Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
MGE Galaxy 5500 60kVA 400-415V Single UPS Off Shore IP22 RAL 7035, Start-up 5X8
G55TUPU60HXS
MGE Galaxy 5500 60kVA 400-415V Single UPS Off Shore IP22 RAL 7035, Start-up 5X8
Specifications
Part Number G55TUPU60HXS
UPC 731304315735
UPC11 73130431573
EAN 0731304315735
Prop 65 This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov
Depth 33.66 inch
Height 85.83 inch
Width 28.03 inch
Weight 1005.31 pound
Characteristics
Presentation UPS is designed to meet the offshore standard requirement.
Lead Time Special Order - Call for Quoted Lead Times
Provided Equipment Installation guide User Manual
Bypass Wiring Configuration 4 wire (3PH + N) 5 wire (3PH + N + G)
Bypass Voltage Tolerance +/-10% settable from +/-4/6/8 and 10%
Max Bypass Input Current 87 A
Bypass Current Protection 125 A
Depth 33.66 in (85.5 cm)
Height 85.83 in (218 cm)
Product Weight 1005.31 lb(US) (456 kg)
Width 28.03 in (71.2 cm)
Network Frequency 45...65 Hz
Number Of Input Connectors 1 Hard Wire 4-wire (3PH + G) 1 Hard Wire 4-wire (3PH + N)
Input Voltage Limits 323...437 V 380 V 340...460 V 400 V 353...477 V 415 V
Inputvolt_Other 380 V 415 V
Maximum Input Current 115 A
Switching Current Capacity 125 A
Max Short Time Withstd Current 20 kA
Input Harmonic Distortion Less than 5% for full load
Input Protection Type GL fuse
Input Voltage 3 phase
Rated Power In W 54000 W
Max Configurable Power In W 54000 W
Harmonic Distortion Less than 2%
Output Frequency 50 Hz programmable +/- 0.5 / 1 / 2 / 4 / 6 / 8% sync to mains 50 Hz +/- 0.1 % for 50 Hz nominal not synced
Outputvolt_Other 380 V 415 V
Crest Factor 3 : 1
Ups Type Double Conversion Online
Wave Type Sine wave
Output Voltage Tolerance +/- 2% static and 100% load step
Output Harmonic Distortion < 1% linear load and < 2.5% non-linear load
Output Overload Operation 10 minutes @ 125% and 60 seconds @ 150%
Req Output Current Protection 87 A
Neutral Output Current 87 A
Bypass Type Built-in Maintenance Bypass Built-in Static Bypass Optional External Bypass
Output Voltage 400 V 3 phase
Product Certifications CE TÜV VDE
Standards EN/IEC 62040-1 EN/IEC 62040-2 EN/IEC 62040-3 ISO 9001
Ambient Air Temp For Op 32…104 °F (0…40 °C)
Relative Humidity 0…95 %
Operating Altitude 0...3333 ft
Ambient Air Temp For Storage -4…113 °F (-20…45 °C)
Storage Altitude 0…40000 ft (0.00…12192.00 m)
Acoustic Level 65 dBA
IP Degree Of Protection IP20 IP32
Battery Type External battery system
Additional Information Configurable for 400 or 415V 3 Phase nominal output voltage
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews