Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
Single-stage heavy duty screw limit switch XR2 – Ithe = 10 A – 3 C/O – 350 rpm
XR2AB03K80
Single-stage heavy duty screw limit switch XR2 – Ithe = 10 A – 3 C/O – 350 rpm
Specifications
Part Number XR2AB03K80
Country of Origin FR
UPC 389110311495
UPC11 38911031149
EAN 3389110311495
Availability N
Lead Time 29
UNSPSC 39122213
ECCN EAR99
HTs Code 8536509025
Prop 65 This product can expose you to chemicals including: Di-isodecyl phthalate (DIDP) and Diisononyl phthalate (DINP) which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov
Discount Schedule T
Return Indicator No
Characteristics
Range Of Product XR and XF
Product Or Component Type Single-stage heavy duty screw limit switch
Device Short Name XR2
Product Specific Application Liquid level control in pumping systems Position control of moving parts of hoisting or materials handling equipment
Material Sheet steel enclosure
Type Of Operator Drive shaft, end fittings with sprocket key and washer
Maximum Revolution Speed 350 rpm input drive shaft
Theoretical Number Of Turns 80 input drive shaft
Number Of Poles 1
Mechanical Durability 10000000 cycles
Number Of Turns 6 threaded shaft
Threaded Shaft Screw Pitch 0.16 in (4 mm)
Operating Finger Radius 1.57 in (40 mm)
Length Of Developed Helical Tr 0.16 in (4 mm)
Differential Snap Over Angle 30 ° contact actuators measured at finger
Repeat Accuracy 0.02 % on the tripping point
Number Of Teeth 16 pinion A) 16 pinion C) 59 pinion B) 59 pinion D)
Actual Number Of Turns 81.586 input drive shaft)
Contacts Type And Composition 3 C/O
Contact Operation Snap action
Ie Rated Operational Current A300, AC-15, Ue = 240 V, Ie = 3 A EN/IEC 60947-5-1 Q300, DC-13, Ue = 250 V, Ie = 0.27 A EN/IEC 60947-5-1
Ithe Cnvtl Enclosed Therm Crrt 10 A
Ui Rated Insulation Voltage 500 V EN/IEC 60947-1 600 V CSA C22.2 No 14
Uimp Rated Imp Wstd Voltage 6 kV EN/IEC 60947-1
Resistance Across Terminals 25 MOhm
Short-Circuit Protection 10 A cartridge fuse gG
Connections - Terminals Screw clamp terminals, 2 x 1.5 mm² with or without cable end Screw clamp terminals, 2 x 2.5 mm² without cable end
Electrical Durability 10000000 cycles AC-15 50/60 Hz inductive 12 V, 70 VA 3600 cyc/h 0.5 EN/IEC 60947-5-1 10000000 cycles AC-15 50/60 Hz inductive 127 V, 270 VA 3600 cyc/h 0.5 EN/IEC 60947-5-1 10000000 cycles AC-15 50/60 Hz inductive 220 V, 290 VA 3600 cyc/h 0.5 EN/IEC 60947-5-1 10000000 cycles AC-15 50/60 Hz inductive 24 V, 120 VA 3600 cyc/h 0.5 EN/IEC 60947-5-1 10000000 cycles AC-15 50/60 Hz inductive 380 V, 300 VA 3600 cyc/h 0.5 EN/IEC 60947-5-1 10000000 cycles AC-15 50/60 Hz inductive 48 V, 180 VA 3600 cyc/h 0.5 EN/IEC 60947-5-1 10000000 cycles AC-15 50/60 Hz inductive 500 V, 300 VA 3600 cyc/h 0.5 EN/IEC 60947-5-1 10000000 cycles AC-15 50/60 Hz resistive 12 V, 45 VA 3600 cyc/h 0.5 EN/IEC 60947-5-1 10000000 cycles AC-15 50/60 Hz resistive 127 V, 180 VA 3600 cyc/h 0.5 EN/IEC 60947-5-1 10000000 cycles AC-15 50/60 Hz resistive 220 V, 200 VA 3600 cyc/h 0.5 EN/IEC 60947-5-1 10000000 cycles AC-15 50/60 Hz resistive 24 V, 75 VA 3600 cyc/h 0.5 EN/IEC 60947-5-1 10000000 cycles AC-15 50/60 Hz resistive 380 V, 200 VA 3600 cyc/h 0.5 EN/IEC 60947-5-1 10000000 cycles AC-15 50/60 Hz resistive 48 V, 120 VA 3600 cyc/h 0.5 EN/IEC 60947-5-1 10000000 cycles AC-15 50/60 Hz resistive 500 V, 200 VA 3600 cyc/h 0.5 EN/IEC 60947-5-1 3000000 cycles AC-15 50/60 Hz inductive 12 V, 100 VA 3600 cyc/h 0.5 EN/IEC 60947-5-1 3000000 cycles AC-15 50/60 Hz inductive 127 V, 1050 VA 3600 cyc/h 0.5 EN/IEC 60947-5-1 3000000 cycles AC-15 50/60 Hz inductive 220 V, 1150 VA 3600 cyc/h 0.5 EN/IEC 60947-5-1 3000000 cycles AC-15 50/60 Hz inductive 24 V, 220 VA 3600 cyc/h 0.5 EN/IEC 60947-5-1 3000000 cycles AC-15 50/60 Hz inductive 380 V, 1150 VA 3600 cyc/h 0.5 EN/IEC 60947-5-1 3000000 cycles AC-15 50/60 Hz inductive 48 V, 480 VA 3600 cyc/h 0.5 EN/IEC 60947-5-1 3000000 cycles AC-15 50/60 Hz inductive 500 V, 1200 VA 3600 cyc/h 0.5 EN/IEC 60947-5-1 3000000 cycles AC-15 50/60 Hz resistive 12 V, 100 VA 3600 cyc/h 0.5 EN/IEC 60947-5-1 3000000 cycles AC-15 50/60 Hz resistive 127 V, 700 VA 3600 cyc/h 0.5 EN/IEC 60947-5-1 3000000 cycles AC-15 50/60 Hz resistive 220 V, 750 VA 3600 cyc/h 0.5 EN/IEC 60947-5-1 3000000 cycles AC-15 50/60 Hz resistive 24 V, 200 VA 3600 cyc/h 0.5 EN/IEC 60947-5-1 3000000 cycles AC-15 50/60 Hz resistive 380 V, 800 VA 3600 cyc/h 0.5 EN/IEC 60947-5-1 3000000 cycles AC-15 50/60 Hz resistive 48 V, 400 VA 3600 cyc/h 0.5 EN/IEC 60947-5-1 3000000 cycles AC-15 50/60 Hz resistive 500 V, 800 VA 3600 cyc/h 0.5 EN/IEC 60947-5-1 10000000 cycles DC-13 inductive 110 V, 80 W 3600 cyc/h 0.5 EN/IEC 60947-5-1 10000000 cycles DC-13 inductive 12 V, 100 W 3600 cyc/h 0.5 EN/IEC 60947-5-1 10000000 cycles DC-13 inductive 220 V, 60 W 3600 cyc/h 0.5 EN/IEC 60947-5-1 10000000 cycles DC-13 inductive 24 V, 90 W 3600 cyc/h 0.5 EN/IEC 60947-5-1 10000000 cycles DC-13 inductive 440 V, 33 W 3600 cyc/h 0.5 EN/IEC 60947-5-1 10000000 cycles DC-13 inductive 48 V, 85 W 3600 cyc/h 0.5 EN/IEC 60947-5-1 10000000 cycles DC-13 resistive 110 V, 30 W 3600 cyc/h 0.5 EN/IEC 60947-5-1 10000000 cycles DC-13 resistive 12 V, 45 W 3600 cyc/h 0.5 EN/IEC 60947-5-1 10000000 cycles DC-13 resistive 220 V, 20 W 3600 cyc/h 0.5 EN/IEC 60947-5-1 10000000 cycles DC-13 resistive 24 V, 40 W 3600 cyc/h 0.5 EN/IEC 60947-5-1 10000000 cycles DC-13 resistive 440 V, 7.5 W 3600 cyc/h 0.5 EN/IEC 60947-5-1 10000000 cycles DC-13 resistive 48 V, 35 W 3600 cyc/h 0.5 EN/IEC 60947-5-1 3000000 cycles DC-13 inductive 110 V, 110 W 3600 cyc/h 0.5 EN/IEC 60947-5-1 3000000 cycles DC-13 inductive 12 V, 100 W 3600 cyc/h 0.5 EN/IEC 60947-5-1 3000000 cycles DC-13 inductive 220 V, 95 W 3600 cyc/h 0.5 EN/IEC 60947-5-1 3000000 cycles DC-13 inductive 24 V, 140 W 3600 cyc/h 0.5 EN/IEC 60947-5-1 3000000 cycles DC-13 inductive 440 V, 65 W 3600 cyc/h 0.5 EN/IEC 60947-5-1 3000000 cycles DC-13 inductive 48 V, 130 W 3600 cyc/h 0.5 EN/IEC 60947-5-1 3000000 cycles DC-13 resistive 110 V, 95 W 3600 cyc/h 0.5 EN/IEC 60947-5-1 3000000 cycles DC-13 resistive 12 V, 100 W 3600 cyc/h 0.5 EN/IEC 60947-5-1 3000000 cycles DC-13 resistive 220 V, 80 W 3600 cyc/h 0.5 EN/IEC 60947-5-1 3000000 cycles DC-13 resistive 24 V, 120 W 3600 cyc/h 0.5 EN/IEC 60947-5-1 3000000 cycles DC-13 resistive 440 V, 45 W 3600 cyc/h 0.5 EN/IEC 60947-5-1 3000000 cycles DC-13 resistive 48 V, 110 W 3600 cyc/h 0.5 EN/IEC 60947-5-1
Cable Entry Removable gland plate
Standards EN/IEC 60947-5-1
Protective Treatment TC
Ambient Air Temp For Op -13…158 °F (-25…70 °C)
Ambient Air Temp For Storage -40…158 °F (-40…70 °C)
Shock Resistance 50 gn 11 ms
Vibration Resistance > 5 gn 10…55 Hz)
IP Degree Of Protection IP54 EN/IEC 60529
Category 22449 - LIMIT SWITCHES,ACCESSORIES
Discount Schedule T
GTIN 03389110311495
Nbr. Of Units In Pkg. 1
Country Of Origin FR
EU RoHs Directive Not applicable, out of EU RoHS legal scope
Warranty 18 months
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews