This Zelio RM35-UB allows monitoring of voltage control in 3-phase networks. This modular multi function 3-phase voltage control relay is ideal for monitoring of electrical values in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market medium form-factors with 35mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 3-pole DIN device. It also offers a sealable cover, simple and precise settings with screw trimmers. It provides automatic shutdown management and fault information to user for a quick fault identification and troubleshooting. multi function controller for wide choice selected in hard-wired logic automated systems, ideal for refurbishment of old installations without using a PLC.
Add to Quote Catalogue| Part Number | RM35UB330 |
|---|---|
| Country of Origin | ID |
| UPC | 785901539551 |
| UPC11 | 78590153955 |
| EAN | 3389119405324 |
| Availability | S |
| Lead Time | 51 |
| UNSPSC | 39122331 |
| ECCN | EAR99 |
| HTs Code | 8536490075 |
| Prop 65 | This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov |
| RoHS Compliant | Yes |
| Discount Schedule | CP2 |
| Return Indicator | Yes |
| Width | 1.38 inch |
| Weight | 0.18 pound |
| Range Of Product | Zelio Control |
|---|---|
| Product Or Component Type | Modular measurement and control relays |
| Relay Type | Voltage control relay |
| Product Specific Application | For 3-phase supply |
| Relay Name | RM35UB3 |
| Relay Monitored Parameters | Overvoltage and undervoltage between phases |
| Time Delay | Adjustable 0.3...30 s, 0 + 10 % on crossing the threshold |
| Switching Capacity In Va | 1250 VA |
| Minimum Switching Current | 10 mA 5 V DC |
| Maximum Switching Current | 5 A AC/DC |
| Power Consumption In Va | 0…22 VA 400 V AC 50 Hz |
| Measurement Range | 194...528 V voltage AC 50/60 Hz |
| Utilisation Category | AC-12 IEC 60947-5-1 AC-13 IEC 60947-5-1 AC-14 IEC 60947-5-1 AC-15 IEC 60947-5-1 DC-12 IEC 60947-5-1 DC-13 IEC 60947-5-1 DC-14 IEC 60947-5-1 |
| Reset Time | 1500 ms time delay |
| Maximum Switching Voltage | 250 V AC/DC |
| [Us] Rated Supply Voltage | 220...480 V AC 50/60 Hz +/- 10 % |
| Supply Voltage Limits | 194…528 V AC |
| Voltage Detection Threshold | 194 V |
| Control Circuit Frequency | 50...60 Hz +/- 15 % |
| Output Contacts | 1 C/O + 1 C/O, 1 per threshold |
| Nominal Output Current | 5 A |
| Measuring Cycle | 150 ms measurement cycle as true rms value |
| Hysteresis | 2 % |
| Delay At Power Up | 650 ms |
| Measurement Accuracy | +/- 10 % of the full scale value |
| Repeat Accuracy | +/- 0.5 % input and measurement circuit +/- 1 % time delay |
| Measurement Error | < 1 % over the whole range with voltage variation 0.05 %/°C with temperature variation |
| Response Time | < 200 ms in the event of a fault) |
| Quality Labels | CE |
| Overvoltage Category | III IEC 60664-1 |
| Insulation Resistance | > 500 MOhm 500 V DC IEC 60255-5 > 500 MOhm 500 V DC IEC 60664-1 |
| Ui Rated Insulation Voltage | 400 V IEC 60664-1 |
| Operating Position | Any position without derating |
| Connections - Terminals | Screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end Screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end Screw terminals, 1 x 0.2...2 x 2.5 mm² AWG 24...AWG 12) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end |
| Tightening Torque | 5.31…8.85 lbf.in (0.6…1 N.m) IEC 60947-1 |
| Housing Material | Self-extinguishing plastic |
| Local Signalling | Power ON LED green) Relay ON LED yellow) |
| Mounting Support | 35 mm symmetrical DIN rail EN/IEC 60715 |
| Electrical Durability | 10000 cycles |
| Mechanical Durability | 30000000 cycles |
| Operating Rate | <= 360 operations/hour full load |
| Safety Reliability Data | B10d = 300000 MTTFd = 319.6 years |
| Width | 1.38 in (35 mm) |
| Product Weight | 0.18 lb(US) (0.08 kg) |
| Functionality | Overvoltage and undervoltage detection |
| Compatibility Code | RM3 |
| Electromagnetic Compatibility | Emission standard for industrial environments EN/IEC 61000-6-4 Emission standard for residential, commercial and light-industrial environments EN/IEC 61000-6-3 Immunity for industrial environments NF EN/IEC 61000-6-2 |
| Standards | EN/IEC 60255-1 |
| Product Certifications | C-tick GOST CSA GL UL |
| Directives | 73/23/EEC - low voltage directive 89/336/EEC - electromagnetic compatibility |
Powered by ![]()