Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
TeSys F contactor – 4P(4 NO)-AC-1
LC1F1854
TeSys F contactor – 4P(4 NO)-AC-1

TeSys F contactor, 4 poles (4NO), 275A/690V AC-1, for non-inductive load applications. Contactor with no coil to allow a later selection and installation (coil to be ordered separately), it provides bolt terminals for bars or cables with lugs. For high operating rates until 2400 cycles/hour and environments until 55°C, it procures high reliability and durability. It makes installation and maintenance easy thanks to a drawer for insertion of the selected coil and a large choice of add-on blocks and accessories (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Add to Quote Catalogue
Specifications
Part Number LC1F1854
Country of Origin CZ
UPC 785901132899
UPC11 78590113289
EAN 3389110122435
Availability N
Lead Time 21
UNSPSC 39121529
ECCN EAR99
HTs Code 8536490065
Prop 65 This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Discount Schedule I12
Return Indicator No
Depth 7.13 inch
Height 6.85 inch
Width 8.21 inch
Weight 12.02 pound
Characteristics
Range TeSys
Product Name TeSys F
Product Or Component Type Contactor
Device Short Name LC1F
Contactor Application Resistive load
Utilisation Category AC-1
Poles Description 4P
Power Pole Contact Composition 4 NO
Ue Rated Operational Voltage <= 690 V AC 50/60 Hz
Ie Rated Operational Current 275 A 104 °F (40 °C)) <= 440 V AC-1
Uc Control Circuit Voltage 24...575 V AC 40...400 Hz with LX9 coil 24...460 V DC with LX4 coil 100...250 V AC 50/60 Hz with LXE coil 100...380 V DC with LXE coil
Uimp Rated Imp Wstd Voltage 8 kV
Overvoltage Category III
Ith Cnvtl Free Air Therm Crrt 275 A 104 °F (40 °C)
Irms Rated Making Capacity 1850 A IEC 60947-4-1
Rated Breaking Capacity 1480 A IEC 60947-4-1
Icw Rated Short-Time Wstd Crrt 1500 A 104 °F (40 °C) - 10 s 920 A 104 °F (40 °C) - 30 s 740 A 104 °F (40 °C) - 1 min 500 A 104 °F (40 °C) - 3 min 400 A 104 °F (40 °C) - 10 min
Associated Fuse Rating 315 A gG <= 440 V
Average Impedance 0.33 mOhm - Ith 275 A 50 Hz
Ui Rated Insulation Voltage 1000 V IEC 60947-4-1 1500 V VDE 0110 group C
Power Dissipation Per Pole 25 W AC-1
Ctrl Circuit Voltage Limits Operational 0.85...1.1 Uc AC 40...400 Hz Drop-out 0.2...0.55 Uc AC 40...400 Hz Operational 0.85...1.1 Uc DC Drop-out 0.15...0.2 Uc DC Operational 85...275 V AC 50/60 Hz Drop-out 0...60 V AC 50/60 Hz Operational 85...418 V DC Drop-out 0...45 V DC
Heat Dissipation 8…9.8 W 2.2…2.5 W
Operating Time 35 ms closing with LX9 coil 130 ms opening with LX9 coil 30...40 ms closing with LX4 coil 30...50 ms opening with LX4 coil 40...80 ms closing with LXE coil 6...54 ms opening with LXE coil
Mounting Support Plate
Standards EN 60947-4-1 IEC 60947-1 EN 60947-1 JIS C8201-4-1 IEC 60947-4-1
Product Certifications ABS CSA DNV BV UL CB RMRoS LROS (Lloyds register of shipping) RINA
Connections - Terminals Power circuit bar 2 25 x 3 mm Power circuit lugs-ring terminals 1 0.23 in² (150 mm²) Power circuit connector 1 0.23 in² (150 mm²) Power circuit bolted connection Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)solid without cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) Control circuit screw clamp terminals 1.0 0.00…0.00 in² (0.2…2.5 mm²)flexible without cable end Control circuit screw clamp terminals 1.0 0.00…0.00 in² (0.25…2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1.0 0.00…0.00 in² (0.2…2.5 mm²)solid without cable end
Tightening Torque Power circuit 159.31 lbf.in (18 N.m) Control circuit 10.62 lbf.in (1.2 N.m) Control circuit 5.31 lbf.in (0.6 N.m)
Mechanical Durability 10 Mcycles
Inrush Power In VA 950…1180 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX9 coil 737…902 VA (at 68 °F (20 °C))with LX4 coil 280…310 VA, 50/60 Hz cos phi 0.5 (at 68 °F (20 °C))with LXE coil 270…320 VA (at 68 °F (20 °C))with LXE coil
Hold-In Power Consumption Va 8.9…10.9 VA 4.13…5.07 VA 4.5…7.0 VA 2.5…4.0 VA
Operating Rate 2400 cyc/h 131 °F (55 °C)
Compatibility Code LC1F
IP Degree Of Protection IP2x front face with shrouds IEC 60529 IP2x front face with shrouds VDE 0106
Protective Treatment TH
Ambient Air Temp For Op 23…131 °F (-5…55 °C)
Ambient Air Temp For Storage -76…176 °F (-60…80 °C)
Ambient Air Temp Around Device -40…158 °F (-40…70 °C)
Mechanical Robustness Vibrations contactor open2 Gn, 5...300 Hz Vibrations contactor closed5 Gn, 5...300 Hz Shocks contactor open7 Gn for 1/2 sine wave (11 ms) Shocks contactor closed15 Gn for 1/2 sine wave (11 ms)
Height 6.85 in (174 mm)
Width 8.21 in (208.5 mm)
Depth 7.13 in (181 mm)
Product Weight 12.02 lb(US) (5.45 kg)
Category 22336 - CTR,F-LINE,AC,OPEN,NONREV
Discount Schedule I12
GTIN 00785901132899
Nbr. Of Units In Pkg. 1
Country Of Origin CZ
Green Premium Status Green Premium product
Documents
Royal Wholesale Electric

5.0

Powered by