| Part Number | LC2D40A3G7 |
|---|---|
| Country of Origin | FR |
| UPC | 389118341104 |
| UPC11 | 38911834110 |
| EAN | 3389118341104 |
| Availability | N |
| Lead Time | 22 |
| UNSPSC | 39121529 |
| ECCN | EAR99 |
| HTs Code | 8536490065 |
| Prop 65 | This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov |
| RoHS Compliant | Yes |
| Discount Schedule | I12 |
| Return Indicator | No |
| Depth | 4.72 inch |
| Height | 4.80 inch |
| Width | 4.69 inch |
| Weight | 4.12 pound |
| Range | TeSys |
|---|---|
| Product Name | TeSys D |
| Product Or Component Type | Reversing contactor |
| Device Short Name | LC2D |
| Contactor Application | Motor control Resistive load |
| Utilisation Category | AC-1 AC-3 |
| Device Presentation | Preassembled with reversing power busbar |
| Poles Description | 3P |
| Power Pole Contact Composition | 3 NO |
| Ue Rated Operational Voltage | Power circuit <= 690 V AC 25...400 Hz Power circuit <= 300 V DC |
| Ie Rated Operational Current | 40 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit 60 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit |
| Motor Power kW | 18.5 kW 380...400 V AC 50 Hz 11 kW 220...230 V AC 50 Hz 22 kW 415...440 V AC 50 Hz 22 kW 500 V AC 50 Hz 30 kW 660...690 V AC 50 Hz |
| Motor Power Hp (Ul / Csa) | 5 hp 230/240 V AC 60 Hz 1 phase 10 hp 230/240 V AC 60 Hz 3 phase 30 hp 575/600 V AC 60 Hz 3 phase 10 hp 200/208 V AC 60 Hz 3 phase 3 hp 115 V AC 60 Hz 1 phase 30 hp 460/480 V AC 60 Hz 3 phase |
| Control Circuit Type | AC 60 Hz |
| Uc Control Circuit Voltage | 120 V AC 60 Hz |
| Auxiliary Contact Composition | 1 NO + 1 NC |
| Uimp Rated Imp Wstd Voltage | 6 kV IEC 60947 |
| Overvoltage Category | III |
| Ith Cnvtl Free Air Therm Crrt | 10 A 140 °F (60 °C) signalling circuit 60 A 140 °F (60 °C) power circuit |
| Irms Rated Making Capacity | 140 A AC signalling circuit IEC 60947-5-1 250 A DC signalling circuit IEC 60947-5-1 800 A 440 V power circuit IEC 60947 |
| Rated Breaking Capacity | 800 A 440 V power circuit IEC 60947 |
| Icw Rated Short-Time Wstd Crrt | 72 A 104 °F (40 °C) - 10 min power circuit 165 A 104 °F (40 °C) - 1 min power circuit 320 A 104 °F (40 °C) - 10 s power circuit 720 A 104 °F (40 °C) - 1 s power circuit 100 A - 1 s signalling circuit 120 A - 500 ms signalling circuit 140 A - 100 ms signalling circuit |
| Associated Fuse Rating | 10 A gG signalling circuit IEC 60947-5-1 80 A gG <= 690 V type 1 power circuit 80 A gG <= 690 V type 2 power circuit |
| Average Impedance | 1.5 mOhm - Ith 60 A 50 Hz power circuit |
| Ui Rated Insulation Voltage | Power circuit 690 V IEC 60947-4-1 Power circuit 600 V CSA Power circuit 600 V UL Signalling circuit 690 V IEC 60947-1 Signalling circuit 600 V CSA Signalling circuit 600 V UL |
| Electrical Durability | 1.5 Mcycles 40 A AC-3 <= 440 V 1.4 Mcycles 60 A AC-1 <= 440 V |
| Power Dissipation Per Pole | 2.4 W AC-3 5.4 W AC-1 |
| Front Cover | With |
| Interlocking Type | Mechanical |
| Mounting Support | Plate Rail |
| Standards | CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 |
| Product Certifications | CCC CSA UL GOST |
| Connections - Terminals | Power circuit EverLink BTR screw connectors 1 0.00…0.05 in² (1…35 mm²)flexible without cable end Power circuit EverLink BTR screw connectors 2 0.00…0.04 in² (1…25 mm²)flexible without cable end Power circuit EverLink BTR screw connectors 1 0.00…0.05 in² (1…35 mm²)flexible with cable end Power circuit EverLink BTR screw connectors 2 0.00…0.04 in² (1…25 mm²)flexible with cable end Power circuit EverLink BTR screw connectors 1 0.00…0.05 in² (1…35 mm²)solid Power circuit EverLink BTR screw connectors 2 0.00…0.04 in² (1…25 mm²)solid Control circuit spring terminals 1 0.00…0.00 in² (0.75…2.5 mm²)flexible without cable end Control circuit spring terminals 2 0.00…0.00 in² (0.75…2.5 mm²)flexible without cable end |
| Tightening Torque | Power circuit 70.81 lbf.in (8 N.m) EverLink BTR screw connectors 0.04…0.05 in² (25…35 mm²) hexagonal 0.16 in (4 mm) Power circuit 44.25 lbf.in (5 N.m) EverLink BTR screw connectors 0.00…0.04 in² (1…25 mm²) hexagonal 0.16 in (4 mm) |
| Operating Time | 4...19 ms opening 12...26 ms closing |
| Safety Reliability Level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
| Mechanical Durability | 6 Mcycles |
| Operating Rate | 3600 cyc/h 140 °F (60 °C) |
| Coil Technology | Without built-in suppressor module |
| Ctrl Circuit Voltage Limits | 0.3...0.6 Uc -40…158 °F (-40…70 °C) drop-out AC 60 Hz 0.85...1.1 Uc -40…140 °F (-40…60 °C) operational AC 60 Hz 1...1.1 Uc 140…158 °F (60…70 °C) operational AC 60 Hz |
| Inrush Power In VA | 140 VA 60 Hz 0.75 68 °F (20 °C)) |
| Hold-In Power Consumption Va | 13 VA 60 Hz 0.3 68 °F (20 °C)) |
| Heat Dissipation | 4…5 W 60 Hz |
| Auxiliary Contacts Type | Mechanically linked 1 NO + 1 NC IEC 60947-5-1 Mirror contact 1 NC IEC 60947-4-1 |
| Signalling Circuit Frequency | 25...400 Hz |
| Minimum Switching Current | 5 mA signalling circuit |
| Minimum Switching Voltage | 17 V signalling circuit |
| Non-Overlap Time | 1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact |
| Insulation Resistance | > 10 MOhm signalling circuit |
| Contact Compatibility | M2 |