This Zelio RM22UA control relay allows monitoring of overvoltage control. This modular control relay is ideal for monitoring of electrical values and voltage variation in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market slim form-factors with 22.5mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 1-pole DIN device. It also offers a selectable memory function, integral LED for indicating control status, sealable cover, with simple and precise settings with screw trimmers. It provides automatic shutdown management and fault information to user for a quick fault identification and troubleshooting. multi function controller for wide choice selected in hard-wired logic automated systems: ideal for refurbishment of old installations without using a PLC.
Add to Quote CataloguePart Number | RM22UA23MR |
---|---|
Country of Origin | ID |
UPC | 785901057826 |
UPC11 | 78590105782 |
EAN | 3606480792229 |
Availability | N |
Lead Time | 50 |
UNSPSC | 39122329 |
HTs Code | 8536490080 |
Prop 65 | This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Discount Schedule | CP2 |
Return Indicator | No |
Width | 0.89 inch |
Weight | 0.24 pound |
Range Of Product | Zelio Control |
---|---|
Product Or Component Type | Modular measurement and control relays |
Relay Type | Voltage control relay |
Network Number Of Phases | 1 phase |
Supply Circuit Type | DC |
Relay Name | RM22UA |
Relay Monitored Parameters | Overvoltage detection |
Time Delay Type | Without |
Switching Capacity In Va | 2000 VA |
Measurement Range | 15...500 V voltage AC/DC 50/60 Hz |
Reset Time | 1500 ms at maximum voltage |
Maximum Switching Voltage | 250 V AC |
Minimum Switching Current | 10 mA 5 V DC |
Maximum Switching Current | 8 A AC |
[Us] Rated Supply Voltage | 24...240 V AC/DC 50/60 Hz |
Supply Voltage Limits | 20.4…264 V AC/DC |
Power Consumption In Va | 3.5 VA AC |
Power Consumption In W | 1.5 W DC |
Supply Voltage Frequency | 40...70 Hz +/- 10 % |
Resistance Across Terminals | 150 kOhm E2-M terminals 300 kOhm E1-M terminals 500 kOhm E3-M terminals |
Output Contacts | 2 C/O |
Hysteresis | 5…50 % adjustable threshold setting |
Run-Up Delay At Power-Up | 600 ms |
Measuring Cycle | 100 ms measurement cycle as true rms value |
Repeat Accuracy | +/- 0.5 % input and measurement circuit |
Measurement Error | < 1 % over the whole range with voltage variation 0.05 %/°C with temperature variation |
Response Time | <= 500 ms |
Overvoltage Category | III IEC 60664-1 |
Insulation Resistance | > 100 MOhm 500 V DC IEC 60255-27 |
Insulation | Between supply and measurement |
Mounting Position | Any position |
Connections - Terminals | Screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end Screw terminals, 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end |
Tightening Torque | 5.31…8.85 lbf.in (0.6…1 N.m) IEC 60947-1 |
Housing Material | Self-extinguishing plastic |
Status Led | Relay ON LED Yellow) Power ON LED Green) |
Mounting Support | 35 mm DIN rail EN/IEC 60715 |
Electrical Durability | 100000 cycles |
Mechanical Durability | 10000000 cycles |
Utilisation Category | AC-15 IEC 60947-5-1 DC-13 IEC 60947-5-1 AC-1 IEC 60947-4-1 DC-1 IEC 60947-4-1 |
Safety Reliability Data | MTTFd = 308.2 years B10d = 290000 |
Contacts Material | Cadmium free |
Width | 0.89 in (22.5 mm) |
Product Weight | 0.24 lb(US) (0.11 kg) |
Immunity To Microbreaks | 10 ms |
Electromagnetic Compatibility | Immunity for residential, commercial and light-industrial environments EN/IEC 61000-6-1 Immunity for industrial environments EN/IEC 61000-6-2 Emission standard for residential, commercial and light-industrial environments EN/IEC 61000-6-3 Emission standard for industrial environments EN/IEC 61000-6-4 Electrostatic discharge 6 kV contact discharge)level 3 IEC 61000-4-2 Electrostatic discharge 8 kV air discharge)level 3 IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test 10 V/mlevel 3 IEC 61000-4-3 Electrical fast transient/burst immunity test 4 kV direct)level 4 IEC 61000-4-4 Electrical fast transient/burst immunity test 2 kV capacitive coupling)level 4 IEC 61000-4-4 Surge immunity test 4 kV common mode)level 4 IEC 61000-4-5 Surge immunity test 2 kV differential mode)level 4 IEC 61000-4-5 Conducted and radiated emissionsclass B group 1 CISPR 11 Conducted and radiated emissionsclass B CISPR 22 |
Standards | EN/IEC 60255-1 |
Product Certifications | CE China RoHS CCC GL RCM UL EAC CSA |
Ambient Air Temp For Storage | -40…158 °F (-40…70 °C) |
Ambient Air Temp For Op | -4…122 °F (-20…50 °C) 60 Hz -4…140 °F (-20…60 °C) 50 Hz AC/DC |
Relative Humidity | 93…97 % 77…131 °F (25…55 °C) IEC 60068-2-30 |
Powered by
Based on 2 User Reviews
1619 Boyd St, Santa Ana, CA 92705
(714) 835-6211
(714) 972-2366