Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
TeSys D contactor – 3P(3 NO) – AC-3 –
LC1D1156F7
TeSys D contactor – 3P(3 NO) – AC-3 –

TeSys D contactor, 3 poles (3NO), for motor control applications up to 115A/1000V AC-3 (55kW@400V). It provides a 110V 50/60Hz AC coil with transient suppressor module, 1NO+1NC built-in auxiliary contacts (NC mirrror contact), power connection for bars or lugs, control connection for lugs. For operating rates until 2400 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (120mm width), mounting on 2 DIN-rails or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Add to Quote Catalogue
Specifications
Part Number LC1D1156F7
Country of Origin CZ
UPC 785901997146
UPC11 78590199714
EAN 3389110380798
Availability N
Lead Time 43
UNSPSC 39121529
ECCN EAR99
HTs Code 8536490065
Prop 65 This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Discount Schedule I12
Return Indicator Yes
Depth 5.35 inch
Height 6.22 inch
Width 4.72 inch
Weight 5.51 pound
Characteristics
Range TeSys
Product Name TeSys D
Product Or Component Type Contactor
Device Short Name LC1D
Contactor Application Motor control Resistive load
Utilisation Category AC-3 AC-1 AC-4
Poles Description 3P
Power Pole Contact Composition 3 NO
Ue Rated Operational Voltage Power circuit <= 1000 V AC 25...400 Hz Power circuit <= 300 V DC
Ie Rated Operational Current 200 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit 115 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit
Motor Power kW 30 kW 220...230 V AC 50/60 Hz AC-3) 55 kW 380...400 V AC 50/60 Hz AC-3) 59 kW 415...440 V AC 50/60 Hz AC-3) 75 kW 500 V AC 50/60 Hz AC-3) 80 kW 660...690 V AC 50/60 Hz AC-3) 65 kW 1000 V AC 50/60 Hz AC-3) 18.5 kW 400 V AC 50/60 Hz AC-4)
Motor Power Hp (Ul / Csa) 30 hp 200/208 V AC 50/60 Hz 3 phase 40 hp 230/240 V AC 50/60 Hz 3 phase 75 hp 460/480 V AC 50/60 Hz 3 phase 100 hp 575/600 V AC 50/60 Hz 3 phase
Control Circuit Type AC 50/60 Hz
Uc Control Circuit Voltage 110 V AC 50/60 Hz
Auxiliary Contact Composition 1 NO + 1 NC
Uimp Rated Imp Wstd Voltage 8 kV IEC 60947
Overvoltage Category III
Ith Cnvtl Free Air Therm Crrt 200 A 140 °F (60 °C) power circuit
Irms Rated Making Capacity 1260 A 440 V power circuit IEC 60947 140 A AC signalling circuit IEC 60947-5-1 250 A DC signalling circuit IEC 60947-5-1
Rated Breaking Capacity 1100 A 440 V power circuit IEC 60947
Icw Rated Short-Time Wstd Crrt 250 A 104 °F (40 °C) - 10 min power circuit 550 A 104 °F (40 °C) - 1 min power circuit 950 A 104 °F (40 °C) - 10 s power circuit 1100 A 104 °F (40 °C) - 1 s power circuit 100 A - 1 s signalling circuit 120 A - 500 ms signalling circuit 140 A - 100 ms signalling circuit
Associated Fuse Rating 250 A gG <= 690 V type 1 power circuit 200 A gG <= 690 V type 2 power circuit 10 A gG signalling circuit
Average Impedance 0.6 mOhm - Ith 200 A 50 Hz power circuit
Ui Rated Insulation Voltage Power circuit 600 V CSA Power circuit 600 V UL Power circuit 1000 V IEC 60947-4-1 Signalling circuit 690 V IEC 60947-1 Signalling circuit 600 V CSA Signalling circuit 600 V UL
Electrical Durability 0.8 Mcycles 200 A AC-1 <= 440 V 0.95 Mcycles 115 A AC-3 <= 440 V
Power Dissipation Per Pole 24 W AC-1 7.9 W AC-3
Front Cover With
Mounting Support Plate Rail
Standards CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508
Product Certifications CCC RINA GOST BV UL DNV LROS (Lloyds register of shipping) CSA GL
Connections - Terminals Control circuit lugs-ring terminals 0.31 in (8 mm)) Power circuit lugs-ring terminals 0.98 in (25 mm)) Power circuit bars 1 5 x 25 mm
Tightening Torque Control circuit 10.62 lbf.in (1.2 N.m) lugs-ring terminals flat Ø 6 mm M3.5 Control circuit 10.62 lbf.in (1.2 N.m) lugs-ring terminals Philips No 2 M3.5 Power circuit 106.21 lbf.in (12 N.m) lugs-ring terminals hexagonal 0.51 in (13 mm) M8 Power circuit 106.21 lbf.in (12 N.m) bars hexagonal 0.51 in (13 mm) M8
Operating Time 6...20 ms opening 20...50 ms closing
Safety Reliability Level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical Durability 8 Mcycles
Operating Rate 2400 cyc/h 140 °F (60 °C)
Coil Technology Built-in bidirectional peak limiting diode suppressor
Ctrl Circuit Voltage Limits 0.3...0.5 Uc -40…158 °F (-40…70 °C) drop-out AC 50/60 Hz 0.8...1.15 Uc -40…131 °F (-40…55 °C) operational AC 50/60 Hz 1...1.15 Uc 131…158 °F (55…70 °C) operational AC 50/60 Hz
Inrush Power In VA 280…350 VA 60 Hz 0.8 68 °F (20 °C)) 280…350 VA 50 Hz 0.8 68 °F (20 °C))
Hold-In Power Consumption Va 2…18 VA 60 Hz 0.3 68 °F (20 °C)) 2…18 VA 50 Hz 0.3 68 °F (20 °C))
Heat Dissipation 3…8 W 50/60 Hz
Auxiliary Contacts Type Mechanically linked 1 NO + 1 NC IEC 60947-5-1 Mirror contact 1 NC IEC 60947-4-1
Signalling Circuit Frequency 25...400 Hz
Minimum Switching Current 5 mA signalling circuit
Minimum Switching Voltage 17 V signalling circuit
Non-Overlap Time 1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact
Insulation Resistance > 10 MOhm signalling circuit
Contact Compatibility M13
Compatibility Code LC1D
IP Degree Of Protection IP20 front face IEC 60529
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews