This Zelio REXL timing relay can be set between 0.1 seconds and 100 hours, has an output rating of 5A, is 48mm wide and can be supplied with 24V DC. It is a plug-in device, meaning it is quick and easy to install with the need for tools. It also offers a sealable cover, simple and precise settings with rotary trimmers. It is designed for socket plug in, this allows quick and easy installation and minimizes set up and repair time. Status display with 2 LEDs: visually inspect the status of you system without specialized tools.
Add to Quote CataloguePart Number | REXL4TMBD |
---|---|
Country of Origin | ID |
UPC | 785901468868 |
UPC11 | 78590146886 |
EAN | 3389119400077 |
Availability | S |
Lead Time | 43 |
UNSPSC | 39121523 |
ECCN | EAR99 |
HTs Code | 8536410045 |
Prop 65 | This product can expose you to chemicals including: Nickel compounds and Di-isodecyl phthalate (DIDP) which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Discount Schedule | CP2 |
Return Indicator | Yes |
Weight | 0.11 pound |
Range Of Product | Zelio Time |
---|---|
Product Or Component Type | Miniature timing relay |
Fixing Mode | Plug-in socket) |
Discrete Output Type | Relay |
Contacts Type And Composition | 4 C/O |
Component Name | REXL |
Time Delay Type | A |
Time Delay Range | 10...100 h 6...60 s 6...60 min 1...10 s 1...10 h 1...10 min 0.1...1 s |
Contacts Material | Cadmium free |
[Us] Rated Supply Voltage | 24 V DC |
Voltage Range | 0.9...1.1 Us |
In Rated Current | 5 A AC |
Repeat Accuracy | +/- 0.5 % |
Setting Accuracy Of Time Delay | 10 % at full scale 25 °C EN/IEC 61812-1 |
Temperature Drift | 0.05 %/°C |
Maximum Reset Time | 250 ms after time delay, on de-energisation 50 ms during time delay, on de-energisation |
Voltage Drift | +/- 0.2 %/V |
Maximum Switching Capacity | 4 x 5 A |
Maximum Temporary Permissible Current | 10 A < 10 s |
Minimum Switching Current | 100 mA |
Electrical Durability | 100000 cycles 250 V AC resistive |
Mechanical Durability | 10000000 cycles |
Maximum Power Consumption | 1.2 W |
Ui Rated Insulation Voltage | 250 V IEC 255 Group C 250 V VDE 0010 |
Output Overvoltage Protct | 2 J |
Surge Withstand | 2 kV EN/IEC 61000-4-5 level 3 |
Creepage Distance | 4 kV/3 IEC 60664-1 |
Local Signalling | Output in operation 1 LED red) Power ON 1 LED yellow) |
Product Weight | 0.11 lb(US) (0.05 kg) |
Immunity To Microbreaks | 5 ms |
Dielectric Strength | 2 kV 1 mA/1 minute 50 Hz EN/IEC 60601-1 2 kV 1 mA/1 minute 50 Hz EN/IEC 61812-1 |
Standards | EN/IEC 60601-2 EN 61000-6-2 73/23/EEC EN/IEC 61812-1 93/68/EEC EN/IEC 60601-1 89/336/EEC EN 50081-2 |
Product Certifications | UL CUL |
Ambient Air Temp For Op | -4…140 °F (-20…60 °C) |
Ambient Air Temp For Storage | -40…158 °F (-40…70 °C) |
IP Degree Of Protection | IP50 IEC 60529 |
Vibration Resistance | 0.35 mm 10…55 Hz)IEC 60068-2-6 |
Relative Humidity | 95 % without condensation IEC 60068-2-6 |
Resist Electrostatic Dischrg | 6 kV in contact EN/IEC 61000-4-2 level 3 8 kV in air EN/IEC 61000-4-2 level 3 |
Resist To Electromagn Fields | 9.14 V/m (10 V/m) EN/IEC 61000-4-3 level 3 |
Resistance To Fast Transients | 2 kV EN/IEC 61000-4-4 level 3 |
Imm To Radioelectric Fields | 10 V 0.15...80 MHz)EN/IEC 61000-4-6 level 3 |
Immunity To Voltage Dips | >= 95 % / 1 s EN/IEC 61000-4-11 30 % / 10 ms EN/IEC 61000-4-11 60 % / 100 ms EN/IEC 61000-4-11 |
Disturbance Radiated/Conducted | Class B EN 55022 (EN 55011 group 1) |
Category | 22370 - RE, RM MISC TIMERS & COUNTERS |
Discount Schedule | CP2 |
GTIN | 00785901468868 |
Nbr. Of Units In Pkg. | 1 |
Country Of Origin | ID |
Green Premium Status | Green Premium product |