Part Number | LC3D320AG7 |
---|---|
Country of Origin | FR |
UPC | 389110508604 |
UPC11 | 38911050860 |
EAN | 3389110508604 |
Availability | N |
Lead Time | 25 |
UNSPSC | 39121529 |
ECCN | EAR99 |
HTs Code | 8536490065 |
Prop 65 | This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Discount Schedule | CP10 |
Return Indicator | No |
Depth | 5.87 inch |
Height | 4.88 inch |
Width | 6.54 inch |
Weight | 4.48 pound |
Range | TeSys |
---|---|
Product Name | TeSys D |
Product Or Component Type | Star delta starter |
Device Short Name | LC3D |
Contactor Application | Motor control |
Utilisation Category | AC-3 |
Device Presentation | Pre-wired |
Poles Description | 3 x 3P |
Power Pole Contact Composition | 3 x 3 NO |
Ue Rated Operational Voltage | Power circuit <= 690 V AC 25...400 Hz |
Ie Rated Operational Current | 32 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit |
Motor Power kW | 15 kW 220/230 V AC 50/60 Hz 25 kW 380/400 V AC 50/60 Hz 30 kW 415 V AC 50/60 Hz 30 kW 440 V AC 50/60 Hz |
Control Circuit Type | AC 50/60 Hz |
Uc Control Circuit Voltage | 120 V 50/60 Hz |
Auxiliary Contact Composition | 1 NC KM1 star contactor |
Uimp Rated Imp Wstd Voltage | 8 kV IEC 60947 |
Overvoltage Category | III |
Ui Rated Insulation Voltage | Power circuit 600 V CSA Power circuit 600 V UL Signalling circuit 600 V CSA Signalling circuit 600 V UL Power circuit 1000 V IEC 60947-4-1 Signalling circuit 1000 V IEC 60947-1 |
Electrical Durability | 1.65 Mcycles 32 A AC-3 <= 440 V |
Safety Cover | Protective cover |
Interlocking Type | Mechanical |
Mounting Support | Rail |
Standards | IEC 60947-5-1 UL 508 EN 60947-4-1 CSA C22.2 No 14 EN 60947-5-1 IEC 60947-4-1 |
Product Certifications | UL GOST LROS (Lloyds register of shipping) RINA DNV CSA CCC BV GL |
Connections - Terminals | Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) flexible without cable end Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) flexible without cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) flexible with cable end Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²) flexible with cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) solid without cable end Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) solid without cable end Power circuit screw clamp terminals 1 0.00…0.02 in² (2.5…10 mm²) flexible without cable end Power circuit screw clamp terminals 2 0.00…0.02 in² (2.5…10 mm²) flexible without cable end Power circuit screw clamp terminals 1 0.00…0.02 in² (1…10 mm²) flexible with cable end Power circuit screw clamp terminals 2 0.00…0.01 in² (1.5…6 mm²) flexible with cable end Power circuit screw clamp terminals 1 0.00…0.02 in² (1.5…10 mm²) solid without cable end Power circuit screw clamp terminals 2 0.00…0.02 in² (2.5…10 mm²) solid without cable end |
Tightening Torque | Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2 Power circuit 22.13 lbf.in (2.5 N.m) screw clamp terminals flat Ø 6 mm Power circuit 22.13 lbf.in (2.5 N.m) screw clamp terminals Philips No 2 |
Mechanical Durability | 15 Mcycles |
Operating Rate | 30 cyc/h 140 °F (60 °C) |
Starting Time | 30 s |
Coil Technology | Without built-in suppressor module |
Ctrl Circuit Voltage Limits | Drop-out 0.3...0.6 Uc 50/60 Hz 140 °F (60 °C)) Operational 0.8...1.1 Uc 50 Hz 140 °F (60 °C)) Operational 0.85...1.1 Uc 60 Hz 140 °F (60 °C)) |
Inrush Power In VA | 70 VA 60 Hz 0.75 68 °F (20 °C)) 70 VA 50 Hz 0.75 68 °F (20 °C)) |
Hold-In Power Consumption Va | 7.5 VA 60 Hz 0.3 68 °F (20 °C)) 7 VA 50 Hz 0.3 68 °F (20 °C)) |
Heat Dissipation | 2…3 W 50/60 Hz |
Auxiliary Contacts Type | Mechanically linked IEC 60947-5-1 3 x 1 NO + 1 NC Mirror contact IEC 60947-4-1 3 x 1 NC |
Signalling Circuit Frequency | 25...400 Hz |
Minimum Switching Current | 5 mA signalling circuit |
Minimum Switching Voltage | 17 V signalling circuit |
Non-Overlap Time | 1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact |
Width | 6.54 in (166 mm) |
Height | 4.88 in (124 mm) |
Depth | 5.87 in (149 mm) |
Product Weight | 4.48 lb(US) (2.03 kg) |
Insulation Resistance | > 10 MOhm signalling circuit |
IP Degree Of Protection | IP2x front face IEC 60529 |
Protective Treatment | TH IEC 60068-2-30 |
Pollution Degree | 3 |
Ambient Air Temp For Storage | -76…176 °F (-60…80 °C) |
Ambient Air Temp For Op | -40…158 °F (-40…70 °C) at Uc |
Operating Altitude | 9842.52 ft (3000 m) without derating |
Powered by