| Part Number | XMLR100M2P06 |
|---|---|
| Country of Origin | CH |
| UPC | 389119611381 |
| UPC11 | 38911961138 |
| EAN | 3389119611381 |
| Availability | N |
| Lead Time | 35 |
| ECCN | EAR99 |
| HTs Code | 9032200000 |
| Prop 65 | This product can expose you to chemicals including: Di-isodecyl phthalate (DIDP) and Diisononyl phthalate (DINP) which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov |
| RoHS Compliant | Yes |
| Discount Schedule | DS2 |
| Return Indicator | No |
| Depth | 1.65 inch |
| Height | 3.46 inch |
| Width | 1.61 inch |
| Weight | 0.41 pound |
| Range Of Product | OsiSense XM |
|---|---|
| Product Or Component Type | Electronic pressure sensors |
| Pressure Sensor Type | Pressure transmitter |
| Pressure Swt Type Of Operation | Pressure switch with 2 switching outputs |
| Device Short Name | XMLR |
| Pressure Sensor Size | 1450 psi (9997.40 kPa) 1450.38 psi (100 bar) |
| Max Perm Accidental Pressure | 30 MPa 4350 psi (29992.19 kPa) 4351.13 psi (300 bar) |
| Destruction Pressure | 8700 psi (59984.39 kPa) 8702.26 psi (600 bar) 60 MPa |
| Controlled Fluid | Fresh water 32…176 °F (0…80 °C)) Air -4…176 °F (-20…80 °C)) Hydraulic oil -4…176 °F (-20…80 °C)) Refrigeration fluid -4…176 °F (-20…80 °C)) |
| Fluid Connection Type | 1/4" - 18 NPT (female) |
| [Us] Rated Supply Voltage | 24 V DC SELV 17…33 V) |
| Current Consumption | <= 50 mA |
| Electrical Connection | Male connector M12, 4 pins |
| Type Of Output Signal | Discrete |
| Discrete Output Type | Solid state PNP, 2 NO/NC programmable |
| Maximum Switching Current | 250 mA |
| Contacts Type And Composition | 2 NO/NC programmable |
| Type Of Scale | Fixed differential |
| Voltage Drop | 2 V |
| Adj Range High Setting | 116…1450 psi (799.79…9997.40 kPa) 0.8…10 MPa 116.03…1450.38 psi (8…100 bar) |
| Adj Range Low Setting | 0.5…9.7 MPa 72.5…1407 psi (499.87…9700.92 kPa) 72.52…1406.87 psi (5…97 bar) |
| Minimum Differential Travel | 0.3 MPa 43.51 psi (3 bar) 43.5 psi (299.92 kPa) |
| Materials In Contact Wth Fluid | 316L stainless steel |
| Front Material | Polyester |
| Housing Material | Polyacrylamide 316L stainless steel |
| Operating Position | Any position, but disposals can falsified the measurement in case of upside down mounting |
| Protection Type | Overload protection Reverse polarity Overvoltage protection Short-circuit protection |
| Response Time On Output | <= 5 ms discrete output |
| Switching Output Time Delay | 0...50 s in steps of 1 second |
| Display Type | 4 digits 7 segments |
| Local Signalling | Light ON when switch is actuated 2 LEDs yellow) |
| Display Response Time Type | Fast 50 ms Normal 200 ms Slow 600 ms |
| Delay First Up | 300 ms |
| Overall Accuracy | <= 1 % of the measuring range |
| Measurement Accuracy On Switching Output | <= 0.6 % of the measuring range |
| Repeat Accuracy | <= 0.2 % of the measuring range |
| Drift Of The Sensitivity | +/- 0.03 % of measuring range/°C |
| Drift Of The Zero Point | +/- 0.1 % of measuring range/°C |
| Display Accuracy | <= 1 % of the measuring range |
| Mechanical Durability | 10000000 cycles |
| Depth | 1.65 in (42 mm) |
| Height | 3.46 in (88 mm) |
| Width | 1.61 in (41 mm) |
| Product Weight | 0.41 lb(US) (0.186 kg) |
| Uimp Rated Imp Wstd Voltage | 0.5 kV DC |
| Electromagnetic Compatibility | Susceptibility to electromagnetic fields 10 V/m 80...2000 MHz EN/IEC 61000-4-3 Immunity to conducted RF disturbances 10 V 0.15...80 MHz EN/IEC 61000-4-6 Surge immunity test 1 kV EN/IEC 61000-4-5 Electrical fast transient/burst immunity test 2 kV EN/IEC 61000-4-4 Electrostatic discharge immunity test 8 kV air, 4 kV contact EN/IEC 61000-4-2 |
| Marking | CE |
| Product Certifications | CULus EAC |
| Standards | EN/IEC 61326-2-3 UL 61010-1 |
| Ambient Air Temp For Op | -4…176 °F (-20…80 °C) |
Powered by ![]()