Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
Multifunction phase control relay
RM35TF30SP01
Multifunction phase control relay
Specifications
Part Number RM35TF30SP01
Country of Origin ID
UPC 785901739647
UPC11 78590173964
EAN 3389119215442
Availability N
Lead Time 36
UNSPSC 39122329
ECCN EAR99
HTs Code 8536490075
Prop 65 This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Discount Schedule CP2
Return Indicator No
Width 1.38 inch
Weight 0.29 pound
Characteristics
Range Of Product Zelio Control
Product Or Component Type Modular measurement and control relays
Relay Type Multifunction control relay
Product Specific Application For 3-phase supply
Relay Name RM35TF
Relay Monitored Parameters Phase sequence Asymmetry Undervoltage and overvoltage in window mode Phase failure detection
Time Delay Adjustable 0.1...10 s, +/- 10 % of the full scale value
Switching Capacity In Va 1250 VA
Measurement Range 194...528 V AC
Reset Time 1500 ms at 480 V
Maximum Switching Voltage 250 V AC 250 V DC
Minimum Switching Current 10 mA 5 V DC
Maximum Switching Current 5 A AC 5 A DC
Supply Voltage Limits 194…528 V AC, 3 phase
Ctrl Circuit Voltage Limits 12 % + 10 % Un
Power Consumption In Va 0…22 VA 400 V AC 50 Hz
Voltage Detection Threshold < 194 V
Control Circuit Frequency 50...60 Hz +/- 10 %
Output Contacts 2 C/O
Nominal Output Current 5 A
Hysteresis 2 %
Delay At Power Up 650 ms
Measuring Cycle 140 ms measurement cycle as true rms value
Threshold Adjustment Voltage 2...20 % of Un selected -12...-2 % in the range 220 V AC +2...+10 % in the range 480 V AC -20...-2 % in the range 380...480 V AC +2...+20 % in the range 220...440 V AC
Voltage Range 220...480 V phase to phase
Adj Of Asymmetry Threshold 5...15 % of Un selected
Repeat Accuracy 0.3 % time delay 0.5 % input and measurement circuit
Measurement Error < 1 % over the whole range with voltage variation 0.05 %/°C with temperature variation
Response Time < 200 ms in the event of a fault)
Marking CE
Overvoltage Category III IEC 60664-1
Insulation Resistance > 500 MOhm 500 V DC IEC 60255-5 > 500 MOhm 500 V DC IEC 60664-1
Ui Rated Insulation Voltage 400 V IEC 60664-1
Supply Frequency 50/60 Hz +/- 10 %
Operating Position Any position without derating
Connections - Terminals Screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end Screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
Tightening Torque 5.31…8.85 lbf.in (0.6…1 N.m) IEC 60947-1
Housing Material Self-extinguishing plastic
Local Signalling Power ON LED green) Relay ON LED yellow) Fault LED yellow)
Mounting Support 35 mm symmetrical DIN rail EN/IEC 60715
Electrical Durability 100000 cycles
Mechanical Durability 30000000 cycles
Operating Rate <= 360 operations/hour full load
Utilisation Category AC-12 IEC 60947-5-1 AC-13 IEC 60947-5-1 AC-14 IEC 60947-5-1 AC-15 IEC 60947-5-1 DC-12 IEC 60947-5-1 DC-13 IEC 60947-5-1
Safety Reliability Data B10d = 360000 MTTFd = 399.5 years
Width 1.38 in (35 mm)
Product Weight 0.29 lb(US) (0.13 kg)
Electromagnetic Compatibility Emission standard for industrial environments EN/IEC 61000-6-4 Emission standard for residential, commercial and light-industrial environments EN/IEC 61000-6-3 Immunity for industrial environments EN/IEC 61000-6-2
Standards EN/IEC 60255-1
Product Certifications CSA C-tick GL GOST UL
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews