Limit switch XCKL – metal end plunger – 1NC+1NO – slow-break – Cable gland
XCKL510
Limit switch XCKL – metal end plunger – 1NC+1NO – slow-break – Cable gland
Specifications
Part Number XCKL510
Country of Origin FR
UPC 785901189022
UPC11 78590118902
EAN 3389110646573
Availability N
Lead Time 20
UNSPSC 39122213
ECCN EAR99
HTs Code 8536509055
Prop 65 This product can expose you to chemicals including: Di-isodecyl phthalate (DIDP) and Diisononyl phthalate (DINP) which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Discount Schedule T
Return Indicator No
Depth 1.18 inch
Height 2.83 inch
Width 2.05 inch
Weight 0.56 pound
Characteristics
Range Of Product OsiSense XC
Series Name Standard format
Product Or Component Type Limit switch
Device Short Name XCKL
Body Type Fixed
Head Type Plunger head
Material Metal
Body Material Zamak
Fixing Mode By the body
Movement Of Operating Head Linear
Type Of Operator Spring return plunger metal
Type Of Approach Vertical approach, 1 direction
Cable Entry 1 metal cable gland entry 0.24…0.53 in (6…13.5 mm)
Number Of Poles 2
Contacts Type And Composition 1 NC + 1 NO
Contact Operation Slow-break, break before make
Switch Actuation On end
Electrical Connection Screw-clamp terminals 1 x 0.5...2 x 2.5 mm²
Contacts Insulation Form Zb
Number Of Steps 1
Positive Opening With
Positive Opening Min Force 45 N
Minimum Force For Tripping 15 N
Minimum Actuation Speed 6 m/min
Maximum Actuation Speed 1.64 ft/s (0.5 m/s)
Repeat Accuracy 0.05 mm on the tripping points with 1 million operating cycles
Contact Code Designation A300, AC-15 (Ue = 240 V), Ie = 3 A EN/IEC 60947-5-1 appendix A Q300, DC-13 (Ue = 250 V), Ie = 0.27 A EN/IEC 60947-5-1 appendix A
Ithe Cnvtl Enclosed Therm Crrt 10 A AC
Ui Rated Insulation Voltage 300 VUL 508 500 V 3)IEC 60947-1 300 VCSA C22.2 No 14
Resistance Across Terminals 25 MOhm IEC 60255-7 category 3
Uimp Rated Imp Wstd Voltage 6 kV IEC 60664 6 kV IEC 60947-1
Short-Circuit Protection 10 A cartridge fuse gG
Electrical Durability 5000000 cycles, DC-13, inductive, 120 V, 4 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C 5000000 cycles, DC-13, inductive, 24 V, 7 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C 5000000 cycles, DC-13, inductive, 48 V, 10 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C
Mechanical Durability 20000000 cycles
Width 2.05 in (52 mm)
Height 2.83 in (72 mm)
Depth 1.18 in (30 mm)
Product Weight 0.56 lb(US) (0.255 kg)
Terminals Description ISO n°1 (21-22)NC (13-14)NO
Shock Resistance 50 gn 11 ms EN/IEC 60068-2-27
Vibration Resistance 25 gn 10…500 Hz)EN/IEC 60068-2-6
IP Degree Of Protection IP66 EN/IEC 60529
IK Degree Of Protection IK05 EN 50102
Electrical Shock Protect Class Class I IEC 61140 Class I NF C 20-030
Ambient Air Temp For Op -13…158 °F (-25…70 °C)
Ambient Air Temp For Storage -40…158 °F (-40…70 °C)
Protective Treatment TC
Product Certifications UL CSA
Standards CSA C22.2 No 14 UL 508 EN 60204-1 EN 60947-5-1 IEC 60947-5-1 IEC 60204-1