TeSys D contactor, 4 poles (2NO+2NC), for non-inductive load applications up to 32A/690V AC-1. It provides a 230V 50/60Hz AC coil, 1NO+1NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (45mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Add to Quote Catalogue
Specifications
Part Number LC1D188P7
Country of Origin ID
UPC 389110250046
UPC11 38911025004
EAN 3389110250046
Availability N
Lead Time 46
UNSPSC 39121529
ECCN EAR99
HTs Code 8536490065
Prop 65 This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Discount Schedule I12
Return Indicator No
Depth 3.90 inch
Height 4.13 inch
Width 1.77 inch
Weight 0.94 pound
Characteristics
Range TeSys
Product Name TeSys D
Product Or Component Type Contactor
Device Short Name LC1D
Contactor Application Resistive load
Utilisation Category AC-1
Poles Description 4P
Power Pole Contact Composition 2 NO + 2 NC
Ue Rated Operational Voltage Power circuit <= 690 V AC 25...400 Hz Power circuit <= 300 V DC
Ie Rated Operational Current 32 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit
Control Circuit Type AC 50/60 Hz
Uc Control Circuit Voltage 230 V AC 50/60 Hz
Auxiliary Contact Composition 1 NO + 1 NC
Uimp Rated Imp Wstd Voltage 6 kV IEC 60947
Overvoltage Category III
Ith Cnvtl Free Air Therm Crrt 10 A 140 °F (60 °C) signalling circuit 32 A 140 °F (60 °C) power circuit
Irms Rated Making Capacity 140 A AC signalling circuit IEC 60947-5-1 250 A DC signalling circuit IEC 60947-5-1 300 A 440 V power circuit IEC 60947
Rated Breaking Capacity 300 A 440 V power circuit IEC 60947
Icw Rated Short-Time Wstd Crrt 145 A 104 °F (40 °C) - 10 s power circuit 240 A 104 °F (40 °C) - 1 s power circuit 40 A 104 °F (40 °C) - 10 min power circuit 84 A 104 °F (40 °C) - 1 min power circuit 100 A - 1 s signalling circuit 120 A - 500 ms signalling circuit 140 A - 100 ms signalling circuit
Associated Fuse Rating 10 A gG signalling circuit IEC 60947-5-1 50 A gG <= 690 V type 1 power circuit 35 A gG <= 690 V type 2 power circuit
Average Impedance 2.5 mOhm - Ith 32 A 50 Hz power circuit
Ui Rated Insulation Voltage Power circuit 690 V IEC 60947-4-1 Power circuit 600 V CSA Power circuit 600 V UL Signalling circuit 690 V IEC 60947-1 Signalling circuit 600 V CSA Signalling circuit 600 V UL
Electrical Durability 1 Mcycles 32 A AC-1 <= 440 V
Power Dissipation Per Pole 2.5 W AC-1
Front Cover With
Mounting Support Rail Plate
Standards CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508
Product Certifications RINA GOST CSA CCC UL LROS (Lloyds register of shipping) GL DNV
Connections - Terminals Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)solid without cable end Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)solid without cable end Power circuit connector 1 0.00…0.02 in² (2.5…10 mm²)flexible without cable end Power circuit connector 2 0.00…0.02 in² (2.5…10 mm²)flexible without cable end Power circuit connector 1 0.00…0.02 in² (2.5…10 mm²)flexible with cable end Power circuit connector 2 0.00…0.02 in² (2.5…10 mm²)flexible with cable end Power circuit connector 1 0.00…0.02 in² (2.5…16 mm²)solid without cable end Power circuit connector 2 0.00…0.02 in² (2.5…16 mm²)solid without cable end
Tightening Torque Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2 Power circuit 15.05 lbf.in (1.7 N.m) connector flat Ø 6 mm Power circuit 15.05 lbf.in (1.7 N.m) connector Philips No 2
Operating Time 12...22 ms closing 4...19 ms opening
Safety Reliability Level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical Durability 15 Mcycles
Operating Rate 3600 cyc/h 140 °F (60 °C)
Coil Technology Without built-in suppressor module
Ctrl Circuit Voltage Limits 0.3...0.6 Uc -40…158 °F (-40…70 °C) drop-out AC 50/60 Hz 0.8...1.1 Uc -40…140 °F (-40…60 °C) operational AC 50 Hz 0.85...1.1 Uc -40…140 °F (-40…60 °C) operational AC 60 Hz 1...1.1 Uc 140…158 °F (60…70 °C) operational AC 50/60 Hz
Inrush Power In VA 70 VA 60 Hz 0.75 68 °F (20 °C)) 70 VA 50 Hz 0.75 68 °F (20 °C))
Hold-In Power Consumption Va 7.5 VA 60 Hz 0.3 68 °F (20 °C)) 7 VA 50 Hz 0.3 68 °F (20 °C))
Heat Dissipation 2…3 W 50/60 Hz
Auxiliary Contacts Type Mechanically linked 1 NO + 1 NC IEC 60947-5-1 Mirror contact 1 NC IEC 60947-4-1
Signalling Circuit Frequency 25...400 Hz
Minimum Switching Current 5 mA signalling circuit
Minimum Switching Voltage 17 V signalling circuit
Non-Overlap Time 1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact
Insulation Resistance > 10 MOhm signalling circuit
Contact Compatibility M6
Compatibility Code LC1D
IP Degree Of Protection IP20 front face IEC 60529
Protective Treatment TH IEC 60068-2-30
Pollution Degree 3