Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
TeSys D changeover contactor – 4P(4 NO) – AC-1 –
LC2DT20B7
TeSys D changeover contactor – 4P(4 NO) – AC-1 –
Specifications
Part Number LC2DT20B7
Country of Origin FR
UPC 785901610656
UPC11 78590161065
EAN 3389110245158
Availability S
Lead Time 22
UNSPSC 39121529
ECCN EAR99
HTs Code 8536490065
Prop 65 This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Discount Schedule I12
Return Indicator No
Depth 3.54 inch
Height 3.35 inch
Width 3.54 inch
Weight 1.61 pound
Characteristics
Range TeSys
Product Name TeSys D
Product Or Component Type Changeover contactor
Device Short Name LC2D
Contactor Application Resistive load
Utilisation Category AC-1
Device Presentation Preassembled, with prewired power connections
Poles Description 4P
Power Pole Contact Composition 4 NO
Ue Rated Operational Voltage Power circuit <= 690 V AC 25...400 Hz Power circuit <= 300 V DC
Ie Rated Operational Current 20 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit
Control Circuit Type AC 50/60 Hz
Uc Control Circuit Voltage 24 V AC 50/60 Hz
Auxiliary Contact Composition 1 NO + 1 NC
Uimp Rated Imp Wstd Voltage 6 kV IEC 60947
Overvoltage Category III
Ith Cnvtl Free Air Therm Crrt 10 A 140 °F (60 °C) signalling circuit 20 A 140 °F (60 °C) power circuit
Irms Rated Making Capacity 250 A 440 V power circuit IEC 60947 140 A AC signalling circuit IEC 60947-5-1 250 A DC signalling circuit IEC 60947-5-1
Rated Breaking Capacity 250 A 440 V power circuit IEC 60947
Icw Rated Short-Time Wstd Crrt 30 A 104 °F (40 °C) - 10 min power circuit 61 A 104 °F (40 °C) - 1 min power circuit 105 A 104 °F (40 °C) - 10 s power circuit 210 A 104 °F (40 °C) - 1 s power circuit 100 A - 1 s signalling circuit 120 A - 500 ms signalling circuit 140 A - 100 ms signalling circuit
Associated Fuse Rating 25 A gG <= 690 V type 1 power circuit 20 A gG <= 690 V type 2 power circuit 10 A gG signalling circuit IEC 60947-5-1
Average Impedance 2.5 mOhm - Ith 20 A 50 Hz power circuit
Ui Rated Insulation Voltage Power circuit 690 V IEC 60947-4-1 Power circuit 600 V CSA Power circuit 600 V UL Signalling circuit 690 V IEC 60947-1 Signalling circuit 600 V CSA Signalling circuit 600 V UL
Power Dissipation Per Pole 1.56 W AC-1
Front Cover With
Interlocking Type Mechanical
Mounting Support Plate Rail
Standards CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508
Product Certifications CCC CSA RINA UL LROS (Lloyds register of shipping) DNV GL BV GOST
Connections - Terminals Power circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible without cable end Power circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)flexible without cable end Power circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible with cable end Power circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)flexible with cable end Power circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)solid Power circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)solid Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)solid Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)solid
Tightening Torque Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2 Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2
Operating Time 12...22 ms closing 4...19 ms opening
Safety Reliability Level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical Durability 15 Mcycles
Operating Rate 3600 cyc/h 140 °F (60 °C)
Coil Technology Without built-in suppressor module
Ctrl Circuit Voltage Limits 0.3...0.6 Uc -40…158 °F (-40…70 °C) drop-out AC 50/60 Hz 0.8...1.1 Uc -40…140 °F (-40…60 °C) operational AC 50 Hz 0.85...1.1 Uc -40…140 °F (-40…60 °C) operational AC 60 Hz 1...1.1 Uc 140…158 °F (60…70 °C) operational AC 50/60 Hz
Inrush Power In VA 70 VA 60 Hz 0.75 68 °F (20 °C)) 70 VA 50 Hz 0.75 68 °F (20 °C))
Hold-In Power Consumption Va 7.5 VA 60 Hz 0.3 68 °F (20 °C)) 7 VA 50 Hz 0.3 68 °F (20 °C))
Heat Dissipation 2…3 W 50/60 Hz
Auxiliary Contacts Type Mechanically linked 1 NO + 1 NC IEC 60947-5-1 Mirror contact 1 NC IEC 60947-4-1
Signalling Circuit Frequency 25...400 Hz
Minimum Switching Current 5 mA signalling circuit
Minimum Switching Voltage 17 V signalling circuit
Non-Overlap Time 1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact
Insulation Resistance > 10 MOhm signalling circuit
Contact Compatibility M6
Compatibility Code LC2D
IP Degree Of Protection IP20 front face IEC 60529
Protective Treatment TH IEC 60068-2-30
Documents
Royal Wholesale Electric

5.0

Powered by