Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
Reversing power base, TeSys U, 3P, 12A/690V, coil 24V DC, without control terminals
LU2BA0BL
Reversing power base, TeSys U, 3P, 12A/690V, coil 24V DC, without control terminals
Specifications
Part Number LU2BA0BL
Country of Origin FR
UPC 389110363098
UPC11 38911036309
EAN 3389110363098
Availability N
Lead Time 20
UNSPSC 39122330
ECCN EAR99
HTs Code 8536490065
Prop 65 This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Discount Schedule I11
Return Indicator No
Depth 4.96 inch
Height 8.82 inch
Width 1.77 inch
Weight 2.80 pound
Characteristics
Range TeSys
Product Name TeSys U
Device Short Name LU2B
Product Or Component Type Reversing power base
Device Application Motor control Motor protection
Product Compatibility Control unit LUC.X6BL Control unit LUC.1XBL Control unit LUC.05BL Control unit LUC.12BL
Poles Description 3P
Suitability For ISOlation Yes
Ue Rated Operational Voltage 690 V AC power circuit
Network Frequency 40...60 Hz
Ith Cnvtl Free Air Therm Crrt 12 A
Ie Rated Operational Current 12 A <= 440 V 12 A 500 V 9 A 690 V
Utilisation Category AC-43 AC-41 AC-44
Ics Rated Service Breaking Cap 50 kA 230 V 50 kA 440 V 10 kA 500 V 4 kA 690 V
Auxiliary Contact Composition 1 NO + 1 NC
Auxiliary Contacts Type Linked contacts 1 NO + 1 NC) IEC 60947-4-1 Mirror contact 1 NC) IEC 60947-1
[Uc] Control Circuit Voltage 24 V DC
Ctrl Circuit Voltage Limits 14.5 V DC drop-out 20...27 V DC in operation
Typical Current Consumption 120 mA 24 V DC I maximum while closing 120 mA 24 V DC I rms sealed
Heat Dissipation 2 W control circuit with LUCA, LUCB, LUCC, LUCD 1.7 W control circuit with LUCM
Inrush Restraint Duration 15 ms DC
Safety Reliability Level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Operating Time 150 ms with change of direction power circuit 75 ms without change of direction power circuit 35 ms opening with LUCA, LUCB, LUCC, LUCD, LUCM control circuit 75 ms closing with LUCM control circuit 70 ms closing with LUCA, LUCB, LUCC, LUCD control circuit
Mechanical Durability 15 Mcycles
Operating Rate 3600 cyc/h
Product Certifications CE UL CSA CCC EAC ASEFA ATEX Marine
Standards EN 60947-6-2 IEC 60947-6-2 UL 60947-4-1, with phase barrier CSA C22.2 No 60947-4-1, with phase barrier
Ui Rated Insulation Voltage 690 V IEC 60947-6-2 3) 600 V UL 60947-4-1 600 V CSA C22.2 No 60947-4-1
Uimp Rated Imp Wstd Voltage 6 kVIEC 60947-6-2
Safe Separation Of Circuit 400 V SELV between the control and auxiliary circuits IEC 60947-1 appendix N 400 V SELV between the control or auxiliary circuit and the main circuit IEC 60947-1 appendix N
Fixing Mode Clipped DIN rail) Screw-fixed plate)
Connections - Terminals Power circuit screw clamp terminals 1 0.00…0.02 in² (1…10 mm²) rigid Power circuit screw clamp terminals 1 0.00…0.01 in² (1…6 mm²) flexible with cable end Power circuit screw clamp terminals 1 0.00…0.02 in² (2.5…10 mm²) flexible without cable end Power circuit screw clamp terminals 2 0.00…0.01 in² (1…6 mm²) flexible with cable end Power circuit screw clamp terminals 2 0.00…0.01 in² (1…6 mm²) rigid Power circuit screw clamp terminals 2 0.00…0.01 in² (1.5…6 mm²) flexible without cable end Control circuit without connection
Tightening Torque Power circuit 16.82…22.13 lbf.in (1.9…2.5 N.m) flat 0.24 in (6 mm) Power circuit 16.82…22.13 lbf.in (1.9…2.5 N.m) Philips No 2 0.24 in (6 mm)
Width 1.77 in (45 mm)
Height 8.82 in (224 mm)
Depth 4.96 in (126 mm)
Product Weight 2.80 lb(US) (1.27 kg)
Compatibility Code LU2B
IP Degree Of Protection IP20 IEC 60947-1 front panel and wired terminals) IP20 IEC 60947-1 other faces) IP40 IEC 60947-1 front panel outside connection zone)
Protective Treatment TH IEC 60068
Ambient Air Temp For Op -13…140 °F (-25…60 °C) with LUCM -13…158 °F (-25…70 °C) with LUCA, LUCB, LUCC, LUCD
Ambient Air Temp For Storage -40…185 °F (-40…85 °C)
Fire Resistance 1760 °F (960 °C) parts supporting live components IEC 60695-2-12 1202 °F (650 °C) IEC 60695-2-12
Operating Altitude 6561.68 ft (2000 m)
Shock Resistance 10 gn power poles open IEC 60068-2-27 15 gn power poles closed IEC 60068-2-27
Vibration Resistance 2 gn 5…300 Hz) power poles open IEC 60068-2-27 4 gn 5…300 Hz) power poles closed IEC 60068-2-27
Resist Electrostatic Dischrg 8 kV 3 in open air IEC 61000-4-2 8 kV 4 on contact IEC 61000-4-2
Resistance To Radiated Fields 9.14 V/m (10 V/m) 3 IEC 61000-4-3
Resistance To Fast Transients 2 kV 3 serial link IEC 61000-4-4 4 kV 4 all circuits except for serial link IEC 61000-4-4
Imm To Radioelectric Fields 10 V IEC 61000-4-6
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews