| Part Number | 9013GHG2J29 |
|---|---|
| Country of Origin | MX |
| UPC | 785901052777 |
| UPC11 | 78590105277 |
| EAN | 0785901052777 |
| Availability | S |
| Lead Time | 5 |
| UNSPSC | 39122210 |
| ECCN | EAR99 |
| HTs Code | 9032200000 |
| Discount Schedule | CP7G |
| Return Indicator | Yes |
| Depth | 3.88 inch |
| Height | 5.4 inch |
| Width | 3.44 inch |
| Weight | 2.25 pound |
| Range Of Product | Square D Pumptrol |
|---|---|
| Pressure Sensor Name | 9013GH |
| Pressure Sensor Size | 200 psi (1378.95 kPa) 40…170 psi (275.79…1172.11 kPa)) |
| Value Of Setting | 75...100 psi |
| Electrical Circuit Type | Power circuit |
| Product Specific Application | Control electrically driven water pumps and air compressors |
| Quantity Per Set | 1 |
| Type Of Packing | Individual |
| Pressure Sensor Type | Electromechanical pressure switch |
| Controlled Fluid | Air -22…257 °F (-30…125 °C)) Fresh water -22…257 °F (-30…125 °C)) |
| Adj Range On Rising Pressure | 65…200 psi (448.16…1378.95 kPa) |
| Approximate Adj Differential | 20…40 psi (137.90…275.79 kPa) |
| Destruction Pressure | 300 psi (2068.43 kPa) |
| Pressure Actuator | Diaphragm |
| Pressure Swt Type Of Operation | Regulation between 2 thresholds |
| Type Of Scale | Adjustable differential |
| Setting | Internal |
| Local Display | Without |
| Contacts Type And Composition | 2 NC, snap action, DPST-DB, Form YY |
| Cable Entry Number | 3 knock-outs for 1/2" conduit UL 508 |
| Electrical Connection | Screw-clamp terminals 10 AWG Screw-clamp terminals 5.261 mm² |
| Fluid Connection Type | 0.25 inch NPSF internal UL 508 |
| Short-Circuit Protection | 20 A cartridge fuse gG |
| Materials In Contact Wth Fluid | Zinc plated steel or equivalent flange Nitrile (Buna-N) or equivalent rubber diaphragm |
| Material | Polypropylene cover Noryl thermoplastic resin or equivalent cover |
| Operating Position | Any position |
| Motor Power kW | 1.5 kW 2 hp)115 V AC, 1 phase 2.2 kW 3 hp)115 V AC, 3 phase 2.2 kW 3 hp)230 V AC, 1 phase 0.75 kW 1 hp)115 V DC 0.75 kW 1 hp)230 V DC 3.75 kW 5 hp)230 V AC, 3 phase 3.7 kW 5 hp)460 V AC, 1 phase 3.7 kW 5 hp)460 V AC, 3 phase 3.7 kW 5 hp)575 V AC, 1 phase 3.7 kW 5 hp)575 V AC, 3 phase |
| Electrical Durability | 100000 cycles 10 cyc/mn |
| Mechanical Durability | 300000 cycles |
| Terminal Block Type | 4 terminals |
| Operating Rate | 10 cyc/mn |
| Ui Rated Insulation Voltage | 575 V UL 508 |
| Product Weight | 2.25 lb(US) (1.02 kg) |
| Repeat Accuracy | +/- 3 % |
| Terminals Description ISO n°1 | L1-T1 L2-T2 |
| Width | 3.44 in (87.38 mm) |
| Height | 5.4 in (137.16 mm) |
| Depth | 3.88 in (98.55 mm) |
| Standards | UL 508 NSF ANSI 372 CE |
| Ambient Air Temp For Op | -33…257 °F (-36…125 °C) |
| Ambient Air Temp For Storage | -33…257 °F (-36…125 °C) |
| Protective Treatment | None |
| Nema Degree Of Protection | NEMA 1 UL 50 |
| IP Degree Of Protection | IP20 IEC 60529 |
| Product Certifications | CSA file LR25490 UL listed file E12158 |
| Category | 21536 - 9013 G COMMERCIAL PRESSURE SWITCH |
| Discount Schedule | CP7G |
| GTIN | 00785901052777 |
| Nbr. Of Units In Pkg. | 1 |
| Country Of Origin | MX |