| Part Number | LC1D956BD |
|---|---|
| Country of Origin | CZ |
| UPC | 389110453195 |
| UPC11 | 38911045319 |
| EAN | 3389110453195 |
| Availability | N |
| Lead Time | 19 |
| ECCN | EAR99 |
| HTs Code | 8536490065 |
| Prop 65 | This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov |
| RoHS Compliant | Yes |
| Discount Schedule | I12 |
| Return Indicator | No |
| Depth | 7.32 inch |
| Height | 5.00 inch |
| Width | 3.35 inch |
| Weight | 5.75 pound |
| Range | TeSys |
|---|---|
| Product Name | TeSys D |
| Product Or Component Type | Contactor |
| Device Short Name | LC1D |
| Contactor Application | Motor control Resistive load |
| Utilisation Category | AC-3 AC-4 AC-1 |
| Poles Description | 3P |
| Power Pole Contact Composition | 3 NO |
| Ue Rated Operational Voltage | Power circuit 1000 V AC 25...400 Hz |
| Ie Rated Operational Current | 95 A 140 °F (60 °C)) <= 440 V AC-3 power circuit 125 A 140 °F (60 °C)) <= 690 V AC-1 power circuit |
| Motor Power kW | 25 kW 220...230 V AC 50 Hz AC-3) 45 kW 380...400 V AC 50 Hz AC-3) 45 kW 415...440 V AC 50 Hz AC-3) 55 kW 500 V AC 50 Hz AC-3) 45 kW 660...690 V AC 50 Hz AC-3) 45 kW 1000 V AC 50 Hz AC-3) |
| Motor Power Hp (Ul / Csa) | 7.5 hp 115 V AC 60 Hz 1 phase 15 hp 230/240 V AC 60 Hz 1 phase 25 hp 200/208 V AC 60 Hz 3 phase 30 hp 230/240 V AC 60 Hz 3 phase 60 hp 460/480 V AC 60 Hz 3 phase 60 hp 575/600 V AC 60 Hz 3 phase |
| Control Circuit Type | DC standard |
| Uc Control Circuit Voltage | 24 V DC |
| Auxiliary Contact Composition | 1 NO + 1 NC |
| Uimp Rated Imp Wstd Voltage | 8 kV IEC 60947 |
| Overvoltage Category | III |
| Ith Cnvtl Free Air Therm Crrt | 10 A 140 °F (60 °C) signalling circuit 125 A 140 °F (60 °C) power circuit |
| Irms Rated Making Capacity | 1100 A 440 V AC power circuit IEC 60947 140 A AC signalling circuit IEC 60947-5-1 250 A DC signalling circuit IEC 60947-5-1 |
| Rated Breaking Capacity | 1100 A 440 V power circuit IEC 60947 |
| Icw Rated Short-Time Wstd Crrt | 1100 A 104 °F (40 °C) - 1 s power circuit 800 A 104 °F (40 °C) - 10 s power circuit 400 A 104 °F (40 °C) - 1 min power circuit 135 A 104 °F (40 °C) - 10 min power circuit 140 A - 100 ms signalling circuit 120 A - 500 ms signalling circuit 100 A - 1 s signalling circuit |
| Associated Fuse Rating | 10 A gG signalling circuit IEC 60947-5-1 200 A gG <= 690 V type 1 power circuit 160 A gG <= 690 V type 2 power circuit |
| Average Impedance | 0.8 mOhm - Ith 125 A 50 Hz power circuit |
| Ui Rated Insulation Voltage | Power circuit 1000 V IEC 60947-4-1 Signalling circuit 690 V IEC 60947-1 |
| Electrical Durability | 1.2 Mcycles 95 A AC-3 1.3 Mcycles 125 A AC-1 |
| Power Dissipation Per Pole | 12.5 W AC-1 7.2 W AC-3 |
| Front Cover | With |
| Mounting Support | Rail Plate |
| Standards | EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.4 |
| Product Certifications | IECEE CB Scheme CCC EAC LROS (Lloyds register of shipping) RINA BV DNV-GL |
| Connections - Terminals | Control circuit lugs-ring terminals 0.31 in (8 mm)) Power circuit bars 1 3 x 16 mm Power circuit lugs-ring terminals 0.67 in (17 mm)) |
| Tightening Torque | Control circuit 10.62 lbf.in (1.2 N.m) lugs-ring terminals flat Ø 6 mm M3.5 Control circuit 10.62 lbf.in (1.2 N.m) lugs-ring terminals Philips No 2 M3.5 Power circuit 106.21 lbf.in (12 N.m) lugs-ring terminals flat Ø 8 mm M6 Power circuit 106.21 lbf.in (12 N.m) lugs-ring terminals hexagonal 0.39 in (10 mm) M6 Power circuit 106.21 lbf.in (12 N.m) bars flat Ø 8 mm M6 Power circuit 106.21 lbf.in (12 N.m) bars hexagonal 0.39 in (10 mm) M6 |
| Operating Time | 95...130 ms closing 20...35 ms opening |
| Safety Reliability Level | B10d = 1.3 Mcycles contactor with nominal load EN/ISO 13849-1 B10d = 20 Mcycles contactor with mechanical load EN/ISO 13849-1 |
| Mechanical Durability | 10 Mcycles |
| Operating Rate | 3600 cyc/h 140 °F (60 °C) |
| Coil Technology | Without built-in suppressor module |
| Ctrl Circuit Voltage Limits | 0.1...0.3 Uc -40…158 °F (-40…70 °C) drop-out DC 0.85...1.1 Uc -40…131 °F (-40…55 °C) operational DC 1...1.1 Uc 131…158 °F (55…70 °C) operational DC |
| Time Constant | 75 ms |
| Inrush Power In W | 22 W 68 °F (20 °C)) |
| Hold-In Power Consumption W | 22 W 68 °F (20 °C) |
| Auxiliary Contacts Type | Mechanically linked 1 NO + 1 NC IEC 60947-5-1 Mirror contact 1 NC IEC 60947-4-1 |
| Signalling Circuit Frequency | 25...400 Hz |
| Minimum Switching Current | 5 mA signalling circuit |
| Minimum Switching Voltage | 17 V signalling circuit |
| Non-Overlap Time | 1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact |
| Insulation Resistance | > 10 MOhm signalling circuit |
| Contact Compatibility | M9 |
| Compatibility Code | LC1D |
| IP Degree Of Protection | IP20 front face IEC 60529 |