Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
Motor Management, TeSys T, motor controller, CANopen, 6 logic inputs, 3 relay logic outputs, 5 to 100A, 100 to 240 VAC
LTMR100CFM
Motor Management, TeSys T, motor controller, CANopen, 6 logic inputs, 3 relay logic outputs, 5 to 100A, 100 to 240 VAC

TeSys T is a motor management system that provides full motor monitoring, control, and protection when used with short circuit protection and a contactor. It manages most critical processes while reducing downtime and increasing productivity as well as predicts what will happen in the process, as it accurately monitors current, voltage, and power over a wide range. This motor management system is also a flexible system that supports six communication protocols which are Modbus™, CANopen, DeviceNet™, Profibus™, Ethernet/IP, and Modbus/TCP. TeSys T motor management system consist of several components which include the LTMR controller, the expansion module, HMI and software along with several accessories. The LTMR controller is the main component of the system that manages the basic functions. This includes the measurement of the ground current, motor temperature, three phase current of the motor, the controller also includes logic inputs and outputs which is used in fault management. The expansion module is directly connected to the controller and provides additional inputs as well as measure the voltage between the phases which allow the controller the monitor additional functions. TeSys T is highly reliable and has a very long product life thanks to a state-of-the-art component selection, to the all in one design and to the advanced electronic protection. TeSys T can be integrated in many different types of harsh environment such as dusty atmospheres, marine applications, high vibration applications and corrosive atmospheres and is used in Metal/Mining/Mineral, Oil & Gas, Water Wastewater. This is a TeSys T LTMR controller that measure current range of 5-100A with a supply voltage of 100-240 Vac and uses CANopen as the communication protocol. This controller measures temperature, phase current, imbalance current, average current and earth-fault current. The dimensions of this device are 61 mm (H) X 91 mm (W) X 122.5 mm (D) and it weighs 0.53 kg. Controller has the following certifications: UL, CSA NOM, ATEX, BV, EAC, RINA, LROS, DNV, ABS, GL, KERI, RMRoS, C-Tick and CCC.

Add to Quote Catalogue
Specifications
Part Number LTMR100CFM
Country of Origin CN
UPC 785901498582
UPC11 78590149858
EAN 3389119404730
Availability S
Lead Time 28
UNSPSC 39122214
ECCN EAR99
HTs Code 8537109160
RoHS Compliant Yes
Discount Schedule I12
Return Indicator Yes
Depth 4.82 inch
Height 2.40 inch
Width 3.58 inch
Weight 1.17 pound
Characteristics
Range TeSys
Product Name TeSys T
Device Short Name LTMR
Product Or Component Type Motor controller
Device Application Equipment monitoring and control
Measurement Current 5…100 A
[Us] Rated Supply Voltage 100...240 V AC 50/60 Hz
Current Consumption 8...62.8 mA
Supply Voltage Limits 93.5…264 V AC
Communication Port Protocol CANopen
Bus Type CANopen ISO 1198 1...127 10...1000 kbit/s, SUB-D 9 4 twisted shielded pairs cable CANopen ISO 1198 1...127 10...1000 kbit/s, terminal block 4 twisted shielded pairs cable
Ui Rated Insulation Voltage 690 V EN/IEC 60947-1 690 V CSA C22.2 No 14 690 V UL 508
Uimp Rated Imp Wstd Voltage 4 kV supply, inputs and outputs EN/IEC 60947-4-1 6 kV current or voltage measurement circuit EN/IEC 60947-4-1 0.8 kV communication circuit EN/IEC 60947-4-1
Short-Circuit Withstand 100 kA EN/IEC 60947-4-1
Associated Fuse Rating 4 A gG output 0.5 A gG control circuit
Protection Type Thermal protection Locked rotor Phase failure Earth-leakage protection Overload (long time) Power factor variation Phase unbalance Load fluctuation Thermal overload protection Reverse polarity protection Overload
Ntw And Machine Diagnosis Type Event recording Trip history information Starting current and time Running hours counter/operating time Motor control command recording Remaining operating time before overload tripping Fault recording Phase fault and earth fault trip counters Waiting time after overload tripping Trip context information
Logic Input Number 6
Input Current 3.1 mA 100 V 7.5 mA 240 V
Current State 0 Guaranteed Logic input 0...40 V <= 15 mA 25 ms
Current State 1 Guaranteed Logic input 79...264 V >= 2 mA 25 ms
Maximum Output Switching Frequency 2 Hz
Load Current 5 A 250 V AC logic output 5 A 30 V DC logic output
Permissible Power 480 VA AC-15), Ie = 2 A, 500000 cycles output) 30 W DC-13), Ie = 1.25 A, 500000 cycles output)
Operating Rate 1800 cyc/h
Contacts Type And Composition 1 NO + 1 NC fault signal 3 NO
Metering Type Earth-fault current Phase current I1, I2, I3 RMS Imbalance current Temperature Average current Iavg
Measurement Accuracy 5...15 % earth fault current internal measurement 1 % voltage 100...830 V) 3 % power factor 5 % earth fault current external measurement +/- 30 min/year internal clock 0,02 temperature 5 % active and reactive power 0,02 current
Overvoltage Category III
Connection Pitch 0.20 in (5.08 mm)
Connections - Terminals Control circuit connector 1 0.00…0.00 in² (0.25…2.5 mm²) AWG 24...AWG 14)flexible with cable end Control circuit connector 1 0.00…0.00 in² (0.2…2.5 mm²) AWG 24...AWG 14)flexible without cable end Control circuit connector 1 0.00…0.00 in² (0.25…2.5 mm²) AWG 24...AWG 14)flexible without cable end Control circuit connector 1 0.00…0.00 in² (0.2…2.5 mm²) AWG 24...AWG 14)solid without cable end Control circuit connector 2 0.00…0.00 in² (0.2…1 mm²) AWG 24...AWG 14)flexible with cable end Control circuit connector 2 0.00…0.00 in² (0.2…1.5 mm²) AWG 24...AWG 14)flexible without cable end Control circuit connector 2 0.00…0.00 in² (0.5…1.5 mm²) AWG 24...AWG 14)flexible without cable end Control circuit connector 2 0.00…0.00 in² (0.2…1 mm²) AWG 24...AWG 14)solid without cable end
Tightening Torque Control circuit 4.43…5.31 lbf.in (0.5…0.6 N.m) flat 0.12 in (3 mm)
Pollution Degree 3
Electromagnetic Compatibility Electrostatic discharge, 3 8 kV air, 6 kV contact)EN/IEC 61000-4-2) Radiated RF fields, 3 10 V/m)EN/IEC 61000-4-3) Fast transients immunity test, level 3 2 kV)EN/IEC 61000-4-4) Fast transients immunity test, level 4 4 kV)EN/IEC 61000-4-4) Voltage dips and interruptions immunity test 70 %, 500 ms)EN/IEC 61000-4-11) Conducted RF disturbances 10 V)EN/IEC 61000-4-6) Surges 0.5 kV)EN/IEC 61000-4-5) Surges 1 kV)EN/IEC 61000-4-5) Surges 1 kV)EN/IEC 61000-4-5) Surges 2 kV)EN/IEC 61000-4-5) Surges 2 kV)EN/IEC 61000-4-5) Surges 4 kV)EN/IEC 61000-4-5) Surges 2 kV)EN/IEC 61000-4-5)
Width 3.58 in (91 mm)
Height 2.40 in (61 mm)
Depth 4.82 in (122.5 mm)
Product Weight 1.17 lb(US) (0.53 kg)
Web Services Web server
Compatibility Code LTMR
Standards IEC 60947-4-1 CSA C22.2 No 14 IACS E10 EN 60947-4-1 UL 508
Product Certifications LROS (Lloyds register of shipping) DNV UL EAC GL CCC BV ABS KERI ATEX NOM RINA RMRoS C-tick CSA
Protective Treatment 12 x 24 hour cycles EN/IEC 60068-2-30 48 h EN/IEC 60070-2-11 TH EN/IEC 60068
Fire Resistance 1202 °F (650 °C) EN/IEC 60695-2-12 1760 °F (960 °C) UL 94
Ambient Air Temp For Op -4…140 °F (-20…60 °C)
Ambient Air Temp For Storage -40…176 °F (-40…80 °C)
Operating Altitude <= 6561.68 ft (2000 m) without derating
Mechanical Robustness Vibrations mounted on symmetrical rail1 Gn, 5...300 Hz EN/IEC 60068-2-6 Vibrations plate mounted4 Gn, 5...300 Hz EN/IEC 60068-2-6 Shocks half sine wave acceleration15 Gn for 11 ms EN/IEC 60068-2-27
IP Degree Of Protection IP20
Category 22338 - SOLID STATE OVERLOAD RELAYS
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews