This XPSAR safety module monitors emergency shutdown pushbuttons, limit switches and light curtains. It meets the requirements of Performance Level PL e/Category 4 conforming to standard EN/ISO 13849-1 and SILCL3 conforming to EN/IEC 61508 and EN/IEC 62061. It can be used for monitoring emergency stop circuits conforming to EN/ISO 13850 and EN/IEC 60204-1 and electrical monitoring of switches activated by protection devices conforming to standard EN/ISO 14119. And for monitoring of type 4 light curtains conforming to EN/IEC 61496-1 that have solid-state safety outputs with test function (light curtains XUS L). It is compatible with emergency push buttons, limit switches and safety light curtains, the 3 most common safety sensors in the industry. It has removable terminals for easier and better control wires tightening, thus improving installation reliability. It has additional solid-state output for communication with PLCs about safety status of your process.
Brand: Telemecanique
Add to Quote CataloguePart Number | XPSAR371144P |
---|---|
Country of Origin | ID |
UPC | 785901672159 |
UPC11 | 78590167215 |
EAN | 3389110274325 |
Availability | N |
Lead Time | 25 |
UNSPSC | 32151802 |
ECCN | EAR99 |
HTs Code | 8536490075 |
Prop 65 | This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Discount Schedule | SAF2 |
Return Indicator | No |
Weight | 0.88 pound |
Range Of Product | Preventa Safety automation |
---|---|
Product Or Component Type | Preventa safety module |
Safety Module Name | XPSAR |
Safety Module Application | For emergency stop, switch and safety light curtain monitoring |
Function Of Module | Monitoring of a movable guard Emergency stop with 2 NC contacts monitoring 2-channel wiring Multiple emergency stop monitoring 2-channel wiring Emergency stop monitoring 1-channel wiring Monitoring of a movable guard associated with 2 switches and automatic start Monitoring of electro-sensitive protection equipment (ESPE) |
Safety Level | Can reach PL e/category 4 EN/ISO 13849-1 Can reach SILCL 3 EN/IEC 62061 |
Safety Reliability Data | DC > 99 % EN/ISO 13849-1 MTTFd = 277.8 years EN/ISO 13849-1 PFHd = 2.22E-9 1/h EN/IEC 62061 |
Type Of Start | Configurable |
Connections - Terminals | Captive screw clamp terminals, removable terminal block, 1 x 0.2...1 x 2.5 mm² flexible with cable end, with double bezel Captive screw clamp terminals, removable terminal block, 1 x 0.2...1 x 2.5 mm² solid with cable end, with double bezel Captive screw clamp terminals, removable terminal block, 1 x 0.25...1 x 2.5 mm² flexible with cable end, with double bezel Captive screw clamp terminals, removable terminal block, 2 x 0.2...2 x 1 mm² solid with cable end, with double bezel Captive screw clamp terminals, removable terminal block, 2 x 0.2...2 x 1.5 mm² flexible with cable end, with double bezel Captive screw clamp terminals, removable terminal block, 2 x 0.25...2 x 1 mm² flexible with cable end, with double bezel Captive screw clamp terminals, removable terminal block, 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel |
Output Type | Relay instantaneous opening, 7 NO, volt-free |
Number Of Additional Circuits | 2 NC + 4 solid state outputs |
Us Rated Supply Voltage | 230 V AC - 15...10 % 24 V DC - 15...10 % |
Synchro Time Between Inputs | 100 ms |
Supply Frequency | 50/60 Hz |
Power Consumption In W | 4 W DC |
Power Consumption In Va | 9 VA AC |
Input Protection Type | Internal, electronic |
Time Delay Range | 0...30 s |
Uc Control Circuit Voltage | 24 V DC |
Line Resistance | 50 Ohm |
Breaking Capacity | 360 VA holding AC-15 C300 relay output 3600 VA inrush AC-15 C300 relay output |
Breaking Capacity | 20 mA 24 V 2 A 24 V DC-13)50 ms relay output |
Output Thermal Current | 10 A per relay relay output |
Ith Cnvtl Free Air Therm Crrt | 40 A |
Associated Fuse Rating | 10 A fast blow relay output EN/IEC 60947-5-1, DIN VDE 0660 part 200 6 A gG or gL relay output EN/IEC 60947-5-1, DIN VDE 0660 part 200 |
Minimum Output Current | 170 mA relay output |
Minimum Output Voltage | 17 V relay output |
Response Time On Input Open | 20 ms |
Ui Rated Insulation Voltage | 300 V 2)IEC 60947-5-1 300 V 2)DIN VDE 0110 part 1 |
Uimp Rated Imp Wstd Voltage | 4 kV III IEC 60947-5-1 4 kV III DIN VDE 0110 part 1 |
Local Signalling | 4 LEDs |
Current Consumption | 30 mA 24 V DC on power supply |
Mounting Support | 35 mm symmetrical DIN rail |
Product Weight | 0.88 lb(US) (0.4 kg) |
Standards | EN/IEC 60947-5-1 EN 1088/ISO 14119 EN/IEC 60204-1 EN/ISO 13850 |
Product Certifications | CSA UL TÜV |
IP Degree Of Protection | IP20 terminals)EN/IEC 60529 IP40 enclosure)EN/IEC 60529 |
Ambient Air Temp For Op | 14…131 °F (-10…55 °C) |
Ambient Air Temp For Storage | -13…185 °F (-25…85 °C) |
Category | 22477 - SAFETY MODULES (PREVENTA) |
Discount Schedule | SAF2 |
GTIN | 00785901672159 |
Nbr. Of Units In Pkg. | 1 |
Country Of Origin | ID |
Green Premium Status | Green Premium product |
EU RoHs Directive | Pro-active compliance (Product out of EU RoHS legal scope) |
Mercury Free | Yes |
WEEE | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
Pvc Free | Yes |
Warranty | 18 months |
Powered by
Based on 2 User Reviews
1619 Boyd St, Santa Ana, CA 92705
(714) 835-6211
(714) 972-2366