This product is part of the Preventa XPS Universal safety relays. This safety relay is designed for extending the number of safety contacts The safety relay is powered with 24V AC/DC, and equipped with a spring removable terminal block. XPS Universal safety relay can forward more than 40 different messages between the solid state output of the relay and a standard digital input of a PLC, reducing the down time of the machine, precising the root cause of production stop. This safety relay embeds a safety extension bus, 4 NO and 2 single NC safety outputs. The maximum safety level achieved by this safety relay is PL e/Category 4 conforming to ISO 13849-1, SILCL 3 conforming to IEC 62061, SIL 3 conforming to IEC 61508. This safety relay weighs 0,200kg. Its dimensions are 22,5mm (Width) x 120mm (Depth) x 100mm (Height). This safety relays is suitable for applications such as Food and Beverage, Hoisting, Material Handling, Material Working, Packaging, Mainly designed for a broad range of machines of the general mechanical engineering. This safety relay conforms to IEC 60947-5-1, IEC 61508-1, IEC 61508-2, IEC 61508-3, ISO 13849-1, IEC 62061, IEC 60947-5-1, IEC 61508-1, IEC 61508-2, IEC 61508-3, ISO 13849-1, IEC 62061 standards, and certified by cULus and TUV. This relay is mounted on a 35mm symmetrical DIN rail. Preventa XPS Universal safety relays are the first choice for managing single safety functions easily, typically in machines of simple to medium complexity.
Add to Quote CataloguePart Number | XPSUEP14AC |
---|---|
EAN | 3606489601768 |
Availability | N |
Lead Time | 15 |
HTs Code | 8536410060 |
Prop 65 | This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Discount Schedule | SAF2 |
Depth | 4.72 inch |
Height | 3.94 inch |
Width | 0.89 inch |
Weight | 0.44 pound |
Range Of Product | Preventa Safety automation |
---|---|
Product Or Component Type | Preventa safety module |
Safety Module Name | XPSUEP |
Safety Module Application | For extending number of safety contacts |
Function Of Module | Safety output extension |
Safety Level | Can reach PL e/category 4 for normally open relay contact ISO 13849-1 Can reach SILCL 3 for normally open relay contact IEC 62061 Can reach SIL 3 for normally open relay contact IEC 61508 Can reach PL c/category 1 for normally closed relay contact ISO 13849-1 Can reach SILCL 1 for normally closed relay contact IEC 62061 Can reach SIL 1 for normally closed relay contact IEC 61508 |
Safety Reliability Data | MTTFd > 30 years ISO 13849-1 Dcavg >= 99 % ISO 13849-1 PFHd = 0.97E-09 ISO 13849-1 HFT = 1 IEC 62061 PFHd = 0.97E-09 IEC 62061 SFF > 99% IEC 62061 HFT = 1 IEC 61508-1 PFHd = 0.97E-09 IEC 61508-1 SFF > 99% IEC 61508-1 Type = B IEC 61508-1 |
Electrical Circuit Type | Addition to Preventa XPSU base module |
Connections - Terminals | Removable spring terminal block, 0.2...2.5 mm² solid or flexible Removable spring terminal block, 0.25...2.5 mm² flexible with ferrule single conductor Removable spring terminal block, 0.2...1.5 mm² solid or flexible twin conductor Removable spring terminal block, 2 x 0.25...1 mm² flexible with ferrule without cable end, with bezel Removable spring terminal block, 2 x 0.5...1.5 mm² flexible with ferrule with cable end, with bezel |
Us Rated Supply Voltage | 24 V AC - 15...10 % 24 V DC - 20...20 % |
Power Consumption In W | 1.5 W 24 V DC |
Power Consumption In Va | 3.5 VA 24 V AC 50/60 Hz |
Input Protection Type | Internal, electronic |
Safety Outputs | 4 NO 2 NC |
Line Resistance | 60 Ohm |
Input Compatibility | Normally closed circuit ISO 14119 XC limit switch ISO 14119 Mechanical contact ISO 14119 Normally closed circuit ISO 13850 Antivalent pair ISO 14119 OSSD pair IEC 61496-1-2 3-wire proximity sensors PNP |
Output Type | relay output, 250 V AC relay output, 250 V AC |
Ie Rated Operational Current | 5 A AC-1 3 A AC-15 5 A DC-1 3 A DC-13 |
Ith Cnvtl Free Air Therm Crrt | 8 A |
Associated Fuse Rating | 10 A gG NO relay output circuit IEC 60947-1 4 A gG NC relay output circuit IEC 60947-1 |
Minimum Output Current | 10 mA relay output |
Minimum Output Voltage | 12 V relay output |
Response Time On Input Open | 20 ms |
Ui Rated Insulation Voltage | 250 V 2)EN/IEC 60947-1 |
Uimp Rated Imp Wstd Voltage | 4 kV II EN/IEC 60947-1 |
Local Signalling | Power ON LED green) Error LED red) Safety output status LED yellow) |
Mounting Support | 35 mm symmetrical DIN rail |
Depth | 4.72 in (120 mm) |
Height | 3.94 in (100 mm) |
Width | 0.89 in (22.5 mm) |
Product Weight | 0.44 lb(US) (0.200 kg) |
Standards | IEC 60947-5-1 IEC 61508-1 functional safety standard IEC 61508-2 functional safety standard IEC 61508-3 functional safety standard IEC 61508-4 functional safety standard IEC 61508-5 functional safety standard IEC 61508-6 functional safety standard IEC 61508-7 functional safety standard ISO 13849-1 functional safety standard IEC 62061 functional safety standard |
Product Certifications | TÜV CULus |
IP Degree Of Protection | IP20 terminals)EN/IEC 60529 IP40 housing)EN/IEC 60529 IP54 mounting area)EN/IEC 60529 |
Ambient Air Temp For Storage | -13…185 °F (-25…85 °C) |
Relative Humidity | 5…95 % non-condensing |
Green Premium Status | Green Premium product |
EU RoHs Directive | Pro-active compliance (Product out of EU RoHS legal scope) |
Mercury Free | Yes |
WEEE | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
Pvc Free | Yes |
Powered by
Based on 2 User Reviews
1619 Boyd St, Santa Ana, CA 92705
(714) 835-6211
(714) 972-2366