This Zelio RM35AT control relay allows monitoring of temperature control. This modular control relay is ideal for monitoring of electrical values and temperature variation in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market medium form-factors with 35mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 3-pole DIN device. It also offers a selectable memory function, integral LED for indicating control status, sealable cover, with simple and precise settings with screw trimmers. It provides automatic shutdown management and fault information to user for a quick fault identification and troubleshooting. multi function controller for wide choice selected in hard-wired logic automated systems: ideal for refurbishment of old installations without using a PLC.
Add to Quote CataloguePart Number | RM35ATL0MW |
---|---|
Country of Origin | ID |
UPC | 785901516323 |
UPC11 | 78590151632 |
EAN | 3389119405164 |
Availability | N |
Lead Time | 25 |
UNSPSC | 39122329 |
ECCN | EAR99 |
HTs Code | 8536490075 |
Prop 65 | This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Discount Schedule | CP2 |
Return Indicator | No |
Width | 1.38 inch |
Range Of Product | Zelio Control |
---|---|
Product Or Component Type | Modular measurement and control relays |
Relay Type | Temperature control relays |
Product Specific Application | For elevator machine rooms and 3-phase supplies |
Relay Name | RM35AT |
Relay Monitored Parameters | Undertemperature: -1...11°C Overtemperature: 34...46°C |
Time Delay Range | 0.1...10 s adjustable 0...10 % of the full scale value) |
Switching Capacity In Va | 1250 VA |
Minimum Switching Current | 10 mA 5 V DC |
Power Consumption In Va | 3.5 VA AC |
Utilisation Category | AC-12 IEC 60947-5-1 AC-13 IEC 60947-5-1 AC-14 IEC 60947-5-1 AC-15 IEC 60947-5-1 DC-12 IEC 60947-5-1 DC-13 IEC 60947-5-1 DC-14 IEC 60947-5-1 |
Reset Time | 8 s |
Maximum Switching Voltage | 250 V AC/DC |
Us Rated Supply Voltage | 24...240 V AC/DC |
[Us] Rated Supply Voltage | 24...240 V AC/DC |
Supply Voltage Limits | 20.4…264 V AC 21.6…264 V DC |
Power Consumption In W | 0.6 W DC |
Resistance Across Terminals | 1.33 kOhm temperature |
Width | 1.38 in (35 mm) |
Output Contacts | 1 C/O |
Contacts Material | Cadmium free |
Nominal Output Current | 5 A |
Delay At Power Up | 0.2 s |
Measurement Accuracy | +/- 2 °C |
Response Time | <= 3.5 s + Tt in case of temperature fault) <= 3.5 s on disappearance of fault) |
Temperature Probe Type | Pt 100 - 3-wire |
Installed Device | Pt 100 probe cable length <= 10 m |
Marking | CE : EMC 89/336/EEC CE : 73/23/EEC |
Overvoltage Category | III IEC 60664-1 |
Insulation Resistance | > 500 MOhm 500 V DC between supply and relay output IEC 60255-5 > 500 MOhm 500 V DC between measurement and relay output IEC 60664-1 > 1 MOhm 500 V DC between supply and measurement IEC 60255-5 > 500 MOhm 500 V DC between supply and relay output IEC 60664-1 > 500 MOhm 500 V DC between measurement and relay output IEC 60255-5 > 1 MOhm 500 V DC between supply and measurement IEC 60664-1 |
Ui Rated Insulation Voltage | 250 V IEC 60664-1 |
Operating Voltage Tolerance | 10 % + 10 % Un DC - 15 % + 10 % Un AC |
Supply Frequency | 50/60 Hz +/- 10 % |
Insulation | Galvanic insulation between supply and measurement |
Operating Position | Any position without derating |
Connections - Terminals | Screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end Screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end |
Tightening Torque | 5.31…8.85 lbf.in (0.6…1 N.m) IEC 60947-1 |
Housing Material | Self-extinguishing plastic |
Local Signalling | 1 LED Green power ON 1 LED Yellow correct temperature (high R1) 1 LED Yellow correct temperature (low R2) |
Mounting Support | 35 mm symmetrical DIN rail EN/IEC 60715 |
Electrical Durability | 100000 cycles |
Mechanical Durability | 30000000 cycles |
Operating Rate | <= 360 operations/hour full load |
Immunity To Microbreaks | 10 ms |
Electromagnetic Compatibility | Emission standard for industrial environments EN/IEC 61000-6-4 Emission standard for residential, commercial and light-industrial environments EN/IEC 61000-6-3 Immunity for industrial environments NF EN/IEC 61000-6-2 |
Standards | IEC 60255-6 NF EN 60255-6 |
Product Certifications | GOST GL C-tick UL CSA |
Ambient Air Temp For Storage | -40…158 °F (-40…70 °C) |
Ambient Air Temp For Op | -4…122 °F (-20…50 °C) |
Vibration Resistance | 0.35 mm 5…57.6 Hz)IEC 60068-2-6/IEC 60255-21-1 1 gn 57.6…150 Hz)IEC 60068-2-6/IEC 60255-21-1 |