Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
Redundant power supply module X80 – 24..48 V DC -for severe environments
BMXCPS4022H
Redundant power supply module X80 – 24..48 V DC -for severe environments

This product is part of the Modicon X80 range, a common platform of modules for Modicon M580 and M340 Programmable Automation Controllers (PAC). This redundant power supply module has a primary voltage of 24V to 48V DC for severe environments. It is a power supply module with a secondary power of 40W at 24V DC, a current at secondary voltage of 5.5A at 3.3V DC and a maximum power dissipation of 8.5W. This ruggedized product can be used in more severe environments, and operate in an extended temperature range, from -25°C to +70°C. It is furnished with 2-pin connector for alarm relay, 5-pin connector for line supply, protective earth for electrical connection. Advanced diagnostics available via networks are temperature sensing, redundancy test, uptime duration, redundancy information and remaining lifetime. It is an IP20 rated product. It weighs 0.81kg. It is suitable for medium to large process applications. It meets EN 61131-2, EN 61000-6-4, EN 61000-6-2 and EN 61010-2-201 standards. This product is compatible with all backplane. Modicon X80 consists in a compatible modules common platform that reduce maintenance and training costs with same spare parts in stock, and unique training for different Programmable Automation Controllers (PAC).

Add to Quote Catalogue
Specifications
Part Number BMXCPS4022H
UPC 606481179081
UPC11 60648117908
EAN 3606481179081
Availability N
Lead Time 35
UNSPSC 32151705
HTs Code 8504409580
Prop 65 This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Discount Schedule PC34
Return Indicator No
Weight 1.79 pound
Characteristics
Range Of Product Modicon X80
Product Or Component Type Power supply module
Backplane Compatibility All backplane
Product Specific Application For severe environments
Advanced Diagnostics Available Via Network Temperature sensing Uptime duration Redundancy test Remaining lifetime Redundancy information
Primary Voltage 24...48 V
Supply Circuit Type DC
Secondary Power 18 W 3.3 V DC -13…158 °F (-25…70 °C) I/O module logic power supply 40 W 24 V DC -13…158 °F (-25…70 °C) I/O module power supply and processor if 3.3 V not loaded
Primary Voltage Limit 18...62.4 V
Input Current 1.9 A 24 V 1 A 48 V
Inrush Current 60 A 48 V 60 A 24 V
I┬▓T On Activation 1 A².s 24 V 3 A².s 48 V
It On Activation 0.3 A.s 24 V 0.4 A.s 48 V
Protection Type Internal fuse not accessible primary circuit Overload protection secondary circuit Overvoltage protection secondary circuit Short-circuit protection secondary circuit
Current At Secondary Voltage 5.5 A 3.3 V DC I/O module logic power supply 1.67 A 24 V DC I/O module power supply and processor
Power Dissipation In W 8.5 W
Status Led Presence of voltages (OK) 1 LED Green) Redundancy OK 1 LED Green) Power supply status 1 LED Green)
Control Type RESET push-button cold restart
Electrical Connection 1 connector 2 alarm relay 1 connector 5 line supply, protective earth
Cable Distance Between Devices 32.81 ft (10 m) 49.21 ft (15 m)
Insulation Resistance >= 100 MOhm primary/ground >= 100 MOhm primary/secondary
Product Weight 1.79 lb(US) (0.81 kg)
Immunity To Microbreaks 1 ms
Dielectric Strength 1500 V primary/ground 1500 V primary/secondary
IP Degree Of Protection IP20
Directives 2014/35/EU - low voltage directive 2014/30/EU - electromagnetic compatibility 2014/34/EU - ATEX directive 2012/19/EU - WEEE directive
Product Certifications CE UL CSA RCM EAC Merchant Navy ATEX zone 2/22 IECEx zone 2/22
Standards EN/IEC 61131-2 EN/IEC 61010-2-201 UL 61010-2-201 CSA C22.2 No 61010-2-201 IACS E10 EN/IEC 61000-6-5 EN/IEC 61850-3 EN/IEC 60079-0
Environmental Characteristic Gas resistant class Gx ISA S71.04 Gas resistant class 3C4 IEC 60721-3-3 Dust resistant class 3S4 IEC 60721-3-3 Sand resistant class 3S4 IEC 60721-3-3 Salt resistant level 2 IEC 68252 Mold growth resistant class 3B2 IEC 60721-3-3 Fungal spore resistant class 3B2 IEC 60721-3-3 Hazardous location class I division 2
Ambient Air Temp For Storage -40…185 °F (-40…85 °C)
Ambient Air Temp For Op -13…158 °F (-25…70 °C)
Relative Humidity 10…95 % without condensation
Protective Treatment Conformal coating
Category 18160 - MODICON M340
Discount Schedule PC34
GTIN 03606481179081
Nbr. Of Units In Pkg. 1
Green Premium Status Green Premium product
EU RoHs Directive Pro-active compliance (Product out of EU RoHS legal scope)
Mercury Free Yes
WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Documents