| Part Number | FYG22NE |
|---|---|
| Country of Origin | MX |
| UPC | 389118228405 |
| UPC11 | 38911822840 |
| EAN | 3389118228405 |
| Availability | N |
| Lead Time | 5 |
| UNSPSC | 39122210 |
| HTs Code | 8544429090 |
| Prop 65 | This product can expose you to chemicals including: Di-isodecyl phthalate (DIDP) and Diisononyl phthalate (DINP) which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov |
| RoHS Compliant | Yes |
| Discount Schedule | DS2 |
| Return Indicator | No |
| Depth | 4.17 inch |
| Height | 4.53 inch |
| Width | 2.83 inch |
| Weight | 0.75 pound |
| Range Of Product | OsiSense XM |
|---|---|
| Pressure Sensor Type | Electromechanical pressure sensor |
| Pressure Sensor Name | FYG |
| Pressure Sensor Size | 101.53 psi (7 bar) |
| Fluid Connection Type | G 1/4 (female) ISO 228 |
| Controlled Fluid | Fresh water 32…158 °F (0…70 °C)) Sea water 32…158 °F (0…70 °C)) |
| Cable Entry | 2 entries incorporating Pg 13.5 plastic cable gland 0.35…0.51 in (9…13 mm) NF C 68-300 |
| Contacts Type And Composition | 2 NC snap action |
| Pressure Swt Type Of Operation | Regulation between 2 thresholds |
| In Rated Current | 10 A 250 V AC EN 60730-1 |
| Electrical Connection | Screw-clamp terminals 1 x 1...2 x 2 mm² |
| Short-Circuit Protection | 20 A cartridge fuse gG |
| Type Of Scale | Adjustable differential |
| Setting | Internal |
| Local Display | Without |
| Electrical Circuit Type | Power circuit |
| Materials In Contact Wth Fluid | Nylon 6/6 Nitrile Zinc plated steel |
| Enclosure Material | PS |
| Operating Position | Any position |
| Motor Power kW | 0.75 kW 1 hp 110 V AC, 1 phase 1.1 kW 1.5 hp 110 V AC, 3 phase 1.5 kW 2 hp 230 V AC, 1 phase 1.5 kW 2 hp 400 V AC, 1 phase 2.2 kW 3 hp 230 V AC, 3 phase 2.2 kW 3 hp 400 V AC, 3 phase |
| Adj Range Low Setting | 7.25…78.32 psi (0.5…5.4 bar) |
| Adj Range High Setting | 40.61…101.53 psi (2.8…7 bar) |
| Possible Diff Min At Low Setg | 17.40 psi (1.2 bar) |
| Possible Diff Min At High Setg | 23.21 psi (1.6 bar) |
| Possible Diff Max At Low Setg | 33.36 psi (2.3 bar) |
| Possible Diff Max At High Setg | 39.16 psi (2.7 bar) |
| Max Perm Accidental Pressure | 217.56 psi (15 bar) |
| Max Perm Pressure - Per Cycle | 126.91 psi (8.75 bar) |
| Destruction Pressure | 290.08 psi (20 bar) |
| Pressure Actuator | Diaphragm |
| Electrical Durability | 100000 cycles 10 cyc/mn |
| Mechanical Durability | 1000000 cycles |
| Terminal Block Type | 4 terminals |
| Possible Diff Min At Mid Setg | 20.31 psi (1.4 bar) |
| Possible Diff Max At Mid Setg | 36.26 psi (2.5 bar) |
| Operating Rate | 10 cyc/mn |
| Ui Rated Insulation Voltage | 500 V EN/IEC 60947-1 |
| Uimp Rated Imp Wstd Voltage | 6 kV EN/IEC 60947-1 |
| Product Weight | 0.75 lb(US) (0.34 kg) |
| Repeat Accuracy | 2 % |
| Terminals Description ISO n°1 | (3-4)NC (1-2)NC |
| Depth | 4.17 in (106 mm) |
| Height | 4.53 in (115 mm) |
| Width | 2.83 in (72 mm) |
| Standards | EN/IEC 60730 CE |
| Ambient Air Temp For Op | 32…113 °F (0…45 °C) |
| Ambient Air Temp For Storage | -22…176 °F (-30…80 °C) |
| Protective Treatment | TC |
| Electrical Shock Protect Class | Class I IEC 536 |
| IP Degree Of Protection | IP65 EN/IEC 60529 |
Powered by ![]()
Based on 2 User Reviews
1619 Boyd St, Santa Ana, CA 92705
(714) 835-6211
(714) 972-2366