| Part Number | LC3D18AM7 |
|---|---|
| Country of Origin | FR |
| UPC | 389110970678 |
| UPC11 | 38911097067 |
| EAN | 3389110970678 |
| Availability | N |
| Lead Time | 20 |
| UNSPSC | 39121529 |
| ECCN | EAR99 |
| HTs Code | 8536504000 |
| Prop 65 | This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov |
| RoHS Compliant | Yes |
| Discount Schedule | I12 |
| Return Indicator | No |
| Depth | 5.63 inch |
| Height | 4.88 inch |
| Width | 5.67 inch |
| Weight | 3.81 pound |
| Range | TeSys |
|---|---|
| Product Name | TeSys D |
| Product Or Component Type | Star delta starter |
| Device Short Name | LC3D |
| Contactor Application | Motor control |
| Utilisation Category | AC-3 |
| Device Presentation | Pre-wired |
| Poles Description | 3 x 3P |
| Power Pole Contact Composition | 3 x 3 NO |
| Ue Rated Operational Voltage | Power circuit <= 690 V AC 25...400 Hz |
| Ie Rated Operational Current | 18 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit |
| Motor Power kW | 11 kW 220/230 V AC 50/60 Hz 22 kW 415 V AC 50/60 Hz 22 kW 440 V AC 50/60 Hz 18.5 kW 380/400 V AC 50/60 Hz |
| Control Circuit Type | AC 50/60 Hz |
| Uc Control Circuit Voltage | 220 V AC 50/60 Hz |
| Auxiliary Contact Composition | 1 NC KM1 star contactor |
| Uimp Rated Imp Wstd Voltage | 6 kV IEC 60947 |
| Overvoltage Category | III |
| Ui Rated Insulation Voltage | Power circuit 690 V IEC 60947-4-1 Power circuit 600 V CSA Power circuit 600 V UL Signalling circuit 690 V IEC 60947-1 Signalling circuit 600 V CSA Signalling circuit 600 V UL |
| Electrical Durability | 1.65 Mcycles 18 A AC-3 <= 440 V |
| Safety Cover | Protective cover |
| Interlocking Type | Mechanical |
| Mounting Support | Plate |
| Standards | UL 508 IEC 60947-5-1 IEC 60947-4-1 EN 60947-4-1 EN 60947-5-1 CSA C22.2 No 14 |
| Product Certifications | BV RINA CSA LROS (Lloyds register of shipping) CCC UL GL DNV GOST |
| Connections - Terminals | Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) flexible without cable end Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) flexible without cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) flexible with cable end Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²) flexible with cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) solid without cable end Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) solid without cable end Power circuit screw clamp terminals 1 0.00…0.01 in² (1.5…6 mm²) flexible without cable end Power circuit screw clamp terminals 2 0.00…0.01 in² (1.5…6 mm²) flexible without cable end Power circuit screw clamp terminals 1 0.00…0.01 in² (1…6 mm²) flexible with cable end Power circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) flexible with cable end Power circuit screw clamp terminals 1 0.00…0.01 in² (1.5…6 mm²) solid without cable end Power circuit screw clamp terminals 2 0.00…0.01 in² (1.5…6 mm²) solid without cable end |
| Tightening Torque | Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2 Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2 |
| Operating Rate | 30 cyc/h 140 °F (60 °C) |
| Starting Time | 30 s |
| Coil Technology | Without built-in suppressor module |
| Ctrl Circuit Voltage Limits | Drop-out 0.3...0.6 Uc 50/60 Hz 140 °F (60 °C)) Operational 0.8...1.1 Uc 50 Hz 140 °F (60 °C)) Operational 0.85...1.1 Uc 60 Hz 140 °F (60 °C)) |
| Inrush Power In VA | 70 VA 60 Hz 0.75 68 °F (20 °C)) 70 VA 50 Hz 0.75 68 °F (20 °C)) |
| Hold-In Power Consumption Va | 7.5 VA 60 Hz 0.3 68 °F (20 °C)) 7 VA 50 Hz 0.3 68 °F (20 °C)) |
| Heat Dissipation | 2…3 W 50/60 Hz |
| Auxiliary Contacts Type | Mechanically linked IEC 60947-5-1 3 x 1 NO + 1 NC Mirror contact IEC 60947-4-1 3 x 1 NC |
| Signalling Circuit Frequency | 25...400 Hz |
| Minimum Switching Current | 5 mA signalling circuit |
| Minimum Switching Voltage | 17 V signalling circuit |
| Non-Overlap Time | 1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact |
| Width | 5.67 in (144 mm) |
| Height | 4.88 in (124 mm) |
| Depth | 5.63 in (143 mm) |
| Product Weight | 3.81 lb(US) (1.73 kg) |
| Insulation Resistance | > 10 MOhm signalling circuit |
| IP Degree Of Protection | IP20 front face IEC 60529 |
| Protective Treatment | TH IEC 60068-2-30 |
| Pollution Degree | 3 |
| Ambient Air Temp For Storage | -76…176 °F (-60…80 °C) |
| Ambient Air Temp For Op | -40…158 °F (-40…70 °C) at Uc |
| Operating Altitude | 9842.52 ft (3000 m) without derating |
| Fire Resistance | 1562 °F (850 °C) IEC 60695-2-1 |