Part Number | SY10K40F |
---|---|
Prop 65 | This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov |
Depth | 35.51 inch |
Height | 81.50 inch |
Width | 23.62 inch |
Weight | 896.89 pound |
Presentation | A high-efficiency 3-phase UPS that is scaleable as your data center grows up to 40KW/40KVA. Suitable for small to medium data center application. |
---|---|
Lead Time | Usually Ships within 3 Weeks |
Provided Equipment | Network Management Card Start up included User Manual |
Bypass Wiring Configuration | 5 wire (3PH + N + G) |
Max Bypass Input Current | 162 A |
Bypass Current Protection | 175 A |
Colour | Black |
Depth | 35.51 in (90.2 cm) |
Height | 81.50 in (207 cm) |
Product Weight | 896.89 lb(US) (406.82 kg) |
Width | 23.62 in (60 cm) |
Network Frequency | 50/60 Hz |
Number Of Input Connectors | 1 Hard Wire 5-wire (3PH + N + G) |
Input Voltage Limits | 177...240 V |
Maximum Input Current | 162 A |
Switching Current Capacity | 175 A |
Max Short Time Withstd Current | 30 kA |
Input Protection Type | 3-pole breaker |
Input Voltage | 3 phase |
Rated Power In W | 10000 W |
Max Configurable Power In W | 40000 W |
Harmonic Distortion | Less than 5% |
Output Frequency | 57...63 Hz for 60 Hz nominal sync to mains 60 Hz +/- 0.1 % for 60 Hz nominal not synced |
Ups Type | Double Conversion Online |
Wave Type | Sine wave |
Connections - Terminals | 1 screw terminals |
Output Connector Type | Hard Wire 5-wire (3PH + N + G) 1 |
Output Voltage Tolerance | +/-1% static and +/- 5% at 100% load step |
Output Harmonic Distortion | < 2% for 0 to 100% linear load and < 5% for full non-linear load |
Output Overload Operation | 60 seconds @ 125% and 30 seconds @ 150% |
Req Output Current Protection | 150 A |
Bypass Type | Built-in Static Bypass |
Output Voltage | 120 V 208 V 208 V 3 phase |
Product Certifications | CUL Listed |
Standards | CSA C22.2 No.107.3-05 EN 50091-1 EN 50091-2 EN 50091-3 FCC Part 15 class A ISO 14001 ISO 9001 UL 1778 UL 60950 |
Ambient Air Temp For Op | 32…104 °F (0…40 °C) |
Relative Humidity | 0…95 % |
Operating Altitude | 0...10000 ft |
Ambient Air Temp For Storage | 5…104 °F (-15…40 °C) |
Storage Altitude | 0…50000 ft (0.00…15240.00 m) |
Acoustic Level | 64 dBA |
Heat Dissipation | 3381 Btu/h |
Nema Degree Of Protection | NEMA 1 |
Battery Type | Lead-Acid battery |
Number Of Battery Filled Slots | 1 |
Number Of Battery Free Slots | 3 |
Battery Recharge Time | 2 h |
Number Of Battery Repl Qty | 1 |
Battery Voltage | +/-192 V (split battery referenced to neutral) |
Powered by
Based on 2 User Reviews
1619 Boyd St, Santa Ana, CA 92705
(714) 835-6211
(714) 972-2366