This Altistart 48 soft start/soft stop unit is a controller with 6 thyristors used for torque-controlled soft starting and stopping of three-phase asynchronous motors. It offers soft starting and deceleration functions along with machine and motor protection functions, as well as functions for communicating with control systems. It works at a rated supply voltage from 208V to 690V AC and up to 1000A rating. Altistart 48 torque control enables starting without mechanical stress and smooth control of hydraulic transitions, with a single acceleration ramp making adjustments is quick and easy, whatever the load. It is suitable for motors with power rating up to 1000hp (at 575V) / 900kW (at 690V) for standards applications and 800hp (at 575V) / 710kW (at 690V) for severe applications. It weighs 115kg and its dimensions are, 770mm wide, 890mm high, 315mm deep. It is designed for use in the most common applications for centrifugal machines, pumps, fans, compressors and conveyors, which are primarily to be found in the construction, food and beverage and chemical industries. It complies with IEC/EN 60947-4-2 standard and is certified CE, UL, CSA, DNV, C-Tick, GOST, CCC, NOM, SEPRO, and TCF. The Altistart 48 is connected directly to the Modbus bus via its RJ45 connector port, It can also be connected to Ethernet, Fipio, Profibus DP and DeviceNet networks via a module (bridge or gateway) to order separately. It is designed to be mounted in vertical position (+/- 10 °) on a panel, thanks to 4 fixing holes. Altistart 48 delivers high performance with its Torque Control System (TCS) for controlled starting and deceleration, an easy integration in enclosures and control systems. This range provides also continual improvement of your machine operation by reducing mechanical or hydraulic stress and limiting energy loss and temperature rise, plus more.
Brand: Telemecanique
Add to Quote CataloguePart Number | ATS48M10Y |
---|---|
Country of Origin | FR |
UPC | 785901982562 |
UPC11 | 78590198256 |
EAN | 3389110982565 |
Availability | N |
Lead Time | 20 |
UNSPSC | 39121521 |
ECCN | EAR99 |
HTs Code | 8504404000 |
Prop 65 | This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Discount Schedule | CP1G |
Return Indicator | No |
Depth | 12.40 inch |
Height | 35.04 inch |
Width | 30.31 inch |
Weight | 253.53 pound |
Range Of Product | Altistart 48 |
---|---|
Product Or Component Type | Soft starter |
Product Destination | Asynchronous motors |
Product Specific Application | Heavy duty industry and pumps |
Device Short Name | ATS48 |
Power Supply Voltage | 208...690 V - 15...10 % |
Motor Power kW | 220 kW 230 V for severe applications 250 kW 230 V for standard applications 400 kW 400 V for severe applications 500 kW 400 V for standard applications 500 kW 440 V for severe applications 500 kW 500 V for severe applications 500 kW 525 V for severe applications 630 kW 440 V for standard applications 630 kW 500 V for standard applications 630 kW 525 V for standard applications 710 kW 660 V for severe applications 710 kW 690 V for severe applications 900 kW 660 V for standard applications 900 kW 690 V for standard applications |
Motor Power Hp | 1000 hp 575 V for standard applications 250 hp 208 V for severe applications 300 hp 230 V for severe applications 350 hp 208 V for standard applications 350 hp 230 V for standard applications 600 hp 460 V for severe applications 800 hp 460 V for standard applications 800 hp 575 V for severe applications |
Power Dissipation In W | 2225 W for standard applications 2865 W for standard applications |
Utilisation Category | AC-53A |
Type Of Start | Start with torque control (current limited to 5 In) |
Icl Nominal Current | 1000 A connection in the motor supply line for standard applications 1000 A connection in the motor supply line for severe applications |
IP Degree Of Protection | IP00 |
Assembly Style | With heat sink |
Function Available | External bypass (optional) |
Power Supply Voltage Limits | 177…759 V |
Power Supply Frequency | 50...60 Hz - 5...5 % |
Power Supply Frequency Limits | 47.5...63 Hz |
Device Connection | In the motor supply line |
Factory Setting Current | 954 A |
Uc Control Circuit Voltage | 110 - 15 % to 230 + 10 %, 50/60 Hz |
Control Circuit Consumption | 80 W |
Discrete Output Number | 2 |
Discrete Output Type | LO1) logic output 0 V common configurable LO2) logic output 0 V common configurable R1) relay outputs fault relay NO R2) relay outputs end of starting relay NO R3) relay outputs motor powered NO |
Output Abs Accuracy Precision | +/- 5 % |
Minimum Switching Current | 10 mA 6 V DC relay outputs |
Maximum Switching Current | Logic output 0.2 A 30 V DC Relay outputs 1.8 A 230 V AC inductive, cos phi = 0.5 20 ms Relay outputs 1.8 A 30 V DC inductive, cos phi = 0.5 20 ms |
Discrete Input Number | 5 |
Discrete Input Type | PTC, 750 Ohm 77 °F (25 °C) Stop, Run, LI3, LI4) logic, <= 8 mA 4300 Ohm |
Discrete Input Voltage | 24 V <= 30 V |
Discrete Input Logic | Positive logic Stop, Run, LI3, LI4 < 5 V <= 2 mA > 11 V, >= 5 mA |
Starting Current | 0.4...1.3 Icl adjustable |
Analogue Output Type | Current output AO 0-20 mA or 4-20 mA 500 Ohm |
Communication Port Protocol | Modbus |
Connector Type | 1 RJ45 |
Communication Data Link | Serial |
Physical Interface | RS485 multidrop |
Transmission Rate | 4800, 9600 or 19200 bps |
Max Nodes Number | 31 |
Protection Type | Phase failure line Thermal protection motor Thermal protection starter |
Marking | CE |
Type Of Cooling | Forced convection |
Operating Position | Vertical +/- 10 degree |
Height | 35.04 in (890 mm) |
Width | 30.31 in (770 mm) |
Depth | 12.40 in (315 mm) |
Product Weight | 253.53 lb(US) (115 kg) |
Motor Power Range Ac-3 | 110…220 kW 200…240 V 3 phase 250…500 kW 380…440 V 3 phase 250…500 kW 480…500 V 3 phase 250…500 kW 200…240 V 3 phase 560…900 kW 380…440 V 3 phase 560…900 kW 480…500 V 3 phase |
Motor Starter Type | Soft starter |
Electromagnetic Compatibility | Conducted and radiated emissions level A IEC 60947-4-2 Damped oscillating waves level 3 IEC 61000-4-12 Electrostatic discharge level 3 IEC 61000-4-2 Immunity to electrical transients level 4 IEC 61000-4-4 Immunity to radiated radio-electrical interference level 3 IEC 61000-4-3 Voltage/current impulse level 3 IEC 61000-4-5 |
Powered by
Based on 2 User Reviews
1619 Boyd St, Santa Ana, CA 92705
(714) 835-6211
(714) 972-2366