| Part Number | XCSTE5542 |
|---|---|
| Country of Origin | FR |
| UPC | 389110825541 |
| UPC11 | 38911082554 |
| EAN | 3389110825541 |
| Availability | F |
| Lead Time | 20 |
| UNSPSC | 39122213 |
| ECCN | EAR99 |
| HTs Code | 8536509055 |
| Prop 65 | This product can expose you to chemicals including: Di-isodecyl phthalate (DIDP) and Diisononyl phthalate (DINP) which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov |
| RoHS Compliant | Yes |
| Discount Schedule | T |
| Return Indicator | No |
| Depth | 1.30 inch |
| Height | 3.70 inch |
| Width | 4.33 inch |
| Weight | 0.79 pound |
| Range Of Product | Preventa Safety detection |
|---|---|
| Product Or Component Type | Safety switch |
| Component Name | XCSTE |
| Design | Rectangular |
| Material | Plastic |
| Head Type | Key operated turret head |
| Contacts Type And Composition | 1 NC + 1 NO |
| Contact Operation | Slow-break, break before make |
| Solenoid Contacts Type Compo | 1 NC slow-break) |
| Cable Entry | 1 entry tapped Pg 11 |
| Electromagnet Interlocking | Locking on energisation and unlocking on de-energisation of solenoid |
| [Us]&Nbsp;Solenoid&Nbsp;Rated&Nbsp;Supply Voltage | 230 V - 20...10 % |
| Cable Outer Diameter | 0.28…0.39 in (7…10 mm) |
| Electrical Connection | Terminal 1 x 0.5...2 x 1.5 mm² with or without cable end |
| Number Of Poles | 2 |
| Locking Options Description | With interlocking, locking by solenoid |
| Insulation | Double insulated |
| Positive Opening | With NC contact |
| Supply Voltage Type | AC/DC |
| Supply Frequency | 50/60 Hz |
| Load Factor | 1 |
| Power Consumption In Va | 10 VA |
| Mechanical Durability | 1000000 cycles |
| Positive Opening Min Force | 15 N |
| Minimum Actuation Speed | 0.03 ft/s (0.01 m/s) |
| Maximum Actuation Speed | 1.64 ft/s (0.5 m/s) |
| Ie Rated Operational Current | 0.55 A 125 V, DC-13, Q300 EN/IEC 60947-5-1 0.27 A 250 V, DC-13, Q300 EN/IEC 60947-5-1 3 A 120 V, AC-15, B300 EN/IEC 60947-5-1 1.5 A 240 V, AC-15, B300 EN/IEC 60947-5-1 |
| Ithe Cnvtl Enclosed Therm Crrt | 6 A |
| Ui Rated Insulation Voltage | 300 VUL 508 500 VEN/IEC 60947-1 300 VCSA C22.2 No 14 |
| Uimp Rated Imp Wstd Voltage | 6 kV EN/IEC 60947-5-1 |
| Short-Circuit Protection | 10 A cartridge fuse gG (gl) |
| Actutr Forcible Withdrawal Rtc | 500 N |
| Operating Rate | 10 cyc/mn for maximum durability |
| Safety Level | Can reach category 4 with the appropriate monitoring system and correctly wired EN/ISO 13849-1 Can reach PL = e with the appropriate monitoring system and correctly wired EN/ISO 13849-1 Can reach SIL 3 with the appropriate monitoring system and correctly wired EN/IEC 61508 |
| Safety Reliability Data | B10d = 5000000 value given for a life time of 20 years limited by mechanical or contact wear |
| Body Material | PA (polyamide) |
| Head Material | PA (polyamide) |
| Depth | 1.30 in (33 mm) |
| Height | 3.70 in (94 mm) |
| Width | 4.33 in (110 mm) |
| Product Weight | 0.79 lb(US) (0.36 kg) |
| Standards | EN/IEC 60204-1 UL 508 EN/ISO 12100 EN 1088/ISO 14119 EN/IEC 60947-5-1 CSA C22.2 No 14 |
| Product Certifications | CSA UL |
| Protective Treatment | TC |
| Ambient Air Temp For Op | -13…140 °F (-25…60 °C) |
| Ambient Air Temp For Storage | -40…158 °F (-40…70 °C) |
| Vibration Resistance | 5 gn 10…500 Hz)IEC 60068-2-6 |
| Shock Resistance | 10 gn 11 ms IEC 60068-2-27 |
| Electrical Shock Protect Class | Class II EN/IEC 61140 |
| IP Degree Of Protection | IP67 EN/IEC 60529 and EN/IEC 60947-5-1 |