminals 1 0.00…0.01 in² (1.5…4 mm²)solid screw clamp terminals 1 0.00…0.01 in² (0.75…4 mm²)flexible without cable end screw clamp terminals 1 0.00…0.00 in² (0.34…2.5 mm²)flexible with cable end screw clamp terminals 2 0.00…0.01 in² (1.5…4 mm²)solid screw clamp terminals 2 0.00…0.01 in² (0.75…4 mm²)flexible without cable end screw clamp terminals 2 0.00…0.00 in² (0.34…1.5 mm²)flexible with cable end
Tightening Torque 11.51 lbf.in (1.3 N.m) screw clamp terminals Philips No 2 11.51 lbf.in (1.3 N.m) screw clamp terminals flat Ø 6 mm
Operating Time 10...20 ms coil energisation and NO closing 10...20 ms coil de-energisation and NO opening
Safety Reliability Level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical Durability 5 Mcycles
Operating Rate 3600 cyc/h
Ctrl Circuit Voltage Limits Operational 0.8...1.15 Uc 122 °F (50 °C)) Drop-out 0.2...0.75 Uc 122 °F (50 °C))
Inrush Power In VA 30 VA 68 °F (20 °C))
Hold-In Power Consumption Va 4.5 VA 68 °F (20 °C))
Heat Dissipation 1.3 W
IP Degree Of Protection IP20 VDE 0106
Protective Treatment TC IEC 60068 TC DIN 50016
Ambient Air Temp For Op -13…122 °F (-25…50 °C)
Ambient Air Temp For Storage -58…176 °F (-50…80 °C)
Operating Altitude 6561.68 ft (2000 m) without derating
Flame Retardance V1 UL 94 Requirement 2 NF F 16-101 Requirement 2 NF F 16-102
Mechanical Robustness Shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27 Shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27 Shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 Shocks contactor opened, on X axis6 Gn for 11 ms IEC 60068-2-27 Shocks contactor opened, on Y axis10 Gn for 11 ms IEC 60068-2-27 Shocks contactor opened, on Z axis10 Gn for 11 ms IEC 60068-2-27 Vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6 Vibrations contactor opened2 Gn, 5...300 Hz IEC 60068-2-6
Height 2.28 in (58 mm)
Width 3.54 in (90 mm)
Depth 2.24 in (57 mm)
Product Weight 0.84 lb(US) (0.38 kg)
Category 22327 - CTR,K-LINE,AC,OPEN,REV