This Zelio RM35-U multi function control relay allows monitoring of voltage control. This modular multi function control relay is ideal for monitoring of electrical values and voltage variation in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market medium form-factors with 35mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 3-pole DIN device. It also offers a selectable memory function, integral LED for indicating control status, sealable cover, with simple and precise settings with screw trimmers. It provides automatic shutdown management and fault information to user for a quick fault identification and troubleshooting. multi function controller for wide choice selected in hard-wired logic automated systems: ideal for refurbishment of old installations without using a PLC.
Add to Quote CataloguePart Number | RM35UA11MW |
---|---|
Country of Origin | ID |
UPC | 785901597230 |
UPC11 | 78590159723 |
EAN | 3389119405294 |
Availability | N |
Lead Time | 43 |
UNSPSC | 39122331 |
HTs Code | 8536410030 |
Prop 65 | This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Discount Schedule | CP2 |
Return Indicator | No |
Width | 1.38 inch |
Weight | 0.18 pound |
Range Of Product | Zelio Control |
---|---|
Product Or Component Type | Modular measurement and control relays |
Relay Type | Multifunction voltage control relay |
Relay Name | RM35UA |
Relay Monitored Parameters | Overvoltage or undervoltage detection |
Time Delay | Adjustable 0.3...30 s, 0 + 10 % on crossing the threshold |
Switching Capacity In Va | 1250 VA |
Minimum Switching Current | 10 mA 5 V DC |
Maximum Switching Current | 5 A AC/DC |
Power Consumption In Va | 0…3.5 VA AC |
Measurement Range | 0.05...5 V voltage |
Utilisation Category | AC-12 IEC 60947-5-1 AC-13 IEC 60947-5-1 AC-14 IEC 60947-5-1 AC-15 IEC 60947-5-1 DC-12 IEC 60947-5-1 DC-13 IEC 60947-5-1 DC-14 IEC 60947-5-1 |
Reset Time | 1500 ms time delay |
Maximum Switching Voltage | 250 V AC/DC |
[Us] Rated Supply Voltage | 24...240 V AC/DC 50/60 Hz +/- 10 % |
Supply Voltage Limits | 20.4…264 V AC/DC |
Power Consumption In W | 0.6 W DC |
Immunity To Microbreaks | 10 ms |
Control Circuit Frequency | 40...70 Hz +/- 10 % |
Resistance Across Terminals | 30 mOhm E2-M terminals 5 mOhm E1-M terminals 50 mOhm E3-M terminals |
Output Contacts | 2 C/O |
Nominal Output Current | 5 A |
Measuring Cycle | 30 ms measurement cycle as true rms value |
Hysteresis | 5…50 % threshold setting |
Delay At Power Up | 600 ms |
Measurement Accuracy | +/- 10 % of the full scale value |
Repeat Accuracy | +/- 0.5 % input and measurement circuit +/- 2 % time delay |
Measurement Error | +/- 0.05 %/°C with temperature variation < 1 % over the whole range with voltage variation |
Polarity | Non reversible polarity on DC supply |
Sensitivity Scale | 0.05...0.5 V E1-M terminals 0.3...3 V E2-M terminals 0.5...5 V E3-M terminals |
Threshold Setting | 10...100 % |
Quality Labels | CE |
Overvoltage Category | III IEC 60664-1 |
Insulation Resistance | > 500 MOhm 500 V DC between supply and relay output IEC 60255-5 > 500 MOhm 500 V DC between measurement and relay output IEC 60664-1 > 1 MOhm 500 V DC between supply and measurement IEC 60255-5 > 500 MOhm 500 V DC between supply and relay output IEC 60664-1 > 500 MOhm 500 V DC between measurement and relay output IEC 60255-5 > 1 MOhm 500 V DC between supply and measurement IEC 60664-1 |
Ui Rated Insulation Voltage | 250 V IEC 60664-1 600 V IEC 60664-1 |
Operating Voltage Tolerance | 15 % + 10 % Un |
Operating Position | Any position without derating |
Connections - Terminals | Screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end Screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end Screw terminals, 1 x 0.2...2 x 2.5 mm² AWG 24...AWG 12) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end |
Tightening Torque | 5.31…8.85 lbf.in (0.6…1 N.m) IEC 60947-1 |
Housing Material | Self-extinguishing plastic |
Local Signalling | Power ON LED green) Relay ON LED yellow) |
Mounting Support | 35 mm symmetrical DIN rail EN/IEC 60715 |
Electrical Durability | 100000 cycles |
Mechanical Durability | 30000000 cycles |
Operating Rate | <= 360 operations/hour full load |
Safety Reliability Data | B10d = 290000 MTTFd = 308.2 years |
Width | 1.38 in (35 mm) |
Product Weight | 0.18 lb(US) (0.08 kg) |
Compatibility Code | RM3 |
Electromagnetic Compatibility | Emission standard for industrial environments EN/IEC 61000-6-4 Emission standard for residential, commercial and light-industrial environments EN/IEC 61000-6-3 Immunity for industrial environments NF EN/IEC 61000-6-2 |