TeSys F contactor, 3 poles (3NO), 150A/690V AC-3, for motor applications up to 75kW@400V. It provides a low sealed consumption 220V 40-400Hz AC coil, bolt terminals for bars or cables with lugs. For high operating rates until 2400 cycles/hour and environments until 55°C, it procures high reliability and durability. It makes installation and maintenance easy thanks to its drawer-mounted coil and a large choice of add-on blocks and accessories (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Add to Quote Catalogue
Specifications
Part Number LC1F150M7
Country of Origin CZ
UPC 785901137658
UPC11 78590113765
EAN 3389110350975
Availability N
Lead Time 46
UNSPSC 39121529
ECCN EAR99
HTs Code 8536490065
Prop 65 This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Discount Schedule I12
Return Indicator Yes
Depth 6.73 inch
Height 6.69 inch
Width 6.44 inch
Weight 7.56 pound
Characteristics
Range TeSys
Product Name TeSys F
Product Or Component Type Contactor
Device Short Name LC1F
Contactor Application Resistive load Motor control
Utilisation Category AC-3 AC-1 AC-4
Poles Description 3P
Power Pole Contact Composition 3 NO
Ue Rated Operational Voltage <= 690 V AC 50/60 Hz
Ie Rated Operational Current 250 A 104 °F (40 °C)) <= 440 V AC-1 150 A 131 °F (55 °C)) <= 440 V AC-3
Motor Power kW 75 kW 380...400 V AC 50/60 Hz AC-3) 80 kW 415 V AC 50/60 Hz AC-3) 80 kW 440 V AC 50/60 Hz AC-3) 90 kW 500 V AC 50/60 Hz AC-3) 100 kW 660...690 V AC 50/60 Hz AC-3) 40 kW 220...230 V AC 50/60 Hz AC-3) 22 kW 400 V AC 50/60 Hz AC-4)
Uc Control Circuit Voltage 220 V AC 40...400 Hz
Uimp Rated Imp Wstd Voltage 8 kV
Overvoltage Category III
Ith Cnvtl Free Air Therm Crrt 250 A 104 °F (40 °C)
Rated Breaking Capacity 1200 A IEC 60947-4-1
Icw Rated Short-Time Wstd Crrt 1200 A 104 °F (40 °C) - 10 s 700 A 104 °F (40 °C) - 30 s 600 A 104 °F (40 °C) - 1 min 450 A 104 °F (40 °C) - 3 min 350 A 104 °F (40 °C) - 10 min
Associated Fuse Rating 160 A aM <= 440 V 250 A gG <= 440 V
Average Impedance 0.35 mOhm - Ith 250 A 50 Hz
Ui Rated Insulation Voltage 1000 V IEC 60947-4-1 1500 V VDE 0110 group C
Power Dissipation Per Pole 22 W AC-1 8 W AC-3
Mounting Support Plate
Standards EN 60947-4-1 EN 60947-1 IEC 60947-4-1 JIS C8201-4-1 IEC 60947-1
Product Certifications BV RINA LROS (Lloyds register of shipping) RMRoS ABS CCC CB UL DNV
Connections - Terminals Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)solid without cable end Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)solid without cable end Power circuit bar 2 25 x 3 mm Power circuit lugs-ring terminals 1 0.19 in² (120 mm²) Power circuit connector 1 0.19 in² (120 mm²) Power circuit bolted connection
Tightening Torque Control circuit 10.62 lbf.in (1.2 N.m) Power circuit 159.31 lbf.in (18 N.m)
Ctrl Circuit Voltage Limits Operational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C)) Drop-out 0.35...0.55 Uc 40...400 Hz 131 °F (55 °C))
Inrush Power In VA 770 VA 40...400 Hz 0.9 68 °F (20 °C))
Hold-In Power Consumption Va 8.1 VA 40...400 Hz 0.9 68 °F (20 °C))
Heat Dissipation 5.9…7.2 W
Operating Time 35 ms closing at Uc) 130 ms opening at Uc)
Mechanical Durability 10 Mcycles
Operating Rate 2400 cyc/h 131 °F (55 °C)
Compatibility Code LC1F
IP Degree Of Protection IP2x front face with shrouds IEC 60529 IP2x front face with shrouds VDE 0106
Protective Treatment TH
Ambient Air Temp For Op -40…140 °F (-40…60 °C)
Ambient Air Temp For Storage -76…176 °F (-60…80 °C)
Ambient Air Temp Around Device 140…158 °F (60…70 °C) at Uc
Operating Altitude 9842.52 ft (3000 m) without derating
Height 6.69 in (170 mm)
Width 6.44 in (163.5 mm)
Depth 6.73 in (171 mm)
Product Weight 7.56 lb(US) (3.43 kg)
Category 22336 - CTR,F-LINE,AC,OPEN,NONREV
Discount Schedule I12
GTIN 00785901137658
Nbr. Of Units In Pkg. 1
Country Of Origin CZ
Green Premium Status Green Premium product