LC1D115P7 is a compact 3-pole TeSys D contactor from Schneider Electric for motor applications. Rated 115A AC-3 55kW@400V, it includes a 230V 50/60Hz AC coil and 1NO+1NC auxiliary contacts. It can be used in safety applications. LC1D115P7 is a 3-pole TeSys D contactor from Schneider Electric for motor applications up to 55kW@400V. It includes a 230V 50/60Hz AC coil and 1NO+1NC built-in auxiliary contacts, it can be used in safety applications thanks to its certified NC mirror contact. Compact, DIN-rail mounting, it procures high reliability and durability. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach). Compact product, 120mm wide, for DIN-rail and panel mounting. Clear separation between power and control circuits, easy front access to coil and auxiliary contacts connections. Equipped with a 230V AC coil that can be supplied at 50Hz or 60Hz. Provides 2 built-in auxiliary contacts 1NO + 1NC, NC is a certified mirror contact suitable to be included in the control of safety systems. High electrical durability, guaranteed for 0.9 million cycles at 115A AC-3 440V, for demanding motor switching applications. Robust design with high making and breaking capacities up to 20 In. Connections by screw clamp terminals.
Add to Quote Catalogue| Part Number | LC1D115P7 |
|---|---|
| Country of Origin | CZ |
| UPC | 785901840794 |
| UPC11 | 78590184079 |
| EAN | 3389110377224 |
| Availability | N |
| Lead Time | 33 |
| UNSPSC | 39121529 |
| ECCN | EAR99 |
| HTs Code | 8536490065 |
| Prop 65 | This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov |
| RoHS Compliant | Yes |
| Discount Schedule | I12 |
| Return Indicator | Yes |
| Depth | 5.35 inch |
| Height | 6.22 inch |
| Width | 4.72 inch |
| Weight | 5.51 pound |
| Range | TeSys |
|---|---|
| Product Name | TeSys D |
| Product Or Component Type | Contactor |
| Device Short Name | LC1D |
| Contactor Application | Motor control Resistive load |
| Utilisation Category | AC-1 AC-4 AC-3 |
| Poles Description | 3P |
| Power Pole Contact Composition | 3 NO |
| Ue Rated Operational Voltage | Power circuit <= 1000 V AC 25...400 Hz Power circuit <= 300 V DC |
| Ie Rated Operational Current | 200 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit 115 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit |
| Motor Power kW | 30 kW 220...230 V AC 50/60 Hz AC-3) 55 kW 380...400 V AC 50/60 Hz AC-3) 59 kW 415...440 V AC 50/60 Hz AC-3) 75 kW 500 V AC 50/60 Hz AC-3) 80 kW 660...690 V AC 50/60 Hz AC-3) 65 kW 1000 V AC 50/60 Hz AC-3) 18.5 kW 400 V AC 50/60 Hz AC-4) |
| Motor Power Hp (Ul / Csa) | 30 hp 200/208 V AC 50/60 Hz 3 phase 40 hp 230/240 V AC 50/60 Hz 3 phase 75 hp 460/480 V AC 50/60 Hz 3 phase 100 hp 575/600 V AC 50/60 Hz 3 phase |
| Control Circuit Type | AC 50/60 Hz |
| Uc Control Circuit Voltage | 230 V AC 50/60 Hz |
| Auxiliary Contact Composition | 1 NO + 1 NC |
| Uimp Rated Imp Wstd Voltage | 8 kV IEC 60947 |
| Overvoltage Category | III |
| Ith Cnvtl Free Air Therm Crrt | 200 A 140 °F (60 °C) power circuit |
| Irms Rated Making Capacity | 1260 A 440 V power circuit IEC 60947 140 A AC signalling circuit IEC 60947-5-1 250 A DC signalling circuit IEC 60947-5-1 |
| Rated Breaking Capacity | 1100 A 440 V power circuit IEC 60947 |
| Icw Rated Short-Time Wstd Crrt | 250 A 104 °F (40 °C) - 10 min power circuit 550 A 104 °F (40 °C) - 1 min power circuit 950 A 104 °F (40 °C) - 10 s power circuit 1100 A 104 °F (40 °C) - 1 s power circuit 100 A - 1 s signalling circuit 120 A - 500 ms signalling circuit 140 A - 100 ms signalling circuit |
| Associated Fuse Rating | 250 A gG <= 690 V type 1 power circuit 200 A gG <= 690 V type 2 power circuit 10 A gG signalling circuit |
| Average Impedance | 0.6 mOhm - Ith 200 A 50 Hz power circuit |
| Ui Rated Insulation Voltage | Power circuit 600 V CSA Power circuit 600 V UL Power circuit 1000 V IEC 60947-4-1 Signalling circuit 690 V IEC 60947-1 Signalling circuit 600 V CSA Signalling circuit 600 V UL |
| Electrical Durability | 0.8 Mcycles 200 A AC-1 <= 440 V 0.95 Mcycles 115 A AC-3 <= 440 V |
| Power Dissipation Per Pole | 24 W AC-1 7.9 W AC-3 |
| Front Cover | With |
| Mounting Support | Rail Plate |
| Standards | CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 |
| Product Certifications | LROS (Lloyds register of shipping) RINA DNV GOST BV GL CCC CSA UL |
| Connections - Terminals | Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.00…0.00 in² (1…2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.00…0.00 in² (1…2.5 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.00…0.00 in² (1…2.5 mm²)solid without cable end Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)solid without cable end Power circuit connector 1 0.02…0.19 in² (10…120 mm²)flexible without cable end Power circuit connector 2 0.02…0.08 in² (10…50 mm²)flexible without cable end Power circuit connector 1 0.02…0.19 in² (10…120 mm²)flexible with cable end Power circuit connector 2 0.02…0.08 in² (10…50 mm²)flexible with cable end Power circuit connector 1 0.02…0.19 in² (10…120 mm²)solid without cable end Power circuit connector 2 0.02…0.08 in² (10…50 mm²)solid without cable end |
| Tightening Torque | Control circuit 10.62 lbf.in (1.2 N.m) screw clamp terminals flat Ø 6 mm Control circuit 10.62 lbf.in (1.2 N.m) screw clamp terminals Philips No 2 Power circuit 106.21 lbf.in (12 N.m) connector hexagonal 0.16 in (4 mm) |
| Operating Time | 6...20 ms opening 20...50 ms closing |
| Safety Reliability Level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
| Mechanical Durability | 8 Mcycles |
| Operating Rate | 2400 cyc/h 140 °F (60 °C) |
| Coil Technology | Built-in bidirectional peak limiting diode suppressor |
| Ctrl Circuit Voltage Limits | 0.3...0.5 Uc -40…158 °F (-40…70 °C) drop-out AC 50/60 Hz 0.8...1.15 Uc -40…131 °F (-40…55 °C) operational AC 50/60 Hz 1...1.15 Uc 131…158 °F (55…70 °C) operational AC 50/60 Hz |
| Inrush Power In VA | 280…350 VA 60 Hz 0.8 68 °F (20 °C)) 280…350 VA 50 Hz 0.8 68 °F (20 °C)) |
| Hold-In Power Consumption Va | 2…18 VA 60 Hz 0.3 68 °F (20 °C)) 2…18 VA 50 Hz 0.3 68 °F (20 °C)) |
| Heat Dissipation | 3…8 W 50/60 Hz |
| Auxiliary Contacts Type | Mechanically linked 1 NO + 1 NC IEC 60947-5-1 Mirror contact 1 NC IEC 60947-4-1 |
| Signalling Circuit Frequency | 25...400 Hz |
| Minimum Switching Current | 5 mA signalling circuit |
| Minimum Switching Voltage | 17 V signalling circuit |
| Non-Overlap Time | 1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact |
| Insulation Resistance | > 10 MOhm signalling circuit |
| Contact Compatibility | M13 |
| Compatibility Code | LC1D |
| Motor Power Range | 30…50 kW 200…240 V 3 phase 55…100 kW 380…440 V 3 phase 55…100 kW 480…500 V 3 phase |