Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
LIMIT SWITCH 600 VAC 10 AMP XCKJ +OPTIONS
XCKJ115H7
LIMIT SWITCH 600 VAC 10 AMP XCKJ +OPTIONS
Specifications
Part Number XCKJ115H7
Country of Origin FR
UPC 389118120785
UPC11 38911812078
EAN 3389118120785
Availability N
UNSPSC 39122213
ECCN EAR99
HTs Code 8536509055
Prop 65 This product can expose you to chemicals including: Di-isodecyl phthalate (DIDP) and Diisononyl phthalate (DINP) which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Discount Schedule T
Return Indicator No
Depth 1.42 inch
Height 3.31 inch
Width 1.69 inch
Weight 0.95 pound
Characteristics
Range Of Product OsiSense XC
Series Name Standard format
Product Or Component Type Limit switch
Device Short Name XCKJ
Sensor Design Form B CENELEC EN 50041
Body Type Plug-in body
Head Type Plunger head
Material Metal
Body Material Zamak
Head Material Zamak
Fixing Mode By the body
Movement Of Operating Head Linear
Type Of Operator Spring return plunger metal
Type Of Approach Vertical approach, 1 direction
Cable Entry 1 entry tapped for 1/2" NPT cable gland
Number Of Poles 1
Contacts Type And Composition 1 C/O
Contact Operation Snap action
Switch Actuation On end
Electrical Connection Screw-clamp terminals 1 x 0.75...2 x 1.5 mm²
Contacts Insulation Form Zb
Number Of Steps 1
Positive Opening Without
Minimum Force For Tripping 20 N
Maximum Actuation Speed 1.64 ft/s (0.5 m/s)
Repeat Accuracy 0.1 mm on the tripping points with 1 million operating cycles
Ie Rated Operational Current 3 A 240 V, AC-15, A300 EN/IEC 60947-5-1 appendix A 0.27 A 250 V, DC-13, Q300 EN/IEC 60947-5-1 appendix A
Ithe Cnvtl Enclosed Therm Crrt 10 A
Ui Rated Insulation Voltage 300 VUL 508 500 V 3)IEC 60947-1 300 VCSA C22.2 No 14
Resistance Across Terminals 25 MOhm IEC 60255-7 category 3
Uimp Rated Imp Wstd Voltage 6 kV IEC 60664 6 kV IEC 60947-1
Short-Circuit Protection 10 A cartridge fuse gG
Electrical Durability 5000000 cycles, DC-13, inductive, 120 V, 4 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C 5000000 cycles, DC-13, inductive, 24 V, 10 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C 5000000 cycles, DC-13, inductive, 48 V, 7 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C
Mechanical Durability 30000000 cycles
Width 1.69 in (43 mm)
Height 3.31 in (84 mm)
Depth 1.42 in (36 mm)
Product Weight 0.95 lb(US) (0.43 kg)
Terminals Description ISO n°1 (13-14)NO (11-12)NC
Shock Resistance 50 gn 11 ms IEC 60068-2-27
Vibration Resistance 25 gn 10…500 Hz)IEC 60068-2-6
IP Degree Of Protection IP66 IEC 60529
IK Degree Of Protection IK07 EN 50102
Overvoltage Category Class I IEC 61140 Class I NF C 20-030
Ambient Air Temp For Op -13…158 °F (-25…70 °C)
Ambient Air Temp For Storage -40…158 °F (-40…70 °C)
Protective Treatment TC
Product Certifications CSA CCC UL
Standards UL 508 IEC 60947-5-1 CENELEC EN 50041 CSA C22.2 No 14 EN 60947-5-1 EN 60204-1 IEC 60204-1
Category 22411 - LIMIT SWITCHES,IEC,XCKJ
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews