| Part Number | XMLK025B2D21 |
|---|---|
| Country of Origin | CH |
| UPC | 785901946144 |
| UPC11 | 78590194614 |
| EAN | 3389119048682 |
| Availability | N |
| Lead Time | 27 |
| UNSPSC | 39122210 |
| ECCN | EAR99 |
| HTs Code | 9032200000 |
| Prop 65 | This product can expose you to chemicals including: Di-isodecyl phthalate (DIDP) and Diisononyl phthalate (DINP) which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov |
| RoHS Compliant | Yes |
| Discount Schedule | DS2 |
| Return Indicator | No |
| Weight | 0.24 pound |
| Range Of Product | OsiSense XM |
|---|---|
| Product Or Component Type | Electronic pressure sensors |
| Pressure Sensor Type | Pressure transmitter |
| Pressure Sensor Name | XMLK |
| Electrical Circuit Type | Control circuit |
| Pressure Sensor Size | 362.59 psi (25 bar) |
| Local Display | Without |
| Controlled Fluid | Air 32…176 °F (0…80 °C)) Fresh water 32…176 °F (0…80 °C)) |
| Fluid Connection Type | G 1/4A (male) DIN 3852-E |
| Electrical Connection | 1 male connector M12 4 pins |
| [Us] Rated Supply Voltage | 24 V DC SELV 8…33 V) |
| Current Consumption | < 20 mA |
| Type Of Output Signal | Analogue |
| Analogue Output Function | 4...20 mA, 2-wire |
| Quantity Per Set | Set of 1 |
| Type Of Packing | Individual |
| Pressure Setting Range | 0.00…362.59 psi (0…25 bar) |
| Max Perm Accidental Pressure | 725.19 psi (50 bar) |
| Destruction Pressure | 1087.78 psi (75 bar) |
| Materials In Contact Wth Fluid | Nitrile (NBR) Stainless steel type AISI 303 Ceramic |
| Operating Position | Any position |
| Protection Type | Load short-circuit Reverse polarity |
| Electromagnetic Compatibility | Electrostatic discharge immunity test EN/IEC 61000-4-2 8 kV air, 6 kV contact Susceptibility to electromagnetic fields EN/IEC 61000-4-3 10 V/m 80...1000 MHz Electrical fast transient/burst immunity test EN/IEC 61000-4-4 2 kV 1.2/50 µs shock waves immunity test EN/IEC 61000-4-5 500 V 12 Ohm, 1 kV 42 Ohm Radiated RF fields EN/IEC 61000-4-6 10 V 0.15...80 MHz Immunity to magnetic fields EN/IEC 61000-4-8 30 A/m 50 Hz |
| Uimp Rated Imp Wstd Voltage | 0.5 kV |
| Response Time On Output | < 5 ms |
| Measurement Accuracy | +/- 1 % of the measuring range |
| Resolution | 0.1 % of the measuring range |
| Drift Of The Sensitivity | +/- 0.04 % of measuring range/°K |
| Drift Of The Zero Point | +/- 0.03 % of measuring range/°K |
| Long Term Stability | +/- 1 % of the measuring range |
| Mechanical Durability | 10000000 cycles |
| Product Weight | 0.24 lb(US) (0.11 kg) |
| Diameter | 1.42 in (36 mm) |
| Length | 2.66 in (67.5 mm) |
| Type Of Scale | Fixed differential |
| Standards | CE EN/IEC 61326-2-3 |
| Product Certifications | CSA C22.2 No 14 EAC RCM UL 508 |
| Protective Treatment | TC |
| Ambient Air Temp For Op | 32…176 °F (0…80 °C) |
| Ambient Air Temp For Storage | -13…176 °F (-25…80 °C) |
| Vibration Resistance | 20 gn 9…2000 Hz) EN/IEC 60068-2-6 |
| Shock Resistance | 25 gn 11 ms EN/IEC 60068-2-27 |
| IP Degree Of Protection | IP65 EN/IEC 60529 |
| Nema Degree Of Protection | NEMA 4 |
| Category | 21561 - XMLK,XMLP PRESSURE TRANSMITTERS |
| Discount Schedule | DS2 |
| GTIN | 00785901946144 |
| Nbr. Of Units In Pkg. | 1 |
| Country Of Origin | CH |
| EU RoHs Directive | Pro-active compliance (Product out of EU RoHS legal scope) |