This Zelio RM17-TU relay allows monitoring of power supply circuits in 3-phase networks. This modular multi function 3-phase supply control relay is ideal for monitoring of electrical values in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market slimmest form-factors with 17.5mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 1-pole DIN device. It also offers a sealable cover, simple and precise settings with screw trimmers. The product monitors its own power supply, when the power supply is abnormal, the output relay de-energizes. multi function controller for wide choice selected in hard-wired logic automated systems, ideal for refurbishment of old installations without using a PLC.
Add to Quote CataloguePart Number | RM17TU00 |
---|---|
Country of Origin | ID |
UPC | 785901832133 |
UPC11 | 78590183213 |
EAN | 3389119405096 |
Availability | S |
Lead Time | 51 |
UNSPSC | 39122331 |
ECCN | EAR99 |
HTs Code | 8536490075 |
Prop 65 | This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Discount Schedule | CP2 |
Return Indicator | Yes |
Width | 0.69 inch |
Weight | 0.29 pound |
Range Of Product | Zelio Control |
---|---|
Product Or Component Type | Modular measurement and control relays |
Relay Type | Multifunction control relay |
Product Specific Application | For 3-phase supply |
Relay Name | RM17TU |
Relay Monitored Parameters | Undervoltage detection Phase sequence Phase failure detection |
Time Delay | Adjustable 0.1...10 s, +/- 10 % of the full scale value |
Switching Capacity In Va | 1250 VA |
Measurement Range | 208...480 V voltage AC |
Reset Time | 1500 ms time delay |
Maximum Switching Voltage | 250 V AC 250 V DC |
Minimum Switching Current | 10 mA 5 V DC |
Maximum Switching Current | 5 A AC 5 A DC |
Supply Voltage Limits | 183…528 V AC |
Ctrl Circuit Voltage Limits | 12 % + 10 % Un |
Power Consumption In Va | 0…22 VA 400 V AC 50 Hz |
Control Circuit Frequency | 50...60 Hz +/- 10 % |
Output Contacts | 1 C/O |
Nominal Output Current | 5 A |
Measurement Voltage Limits | 183…528 V AC |
Hysteresis | 2 % |
Delay At Power Up | 650 ms |
Measuring Cycle | 150 ms measurement cycle as true rms value |
Threshold Adjustment Voltage | -2...-12 % in the range 208 V AC -2...-17 % in the range 220 V AC 2...20 % of Un selected +2...+17 % in the range 480 V AC |
Voltage Range | 208...480 V phase to phase |
Adj Of Asymmetry Threshold | 5...15 % of Un selected |
Repeat Accuracy | 0.5 % input and measurement circuit 3 % time delay |
Measurement Error | < 0.05 %/°C with temperature variation < 1 % over the whole range with voltage variation |
Phase Failure Sensitivity | 0.7 Un |
Response Time | < 200 ms in the event of a fault) |
Marking | CE |
Overvoltage Category | III IEC 60664-1 |
Insulation Resistance | > 500 MOhm 500 V DC IEC 60255-5 > 500 MOhm 500 V DC IEC 60664-1 |
Ui Rated Insulation Voltage | 400 V IEC 60664-1 |
Supply Frequency | 50/60 Hz +/- 10 % |
Operating Position | Any position without derating |
Connections - Terminals | Screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end Screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end |
Tightening Torque | 5.31…8.85 lbf.in (0.6…1 N.m) IEC 60947-1 |
Housing Material | Self-extinguishing plastic |
Local Signalling | Power ON LED green) Relay ON LED yellow) |
Mounting Support | 35 mm symmetrical DIN rail EN/IEC 60715 |
Electrical Durability | 100000 cycles |
Mechanical Durability | 30000000 cycles |
Operating Rate | <= 360 operations/hour full load |
Utilisation Category | AC-12 IEC 60947-5-1 AC-13 IEC 60947-5-1 AC-14 IEC 60947-5-1 AC-15 IEC 60947-5-1 DC-12 IEC 60947-5-1 DC-13 IEC 60947-5-1 |
Safety Reliability Data | MTTFd = 502.2 years B10d = 470000 |
Width | 0.69 in (17.5 mm) |
Product Weight | 0.29 lb(US) (0.13 kg) |
Electromagnetic Compatibility | Emission standard for industrial environments EN/IEC 61000-6-4 Emission standard for residential, commercial and light-industrial environments EN/IEC 61000-6-3 Immunity for industrial environments EN/IEC 61000-6-2 |
Standards | EN/IEC 60255-1 |