Part Number | XB6AS9345B |
---|---|
Country of Origin | MX |
UPC | 785901190202 |
UPC11 | 78590119020 |
EAN | 0785901190202 |
Availability | N |
Lead Time | 5 |
UNSPSC | 39122216 |
ECCN | EAR99 |
HTs Code | 8536509031 |
Prop 65 | This product can expose you to chemicals including: Nickel compounds and Di-isodecyl phthalate (DIDP) which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Discount Schedule | CS2 |
Return Indicator | No |
Depth | 3.82 inch |
Height | 1.18 inch |
Width | 1.18 inch |
Weight | 0.12 pound |
Range Of Product | Harmony XB6 |
---|---|
Product Or Component Type | Complete emergency stop push-button |
Device Short Name | XB6 |
Bezel Material | Plastic |
Mounting Diameter | 0.63 in (16 mm) |
Sale Per Indivisible Qty | 1 |
Shape Of Signaling Unit Head | Round |
Type Of Operator | trigger action and mechanical latching |
Reset | Key release |
Operator Profile | Red mushroom Ø 30 mm, unmarked |
Contacts Type And Composition | 1 NO + 1 NC |
Contact Operation | Slow-break |
Connections - Terminals | Faston connectors 2.8 x 0.5 mm |
Height | 1.18 in (30 mm) |
Width | 1.18 in (30 mm) |
Depth | 3.82 in (97 mm) |
Terminals Description ISO n°1 | (13-14)NO (21-22)NC |
Product Weight | 0.12 lb(US) (0.056 kg) |
Operating Position | Any position |
Type Of Keylock | Ronis 200 |
Contacts Usage | Standard |
Positive Opening | With EN/IEC 60947-5-1 appendix K |
Operating Travel | 0.04 in (1 mm) NC changing electrical state) 0.08 in (2 mm) NO changing electrical state) 0.14 in (3.5 mm) total travel) |
Operating Force | 3.5 N NO changing electrical state 4.5 N NC changing electrical state |
Mechanical Durability | 100000 cycles |
Contacts Material | Silver alloy (Ag/Ni) |
Short-Circuit Protection | 6 A cartridge fuse gG |
Ui Rated Insulation Voltage | 250 V 3)EN/IEC 60947-1 |
Uimp Rated Imp Wstd Voltage | 4 kV EN/IEC 60947-1 |
Ie Rated Operational Current | 3 A 120 V, AC-15, B300 EN/IEC 60947-5-1 1.5 A 240 V, AC-15, B300 EN/IEC 60947-5-1 0.1 A 250 V, DC-13, R300 EN/IEC 60947-5-1 0.22 A 125 V, DC-13, R300 EN/IEC 60947-5-1 |
Electrical Durability | 1000000 cycles, AC-15 230 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C 1000000 cycles, DC-13 230 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C |
Electrical Reliability | Λ < 10exp(-8) 5 V, 1 mA with confidence level of 90 % IEC 60947-5-4 |
Protective Treatment | TC |
Ambient Air Temp For Storage | -40…158 °F (-40…70 °C) |
Ambient Air Temp For Op | -13…158 °F (-25…70 °C) |
Electrical Shock Protect Class | Class II IEC 61140 |
IP Degree Of Protection | IP65 IEC 60529 |
Nema Degree Of Protection | NEMA 13 UL 50 NEMA 4 UL 50 NEMA 4X UL 50 NEMA 13 CSA C22.2 No 94 NEMA 4X CSA C22.2 No 94 NEMA 4 CSA C22.2 No 94 |
Standards | JIS C8201-5-1 UL 508 EN/IEC 60947-5-5 JIS C 852 EN/IEC 60947-1 EN/IEC 60947-5-1 CSA C22.2 No 14 EN/IEC 60204-1 EN/ISO 13850 JIS C8201-1 |
Product Certifications | CCC UL GOST CSA |
Vibration Resistance | +/- 3 mm 2…500 Hz)IEC 60068-2-6 5 gn 2…500 Hz)IEC 60068-2-6 |
Shock Resistance | 30 gn 18 ms) half sine wave acceleration IEC 60068-2-27 50 gn 11 ms) half sine wave acceleration IEC 60068-2-27 |
Category | 22459-PUSHBUTTONS, 16MM |
Discount Schedule | CS2 |
GTIN | 00785901190202 |
Country Of Origin | MX |
Green Premium Status | Green Premium product |
REACh Free Of SVHC | Yes |
EU RoHs Directive | Pro-active compliance (Product out of EU RoHS legal scope) |
Mercury Free | Yes |
Powered by