This Zelio RE17R timing relay can be set between 0.1 seconds and 100 hours, has an output rating of 8A, is 17.5mm wide and can be supplied with 24 V DC, 24 to 240 V AC. It also has 1 changeover contact SPDT (single pole double throw). It has one of market slimmest form-factors, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 1-pole DIN device. It also offers a sealable cover, simple and precise settings with rotary trimmers. This timer offers pause and summation control signals. Single function timer for a simple integration in hard-wired logic schematics: ideal for refurbishment of old installations without using a PLC.
Add to Quote Catalogue| Part Number | RE17RAMU |
|---|---|
| Country of Origin | ID |
| UPC | 785901284864 |
| UPC11 | 78590128486 |
| EAN | 3606480552670 |
| Availability | N |
| Lead Time | 48 |
| UNSPSC | 39122329 |
| ECCN | EAR99 |
| HTs Code | 8536490065 |
| Prop 65 | This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov |
| RoHS Compliant | Yes |
| Discount Schedule | CP2 |
| Return Indicator | Yes |
| Depth | 2.83 inch |
| Height | 3.54 inch |
| Width | 0.69 inch |
| Weight | 0.15 pound |
| Range Of Product | Zelio Time |
|---|---|
| Product Or Component Type | Modular timing relay |
| Discrete Output Type | Relay |
| Width | 0.69 in (17.5 mm) |
| Device Short Name | RE17R |
| Time Delay Type | At A |
| Time Delay Range | 1...10 min 10...100 h 0.1...1 s 6...60 s 6...60 min 1...10 s 1...10 h |
| Nominal Output Current | 8 A |
| Contacts Type And Composition | 1 C/O |
| Contacts Material | Cadmium free |
| Height | 3.54 in (90 mm) |
| Depth | 2.83 in (72 mm) |
| Control Type | Selector switch front panel |
| [Us] Rated Supply Voltage | 24...240 V AC 50/60 Hz 24 V DC |
| Voltage Range | 0.85...1.1 Us |
| Supply Frequency | 50...60 Hz +/- 5 % |
| Release Of Input Voltage | 10 V |
| Connections - Terminals | Screw terminals, 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12) solid without cable end Screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end |
| Tightening Torque | 5.31…8.85 lbf.in (0.6…1 N.m) IEC 60947-1 |
| Housing Material | Self-extinguishing |
| Repeat Accuracy | +/- 0.5 % IEC 61812-1 |
| Temperature Drift | +/- 0.05 %/°C |
| Voltage Drift | +/- 0.2 %/V |
| Setting Accuracy Of Time Delay | +/- 10 % of full scale 25 °C IEC 61812-1 |
| Control Signal Pulse Width | 100 ms with load in parallel typical 30 ms typical |
| Insulation Resistance | 100 MOhm 500 V DC IEC 60664-1 |
| Reset Time | 120 ms on de-energisation typical |
| On-Load Factor | 100 % |
| Power Consumption In Va | 0…32 VA 240 V AC |
| Power Consumption In W | 0.6 W 24 V DC |
| Minimum Switching Current | 10 mA 5 V DC |
| Maximum Switching Current | 8 A AC/DC |
| Maximum Switching Voltage | 250 V AC |
| Breaking Capacity | 2000 VA |
| Operating Frequency | 10 Hz |
| Electrical Durability | 100000 cycles resistive 8 A 250 V AC |
| Mechanical Durability | 10000000 cycles |
| Dielectric Strength | 2.5 kV 1 mA/1 minute 50 Hz IEC 61812-1 |
| Uimp Rated Imp Wstd Voltage | 5 kV 1.2/50 µs |
| Power On Delay | 100 ms |
| Marking | CE |
| Creepage Distance | 4 kV/3 IEC 60664-1 |
| Safety Reliability Data | B10d = 270000 MTTFd = 296.8 years |
| Mounting Position | Any position in relation to normal vertical mounting plane |
| Mounting Support | 35 mm DIN rail EN/IEC 60715 |
| Local Signalling | LED indicator on steady: relay energised, no timing in progress LED indicator 80 % ON and 20 % OFF flashing: timing in progress LED indicator 5 % ON and 95 % OFF pulsing: relay de-energised, no timing in progress (except function Di-D, Li-L) |
| Product Weight | 0.15 lb(US) (0.07 kg) |
| Time Delay Type | A, At |
| Functionality | On-delay timing |
| Compatibility Code | RE17 |