| Part Number | CAD503EL |
|---|---|
| Country of Origin | FR |
| UPC | 389110820737 |
| UPC11 | 38911082073 |
| EAN | 3389110820737 |
| Availability | N |
| Lead Time | 20 |
| ECCN | EAR99 |
| HTs Code | 8536410060 |
| Prop 65 | This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov |
| RoHS Compliant | Yes |
| Discount Schedule | I12 |
| Return Indicator | No |
| Depth | 3.66 inch |
| Height | 3.90 inch |
| Width | 1.77 inch |
| Weight | 1.28 pound |
| Range | TeSys |
|---|---|
| Product Name | TeSys CAD |
| Product Or Component Type | Control relay |
| Device Short Name | CAD |
| Contactor Application | Control circuit |
| Utilisation Category | DC-13 AC-15 AC-14 |
| Pole Contact Composition | 5 NO |
| Ue Rated Operational Voltage | <= 690 V AC 25...400 Hz |
| Control Circuit Type | DC low consumption |
| Uc Control Circuit Voltage | 48 V DC |
| Uimp Rated Imp Wstd Voltage | 6 kV IEC 60947 |
| Ith Cnvtl Free Air Therm Crrt | 10 A 140 °F (60 °C) |
| Irms Rated Making Capacity | 140 A AC IEC 60947-5-1 250 A DC IEC 60947-5-1 |
| Icw Rated Short-Time Wstd Crrt | 100 A - 1 s 120 A - 500 ms 140 A - 100 ms |
| Associated Fuse Rating | 10 A gG IEC 60947-5-1 |
| Ui Rated Insulation Voltage | 600 V UL 600 V CSA 690 V IEC 60947-5-1 |
| Mounting Support | Rail Plate |
| Connections - Terminals | spring terminals 1 0.00…0.00 in² (1…2.5 mm²)flexible without cable end spring terminals 2 0.00…0.00 in² (1…2.5 mm²)flexible without cable end spring terminals 1 0.00…0.00 in² (1…2.5 mm²)solid without cable end spring terminals 2 0.00…0.00 in² (1…2.5 mm²)solid without cable end |
| Ctrl Circuit Voltage Limits | 0.1...0.25 Uc -40…158 °F (-40…70 °C) drop-out DC 0.7...1.25 Uc -40…140 °F (-40…60 °C) operational DC 1...1.25 Uc 140…158 °F (60…70 °C) operational DC |
| Operating Time | 65...88 ms coil energisation and NO closing 14...25 ms coil de-energisation and NO opening |
| Mechanical Durability | 30 Mcycles |
| Operating Rate | 180 cyc/mn |
| Time Constant | 40 ms |
| Inrush Power In W | 2.4 W 68 °F (20 °C)) |
| Hold-In Power Consumption W | 2.4 W 68 °F (20 °C) |
| Minimum Switching Voltage | 17 V |
| Minimum Switching Current | 5 mA |
| Non-Overlap Time | 1.5 ms on energisation between NC and NO contact 1.5 ms on de-energisation between NC and NO contact |
| Insulation Resistance | > 10 MOhm |
| Mechanical Robustness | Shocks control relay open10 Gn for 11 ms IEC 60068-2-27 Shocks control relay closed15 Gn for 11 ms IEC 60068-2-27 Vibrations control relay open2 Gn, 5...300 Hz IEC 60068-2-6 Vibrations control relay closed4 Gn, 5...300 Hz IEC 60068-2-6 |
| Height | 3.90 in (99 mm) |
| Width | 1.77 in (45 mm) |
| Depth | 3.66 in (93 mm) |
| Product Weight | 1.28 lb(US) (0.58 kg) |
| Standards | BS 4794 EN 60947-5 IEC 60947-5-1 NF C 63-140 VDE 0660 |
| Product Certifications | UL CSA |
| IP Degree Of Protection | IP2x VDE 0106 |
| Protective Treatment | TH IEC 60068 |
| Ambient Air Temp For Op | -40…140 °F (-40…60 °C) 140…158 °F (60…70 °C) with derating |
| Ambient Air Temp For Storage | -76…176 °F (-60…80 °C) |
| Operating Altitude | 0...9842.52 ft (0...3000 m) |
| Category | 22371 - RELAYS, CONTROL |
| Discount Schedule | I12 |
| GTIN | 03389110820737 |
| Nbr. Of Units In Pkg. | 1 |
| Country Of Origin | FR |
| EU RoHs Directive | Compliant |
| Mercury Free | Yes |
| WEEE | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
| Warranty | 18 months |
Powered by ![]()